www.pulsar.pl HPSBOC5012C
5
1.4 Specifications:
- electrical parameters (tab.3)
- mechanical parameters (tab.4)
- operation safety (tab.5)
- operating parameters (tab.6)
Electrical parameters (tab. 3)
Mains supply
176÷264V AC
Current up to
0.95A@230VAC
Supply power
100W max.
Efficiency
80%
Output voltage
11V÷ 13,8V DC – buffer operation
9,5V÷13,8V DC – battery-assisted operation
Output current
6 A + 1A battery charge
5 A + 2A battery charge
Output current t
AMB
<30°C
6 A + 1,0A battery charge - refer to chart 1
5A + 2,0A battery charge - refer to chart 1
Output current t
AMB
=40°C
4,9 A + 1A battery charge - refer to chart 1
3,9 A + 2A battery charge - refer to chart 1
Voltage adjustment range
12÷14VDC
Ripple
120mV p-p max.
Battery charge current
1A or 2A max. @ 17Ah (± 5%) – jumper selectable
Short-circuit protection SCP
Electronic, automatic recovery
Overload protection OLP
105-150% of power supply, automatic recovery
Battery circuit protection SCP and reverse
polarity connection
polymer fuse
Surge protection
varistors
Overvoltage protection OVP
>16V (automatic return)
Excessive discharge protection UVP
U<9,5 V (± 5%) – disconnect of connection battery
Tampering protection system:
- TAMPER – indicating unwanted opening of the
PSU’s enclosure
- a microswitch, NC contacts (enclosure closed)
0,5A@50V DC (max.)
LED indication:
- AC diode indicating AC power status
- AUX diode indicating DC power status at
the PSU output
- red, normal status – on, failure: off
- green, normal status – on, failure: off
Technical outputs:
- FAC; output indicating AC power failure
- FPS; output indicating DC absence/PSU failure
-FLB output indicating battery low voltage
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s.
CAUTION! In Fig.2. the contact set in the potential-free
status corresponds to a state with no AC power (AC
power failure).
- OC type, 50mA max., normal status: L (0V) level,
failure: hi-Z level, time lag: 10s.
- OC type, 50mA max., normal status: L (0V) level,
failure: hi-Z level
- OC type, 50mA max., normal status: (U
BAT
>11,5V): L
(0V) level,
failure: (U
BAT
<11,5V): hi-Z level
Mechanical parameters (tab. 4)
Enclosure dimensions
285 x 297 x 80 +8 (280 x 292 x 80) (WxHxD)
Fixation
See figure 2
Fitting battery
17Ah/12V (SLA) max.
Net/gross weight
2,37kg / 2,57kg
Enclosure
Steel plate, DC01 0,7mm colour: RAL 9003
Closing
Cheese head screw x 2 (at the front), (lock assembly possible)
Connectors
Power supply:
Φ
0,63-2,50 (AWG 22-10)
Outputs:
Φ
0,63-2,50 (AWG 22-10), battery output BAT: 6,3F-2,5
TAMPER output: wires
Notes
The enclosure does not adjoin the assembly surface so that cables can be led