7
5. Operation and use.
5.1. Overload or short circuit of the PSU module output.
The AUX1÷AUXn PSU outputs are protected against short circuit by glass fuses. Activation of the protection (glass fuse
blowing) is indicated by shutting down green LED nearby appropriate outputs fuse on the PSU module and illuminating the red
LED FPS. In case of damage, replace the fuse (compatible with the original). As a precaution, it is possible to use fuses with a
higher current (up to 2 A) and a fast blow characteristic (F), which will increase the current-carrying capacity of the given output.
However, this does not affect the overall current capacity of the power supply.
5.2. Operation of the PSU OVP system.
If the OVP system is activated, the output voltage is automatically cut off. Operation can be resumed after
disconnecting the PSU from 230 V after approx. 1 minute.
6. Maintenance.
Any and all maintenance operations may be performed following the disconnection of the PSU from the power
supply network. The PSU does not require performing any specific maintenance measures, however, in the case of
significant dust rate, its interior is recommended to be cleaned with compressed air.