www.pulsar.pl                                                      HADOC8012C                                                             

GREEN POWER plus

  

 

 

6

 

     Operating parameters (tab.6) 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 

2. Installation. 

 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that 

guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 
 
Before installation, prepare a PSU load balance. During normal operation, the total current drawn 

by the device may not exceed I = 8A.  Maximum battery charge current: 0,5A. Total device c battery: 

8,5A max

*

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
 
2.2 Installation procedure. 

 

1. Before installation, cut off the voltage in the 230V power-supply circuit.

 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE (PSU module connector). Use a three-core cable (with a yellow and green PE protection wire) to 
make the connection. Lead the cables to the appropriate clips through the insulating bushing of the connection 
board. 
 
 
 
 
 
 
 
 

                                                 

*

 

Refer to chart 1

 

Содержание HADOC 8012C

Страница 1: ...HADOC 8012C v 1 0 HADOC 13 8V 8A 17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 3 from 10 10 2014 Supercedes edition 2 from 05 06 2014 GREEN POWER plus ...

Страница 2: ...sted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for uninterrupted supply to devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output current of I 8A 0 5A for battery charge In case of power decay a battery back up is activated immediately The PSU is constructed based on the switch mode PSU with h...

Страница 3: ...nd connectors Table 1 Elements of the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC power 3 LED indicating correct battery voltage 4 FAC AC absence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 F...

Страница 4: ...ents and connectors tab 2 fig 3 lement no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of the PSU Fig 3 The view of the PSU 1 4 Specifications electrical parameters tab 3 mechanical parameters tab 4 operation safety tab 5 operating parameters tab 6 ...

Страница 5: ...ff green normal status on failure off Technical outputs FAC output indicating AC power failure FPS output indicating DC absence PSU failure FLB output indicating battery low voltage relay type 1A 30VDC 50VAC time lag approx 10s OC type 50mA max normal status L 0V level failure hi Z level time lag 10s relay type 1A 30VDC 50VAC OC type 50mA max normal status L 0V level failure hi Z level relay type ...

Страница 6: ...tional air flow through ventilating holes of the enclosure Before installation prepare a PSU load balance During normal operation the total current drawn by the device may not exceed I 8A Maximum battery charge current 0 5A Total device current battery 8 5A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection sha...

Страница 7: ...normal status AC power permanently illuminated AC power absence is indicated by the AC diode going out Caution LED indicates power absence if the outage lasts 10s green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short circuit or an overload the diode is off green LED Fig 2 element 3 indicates battery voltage level ...

Страница 8: ...Overload or short circuit of the PSU output SCP on In case of overload the output voltage is automatically shut off and so is the LED indicator The restoration of the voltage takes place immediately after the failure overload is over 4 2 Battery assisted operation In case of a main power outage the device is immediately switched into a battery assisted operation The PSU is equipped with the discha...

Страница 9: ...www pulsar pl HADOC8012C GREEN POWER plus 9 ...

Страница 10: ... later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service cent...

Отзывы: