background image

www.pulsar.pl                                                      HPSBOC3524C                                                              

GREEN POWER plus

 

 

6

 

Mechanical parameters (tab. 4). 

Dimensions 

W=400, H=350, D+D

1

=92+8 [+/- 2mm] 

W

1

=405, H

1

=355 [+/- 2mm] 

The dimensions of the 
battery compartment 

370x170x80mm (WxHxD) max 

Fixation 

See figure 3 

Net/gross weight 

3,5kg/ 3,8kg 

Enclosure  

Steel plate, DC01 0,7mm colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front),  lock assembly possible 

Connectors 

Power-supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: Φ0,63-2,50 (AWG 22-10) 
Battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 

        
      

Operation safety (tab.5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

       
      Operating parameters (tab.6)

 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 

2. Installation. 

 

2.1 Requirements. 

The  buffer  PSU  shall  be  mounted  by  a  qualified  installer  with  appropriate  permissions  and  qualifications  for  

230V  AC  installations  and  low-voltage  installations  (required  and  necessary  for  a  given  country).  The  device  shall  be 
mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max.  without 
condensation)  and  the  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that  guarantees 

sufficient convectional air-flow through ventilating holes of the enclosure. 

 
 
 
 
 
 
 
 

Содержание HPSBOC 3524C

Страница 1: ...HPSBOC 3524C v 1 1 HPSBOC 27 6V 3A 2x17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016 GREEN POWER plus ...

Страница 2: ...ircuit of the PSU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilized voltage of 24V DC 15 The PSU provides voltage of U 27 6V DC Current efficiency 1 Output current 3A 0 5A battery charge 2 Output current 2 5A 1A battery charge Total device current battery ...

Страница 3: ...the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC power 3 LED indicating correct battery voltage 4 EPS AC absence technical output relay type 5 PSU output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PS...

Страница 4: ...ulsar pl HPSBOC3524C GREEN POWER plus 4 Fig 2 The view of the PSU Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of the PSU Fig 3 The view of the PSU ...

Страница 5: ...y connection polymer fuse Surge protection varistors Overvoltage protection OVP 32V automatic recovery Excessive discharge protection UVP U 19V 5 disconnect of connection battery Tampering protection system TAMPER indicating unwanted opening of the PSU s enclosure a microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status AUX diode indicating DC p...

Страница 6: ...n 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500V DC Operating parameters tab 6 Operating temperature 10ºC 40ºC see chart 1 Storage temperature 20ºC 60ºC Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insulation unacceptable Vibrations and im...

Страница 7: ...protection circuit shall be performed with a particular care i e the yellow and green wire coat of the power cable shall stick to one side of the terminal marked with symbol on the PSU enclosure Operation of the PSU without the properly made and fully operational shock protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 4 Connect the receivers cables to the termin...

Страница 8: ...vel 0V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION In the Fig 2 the set of contacts shows a potential free status of the relay which corresponds to a state with no DC power PSU failure LoB technical output indicating battery voltage OC type outp...

Страница 9: ...nto a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing an...

Страница 10: ...ipal waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the applicable law Pulsar Siedlec 150 32 744 Łapczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl ...

Отзывы: