Pulsar HPSB 5048C Скачать руководство пользователя страница 5

www.pulsar.pl

                                                               

HPSB5048C                                                    

GREEN POWER

 

 

 

5

 

W

H

D

LED indication:  
- AC diode indicating AC power status 
- DC diode indicating DC power status at 
the PSU output 

 
- red, normal status 

– on, failure: off 

- green, normal status 

– on, failure: off 

 
      Table 3. Mechanical parameters  

Enclosure dimensions 

420 x 375 x 182+8  [mm] (WxHxD) 

Fixation 

see figure 2 

Fitting battery 

4x17Ah/12V (SLA) max. 
370x175x165mm (WxHxD) max  

Net/gross weight 

7,40/ 7,90 kg 

Enclosure  

Steel plate DC01, thickness: 1,0mm, colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front), lock assembly possible 

Connectors 

Power supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: Φ0,63-2,50 (AWG 22-10),  
Battery output BAT: 

Ф6/1,5mm

2

 

TAMPER output: wires  

Notes 

The enclosure does not touch the assembly surface so that cables can be led. 
Forced cooling - built-in fan. 

       

       Table 4. Operation safety  

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 

Table 5. Operating parameters 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-

20ºC...+60ºC 

Environmental class 

II 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 
 
 
 
 
 

 

Содержание HPSB 5048C

Страница 1: ...HPSB 5048C v 1 0 HPSB 54V 5A 4x17Ah Buffer switch power supply unit EN Edition 2 from 24 10 2016 Supercedes the edition 1 from 18 03 2016...

Страница 2: ...Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical des...

Страница 3: ...2 Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 Batter...

Страница 4: ...current tAMB 40 C 3A 0 5A battery charge refer to chart 1 2 5A 1A battery charge refer to chart 1 1 5A 2A battery charge refer to chart 1 Voltage adjustment range 48 56VDC Ripple 150mV p p max Curren...

Страница 5: ...s can be led Forced cooling built in fan Table 4 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input a...

Страница 6: ...The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected...

Страница 7: ...ed with the discharged battery disconnection system During the battery assisted operation reducing voltage below 38V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and a...

Страница 8: ...equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they...

Отзывы: