Pulsar HPSBOC 1824B Скачать руководство пользователя страница 5

www.pulsar.pl

                                                      

HPSBOC1824B  

         

 

5

 

Surge protection 

varistors 

Overvoltage protection OVP 

>32V (automatic recovery) 

Excessive discharge protection UVP 

U<19 V (± 5%) – disconnection of battery terminal 

Tampering protection system: 
- TAMPER – indicating unwanted opening of the 
PSU’s enclosure 

- a microswitch, NC contacts (enclosure closed) 
0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 
- AUX diode indicating DC power status at 
the PSU output 

 
- red, normal status – on, failure: off 
- green, normal status – on, failure: off  

Technical outputs: 

- FAC; output indicating AC power failure 

 
 
 
 
 
- FPS; output indicating DC absence/PSU failure 
 
 
-FLB output indicating battery low voltage 
 
 

- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
CAUTION!  In  Fig.2.  the  contact  set  in  the  potential-free 
status  corresponds  to  a  state  with  no  AC  power  (AC 
power failure). 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level, time lag: 10s. 
 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level  
 
- OC type, 50mA max., normal status: (U

BAT

 >23V):  

L (0V) level, 
 failure: (U

BAT

 <23V): hi-Z level 

 
Mechanical parameters (tab. 4) 

Enclosure dimensions 

285 x 297 x 80+8  (280 x 292 x 80) (WxHxD)

 

Fixation 

See figure 3 

Fitting battery 

2x 7Ah/12V (SLA) max. 

Net/gross weight 

2,20kg / 2,40kg 

Enclosure  

Steel plate, DC01 0,7mm colour: RAL 9003 

Closing 

Cheese screw x 2 (at the front),  (lock assembly possible) 

Connectors 

Power-supply: 

Φ

0,63-2,50 (AWG 22-10) 

Outputs : 

Φ

0,63-2,50 (AWG 22-10) 

Battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led 

    Operation safety (tab.5) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

     Operating parameters (tab.6) 

Operating temperature 

-10ºC...+40ºC (see: chart 1) 

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Содержание HPSBOC 1824B

Страница 1: ...HPSBOC 1824B v 1 0 HPSBOC 27 6V 1 5A 2x7Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 2 from 07 03 2013 Supersedes edition 1 from 13 02 2013...

Страница 2: ...r PSU is intended for uninterrupted supply to devices that require stabilised voltage of 24 V DC 15 The PSU provides voltage of U 27 6 V DC with output current of I 1 5A 0 3A for battery charge In cas...

Страница 3: ...e 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8 VA...

Страница 4: ...y 77 Output voltage 22V 27 6V DC buffer operation 19V 27 0V DC battery assisted operation Output current 1 5A 0 3A battery charge Output current tAMB 30 C 1 5 A 0 3A battery charge refer to chart 1 Ou...

Страница 5: ...ers tab 4 Enclosure dimensions 285 x 297 x 80 8 280 x 292 x 80 WxHxD Fixation See figure 3 Fitting battery 2x 7Ah 12V SLA max Net gross weight 2 20kg 2 40kg Enclosure Steel plate DC01 0 7mm colour RAL...

Страница 6: ...over the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Inst...

Страница 7: ...s permanently illuminated In case of decrease of battery voltage UBAT 23V the diode is off 3 2 Technical outputs The PSU has indication outputs FAC absence of AC supply output OC type output that indi...

Страница 8: ...switched into a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminal...

Страница 9: ...t within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs o...

Отзывы: