Pulsar MS 1012 Скачать руководство пользователя страница 6

www.pulsar.pl                                                                                        MS1012 

   

 

 

4. Operation and use. 

            4.1 Overload or short circuit of the PSU module output. 

The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load 

of the PSU module exceeds Imax 

(load 110% ÷ 150% @25ºC of the PSU module  power), the output voltage is 

automatically cut off and indicated by the green diode going off. To restore the output power, cut off the output load 
for approximately 1 minute. 

In case of of the short-circuit to the AUX, BAT output, or incorrect connection of the battery, the fuse F

BAT

 in 

the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the 
replacement of the fuse. 

 

4.2 Battery-assisted operation 

              In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

The PSU module is not equipped with a discharged battery disconnection system. 
 

4.3 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU module  from the 

power supply network. The PSU module  does not require performing any specific maintenance measures, however, in 
the case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse 
replacement, use a replacement of the same parameters. 

 
 

 

WEEE MARK 

 

According to the EU WEE Directive 

– It is required not to dispose of electric or electronic waste as 

unsorted municipal waste and to collect such WEEE separately. 

CAUTION!

 

The power supply  module unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed 

of but recycled according to the applicable law. 

 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 