• All loads
MUST
be disconnected from the generator. Never start or stop the engine with electrical devices plugged in to
the receptacles.
• Turn the engine START/ON/OFF switch to the “OFF” position.
• Turn the fuel valve to the “OFF” position.
Receptacles and Extension Cords
Only use high quality, well-insulated, grounded extension cords in good condition with generator receptacles. Extension
cords should be adequately sized for load and kept as short as possible to minimize voltage drop. Follow equipment
manufacturer’s power rating when selecting receptacle and extension cord.
This generator is equipped with the following receptacles:
How to Stop Engine (See fig 12-14)
ON
OFF
START
2
Fig 12
Fig 13
Fig 14
OPERATION
• Four 120 GFCI outlets (NEMA 5-20R).
• One 240 Volt AC, 30Amp Twist-Lock Receptacle (NEMA L14-30).
• 12 Volt 8.3 DC Amp Output
•
120 Volt GFCI duplex receptacles (NEMA 5-20R)
• This receptacle has a 20 Amp push-to reset circuit breaker to protect against overload.
• Each socket is rated to operate 120 Volt, AC, single phase, 60Hz loads requiring up to 2400 watts (2.4 kW) at 20 Amps.
• Use extension cords having a minimum rating of 125 Volts AC, 20 Amps.
Do not connect 3-phase loads to generator.
CAUTION!
16
120 / 240 Volt AC, 30 Amp locking receptacle
•
This receptacle has a 30 Amp push-to reset circuit breaker to protect against overload.
•
This receptacle is rated to operate 120 Volt, AC, single phase, 60Hz loads requiring up to 3600 watts (3.6 kW) at 30
Amps. It is also rated to operate 240 Volt AC, single phase, 60Hz loads requiring up to 7,200 watts (7.2 kW).
•
Use a NEMA L14-30 plug with this receptacle.
•
Use a 4-wire cord rated for 240 Volts AC, 30 Amps to the plug. You can use the same 4-wire cord to operate a 120 Volt
load.