![Pulsar Green Power HPSB 3512C Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/pulsar/green-power-hpsb-3512c/green-power-hpsb-3512c_manual_1624864005.webp)
www.pulsar.pl HPSB3512C
GREEN POWER
5
W
H
D
1.4 Technical parameters:
- electrical parameters (tab.3)
- mechanical parameters (tab.4)
- operation safety (tab.5)
- operation parameters (tab.6)
Electrical parameters (tab. 3)
PSU type
A (EPS - External Power Source)
Mains supply
176÷264V AC
Current up to
0,6A@230VAC
Power frequency
50÷60Hz
Supply power
50W max.
Efficiency
76%
Output voltage
13,8V DC
– buffer operation
9,5V÷13,8V DC – battery-powered operation
Output current t
AMB
<30°C
3A + 0,5A battery charge - refer to chart 1
Output current t
AMB
=40°C
2,1A + 0,5A battery charge - refer to chart 1
Voltage adjustment range
12
÷14VDC
Ripple
100mV p-p max.
Battery charge current
0,5A max. @ 17Ah (
± 5%)
Short-circuit protection SCP
electronic, automatic return
Overload protection OLP
105-150% of the PSU power, automatic return
Battery circuit protection SCP and reverse
polarity connection
PTC polymer fuse
Surge protection
varistors
Overvoltage protection OVP
>16V (automatic recovery)
Excessive discharge protection UVP
U<9,5V (
± 5%) – disconnect of connection battery
Sabotage protection:
- TAMPER output indicating enclosure opening
- microswitch, NC contacts (enclosure closed),
0,5A@50V DC (max.)
LED indication:
- AC diode indicating AC power status
- AUX diode indicating DC power status at
the PSU output
- red, normal status
– on, failure: off
- green, normal status
– on, failure: off
Mechanical parameters (tab. 4)
Dimensions
W=280 H=292 D+D
1
=82+8 [+/- 2 mm]
W
1
=285, H
1
=296 [+/- 2 mm]
Fixation
See figure 2
Fitting battery
17Ah/12V (SLA) max.
180x120x75mm (WxHxD) max
Net/gross weight
2,1 / 2,3 kg
Enclosure
Steel plate DC01, thickness: 0,7mm, colour: RAL 9003
Closing
Cheese screw x 2 (at the front), (lock assembly possible)
Connectors
Power-supply:
Φ0,63-2,50 (AWG 22-10)
Outputs: Φ0,63-2,50 (AWG 22-10)
Battery output BAT: 6,3F-2,5
TAMPER output: wires
Notes
The enclosure does not touch the assembly surface so that cables can be led.
Convectional cooling.