Safety of use (Table 5).
Protection class PN-EN 60950-1:2004
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU
(I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 M
Ω
, 500V/DC
Operation parameters (Table 6).
Operating temperature
-10ºC...+40ºC (see Figure1)
Storing temperature
-20ºC...+60ºC
Relative humidity
20%...90%, no condensation
Vibrations during operation
unacceptable
Surges during operation
unacceptable
Direct insolation
unacceptable
Vibrations and surges during transport
According
to
the
PN-83/T-42106
standard
Diagram 1. Acceptable output current from the PSU depending on ambient temperature.
2. Installation.
2.1. Requirements.
The buffer PSU should be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC and low-voltage installations. The unit should be
mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative humidity
(RH=90% maximum, no condensation) and temperature range from -10°C up to +40°C. The power supply sh ould
operate in a vertical position in order to provide free and convectional air flow through ventilating holes of the
enclosure.
The power supply load balance should be done before installation:
1. Output current 8x1A + 1A battery charging
2. Output current 8x0,87A + 4A battery charging
Total current of the rec battery is max. 11A.
The power supply is designed for a continuous operation and is not equipped with a power-switch.
Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the user
should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an
appropriate fuse in the fuse box). The electrical system shall be made in accordance with applicable standards
and regulations.