www.pulsar.pl                                                      HPSBOC5012C            

 

 

5

 

1.4 Specifications:  
- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operating parameters (tab.6) 

      Electrical parameters (tab. 3) 

Mains supply 

176÷264V AC  

Current up to 

0.95A@230VAC  

Supply power 

100W max.  

Efficiency 

80% 

Output voltage 

11V÷ 13,8V DC – buffer operation 
9,5V÷13,8V DC – battery-assisted operation 

Output current 

6 A + 1A battery charge 
5 A + 2A battery charge 

Output current t

AMB

<30°C 

6 A + 1,0A battery charge - refer to chart 1 

5A + 2,0A battery charge - refer to chart 1 

Output current t

AMB

=40°C 

4,9 A + 1A battery charge - refer to chart 1 

3,9 A + 2A battery charge - refer to chart 1 

Voltage adjustment range 

12÷14VDC 

Ripple 

120mV p-p max. 

Battery charge current 

1A or 2A max. @ 17Ah (± 5%) – jumper selectable 

Short-circuit protection SCP 

Electronic, automatic recovery 

Overload protection OLP 

105-150% of power supply, automatic recovery 

Battery circuit protection SCP and reverse 
polarity connection 

polymer fuse 

Surge protection 

varistors 

Overvoltage protection OVP 

>16V (automatic return)

 

Excessive discharge protection UVP 

U<9,5 V (± 5%) – disconnect of connection battery 

Tampering protection system: 
- TAMPER – indicating unwanted opening of the 
PSU’s enclosure 

- a microswitch, NC contacts (enclosure closed) 
0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 
- AUX diode indicating DC power status at 
the PSU output 

- red, normal status – on, failure: off 
- green, normal status – on, failure: off 

Technical outputs: 

- FAC; output indicating AC power failure 

 
 
 
 
 
 
 
 
- FPS; output indicating DC absence/PSU failure 
 
 
 
-FLB output indicating battery low voltage 
 
 

 
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
CAUTION!  In  Fig.2.  the  contact  set  in  the  potential-free 
status  corresponds  to  a  state  with  no  AC  power  (AC 
power failure). 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level, time lag: 10s. 
 
 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level  
 
 
- OC type, 50mA max., normal status: (U

BAT

 >11,5V): L 

(0V) level, 
 failure: (U

BAT

 <11,5V): hi-Z level 

 
Mechanical parameters (tab. 4) 

Enclosure dimensions 

285 x 297 x 80 +8  (280 x 292 x 80) (WxHxD) 

Fixation 

See figure 2 

Fitting battery 

17Ah/12V (SLA) max. 

Net/gross weight 

2,37kg / 2,57kg 

Enclosure  

Steel plate, DC01 0,7mm colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front),  (lock assembly possible) 

Connectors 

Power supply: 

Φ

0,63-2,50 (AWG 22-10) 

Outputs: 

Φ

0,63-2,50 (AWG 22-10), battery output BAT: 6,3F-2,5  

TAMPER output: wires  

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led 

Содержание HPSBOC 7012C

Страница 1: ...HPSBOC 7012C v 1 0 HPSBOC 13 8V 6A 17Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 1 from 22 01 2013 Supercedes...

Страница 2: ...SU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised vol...

Страница 3: ...1 The block diagram of the PSU 1 3 Description of the module s components and connectors Table 1 Elements of the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED...

Страница 4: ...4 Fig 2 The view of the PSU Description of PSU components and connectors tab 2 fig 3 lement no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 3 Output terminals of the PSU...

Страница 5: ...n system TAMPER indicating unwanted opening of the PSU s enclosure a microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status AUX diode indicating DC...

Страница 6: ...llation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and n...

Страница 7: ...It can cause a device failure or an electric shock 4 Connect the receivers cables to the terminals V V of the PSU module 5 Connect the power 230V 6 Connect the battery mind the colours battery output...

Страница 8: ...OC type output Under normal status UBAT 11 5V the output is connected to ground L level 0V In case of decrease of battery voltage UBAT 11 5V the output is switched into high impedance state hi Z Fig 4...

Страница 9: ...at within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs...

Отзывы: