15 

 6.2.1. 

Voltage indicator  „Uo1”, „Uo2”  

   

 

 

Voltage indicator displays the measured output voltage at the AUX1 and AUX2 outputs. If the voltage drops 

below 26V or exceeds 29.2V,  the PSU will indicate a failure.  
 

The resolution of voltage measurement is 0.1V and should be treated with caution. If a greater accuracy is 

required, use a multimeter. 
 

6.2.2. 

Total current of the receivers indicator „Io” 

 

 

Total output current indicator displays the measured output current drawn from the AUX1 and AUX2 

outputs. If the value of total current is exceeded, the power supply unit will indicate a failure. 

 

Io = IAUX1 + IAUX2 

 

 

The resolution of current measurement is 0.1A and should be treated with caution. If a greater accuracy is 

required, use a multimeter. 
 

6.2.3. 

Resistance of the battery circuit indicator  „bre” 

 

 

Resistance of the battery circuit indicator  displays the measured resistance of the battery circuit of the 

PSU. The resistance value is affected by: 
- The quality of the batteries 
- The quality of the battery cables and connections 
- The quality of the FBAT fuse 
 
If the resistance value increases ab

ove 300 mΩ, the power supply unit will indicate a failure. 

 

The measurement result is displayed with a resolution of 0.01 ohm. 
 

6.2.4. Battery temperature indicator  

„t°C”   

 

 

Battery voltage indicator  displays the measured temperature of the batteries. The temperature is used by 

the automatic control system for compensation of the battery charging voltage. 
 

The measurement result is displayed with a resolution of 

1°C. 

 

6.2.5. 

230V AC mains voltage indicator „UAC”   

 

 

230V AC mains voltage indicator displays the measured mains voltage at the  230V AC mains terminals. If 

the voltage drops below 195V AC or exceeds 254V AC,  the power supply unit will indicate a failure. 
 

 

The resolution of current measurement is 1V and should be treated with caution. If a greater accuracy is required, 
use a multimeter. 

6.2.6. Failure 

history “FLh”

 

 

The PSU remembers 30 last failures in non-volatile memory, which can be reviewed later. 

In order  to  review  the  failures,  use  the  "<"  or  ">"  button  to set the 

FLh

  parameter  and  confirm  by  pressing  "OK". 

The display will show the number of failure in the memory and its code. Pressing the "OK" button again will display 
next failure in the memory.  

 
The  memory  of  the  new  power  supply  remembers  the  events  that  are  the  result  of  the  efficiency  tests 
carried out at the production stage. 
 

 
 
 
 
 
 

press „<” or „>” button to set the „FLh” parameter on the display 

 
 
                                                                                                                                                             
 
 
 
 

Содержание EN54-3A28

Страница 1: ...EN54 3A28 v 1 1 EN54 27 6V 3A 2x28Ah power supply for fire alarm systems EN Edition 4 from 12 01 2016 Supersedes the edition 3 from 26 08 2014 LED Version...

Страница 2: ...failure codes and information messages 17 6 3 PSU CONFIGURATION 19 6 3 1 Performing battery test tSt 20 6 3 2 EXTo output ON OFF Eto 21 6 3 3 Setting the delay time for EPS output EPS 21 6 3 4 Acousti...

Страница 3: ...0 7 7 BATTERY TEMPERATURE MEASUREMENT 31 7 8 STANDBY TIME 31 8 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 32 8 1 COMMUNICATION VIA THE USB TTL INTERFACE 32 8 2 ETHERNET NETWORK COMMUNICATION 3...

Страница 4: ...port with implemented MODBUS RTU protocol Power Security is a free application for remote monitoring of power supplies for PC and Android Phones remote monitoring options WiFi Ethernet RS485 USB remo...

Страница 5: ...al Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial co...

Страница 6: ...YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Battery fuse failure indication YES YES Charging circ...

Страница 7: ...Output current Imax b 3A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing RAL 3001 red with battery housing for two...

Страница 8: ...ery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging 11 Terminals AC AC power input EPS FLT technical output of AC power failur...

Страница 9: ...onents of the PCB of the EMC filter Fig 3 Component No Description FMAINS fuse in the power supply circuit 230V T3 15A 250V L N power supply connector 230V AC PE protective connector Connector for con...

Страница 10: ...module INTR INTE INTW 5 Place to install the EN54 LB4 or EN54 LB8 fuse module 6 TAMPER microswitch contacts of antisabotage protection NC 7 EMC filter module see Table 2 Fig 3 8 2x28Ah batteries 9 Emb...

Страница 11: ...free and convectional air flow through ventilating holes of the casing As the PSU performs a periodic battery test measuring the resistance of connections special attention should be paid to the prope...

Страница 12: ...output of PSU failure APS FLT technical output of the battery failure EXTi input of collective failure 5 Install the batteries in a designated area of the enclosure see Fig 4 Connect the batteries wit...

Страница 13: ...escription Additional information moves the pointer on the screen next screen selection selection approval green LED indicating 230V AC voltage yellow LED indicating exceeding the Imax a current or po...

Страница 14: ...7 The description of display symbols Symbol Description Additional information AUX1 output voltage V Factory setting 27 6V 20 C AUX2 output voltage V Factory setting 27 6V 20 C Total current of the re...

Страница 15: ...he power supply unit will indicate a failure The measurement result is displayed with a resolution of 0 01 ohm 6 2 4 Battery temperature indicator t C Battery voltage indicator displays the measured t...

Страница 16: ...aneously indicate several failures Thanks to this solution codes of all failures and their priority can be previewed in the FLc menu In the FLc menu each press of the OK button on the panel displays t...

Страница 17: ...S FLT ALARM No AC mains supply FMAIN fuse failure F02 AUX1 fuse fail PSU FLT ALARM Blown FAUX1 fuse AUX2 fuse fail Blown FAUX2 fuse F03 BAT fuse fail APS FLT ALARM Blown FBAT fuse Short circuit in the...

Страница 18: ...voltage PSU FLT ALARM Mains supply below 195V AC Section 6 2 5 F21 PSU cover opened PSU FLT ALARM Section 6 6 F50 F54 Internal supply fail PSU FLT ALARM service codes F60 No communication PSU FLT ALAR...

Страница 19: ...ration The PSU is equipped with a configuration menu that allows to configure the settings by changing or the activation of some of its parameters The figure illustrating the configuration menu struct...

Страница 20: ...ission trS Determines the speed of communication 9 6k 115 2k factory setting Section 6 3 7 Parity of the transmission trP Determines the method of communication 8N2 8E1 factory setting 8O1 Section 6 3...

Страница 21: ...ost buttons on the LED panel the tSt parameter will be displayed use the or buttons to display the Eto parameter press OK The current status of the relay will be displayed use the or buttons to in ord...

Страница 22: ...icated acoustically The frequency and number of signals depend on the type of event Table 11 Acoustic indication No Description Event 1 1 signal every 10s battery mode 230V AC power failure 2 1 signal...

Страница 23: ...y if no buttons are pressed within 5 minutes If the display is in the blackout mode pressing any button will reactivate the display simultaneously press the rightmost and leftmost buttons on the LED p...

Страница 24: ...er press OK The current address of the PSU will be displayed use the or buttons in order to set the address 1 247 address of the PSU during the communication with the computer confirm by pressing OK i...

Страница 25: ...he PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 i...

Страница 26: ...SU FLT output indicating PSU failure The output indicates the PSU failure Under normal status during correct operation the output is closed In case of PSU failure it will switch into the open position...

Страница 27: ...the EXT IN input The connection of external devices to the EXT IN input is shown in the electrical diagram below OC outputs open collector or relay outputs can be used as the source of the signal Fig...

Страница 28: ...rcuit on the line could cause damage to other receivers connected to the same output The solution is provided by the optional fuse module EN54 LB4 4 channel or EN54 LB8 8 channel while its mounting lo...

Страница 29: ...ime and overload level microprocessor may disconnect the AUX1 and AUX2 outputs and switch into the battery assisted operation Restart will occur after 1 minute PSU overload is indicated by the PSU FLT...

Страница 30: ...Deep discharge battery protection UVP The PSU is fitted with the disconnection system and the battery discharge indication If the voltage at the battery terminals drops below 20V 0 2V during battery a...

Страница 31: ...in battery mode should be limited Required minimum battery capacity to work with the PSU can be calculated with the following formula QAKU 1 25 Id Iz Td Ia Iz Ta 0 05 Ic where QAKU The minimum batter...

Страница 32: ...wer supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 7 8 8 1 Communication via the USB TTL interface The easiest way of co...

Страница 33: ...against adverse environmental conditions Fig 17 Ethernet network communication using the RS485 INTRE interface 8 3 The Wi Fi wireless communication The Wi Fi wireless communication can be implemented...

Страница 34: ...t adverse environmental conditions Fig 19 The Wi Fi communication using the RS485 WIFI INTRW interface 8 4 RS485 network communication Another type of network communication is the RS485 communication...

Страница 35: ...f the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orien...

Страница 36: ...ort circuit protection SCP F5A current limit FAUX melting fuse failure requires fuse replacement Overload protection OLP Hardware Software Battery circuit protection SCP and reverse polarity connectio...

Страница 37: ...ins supply 0 51 2 AWG 24 12 Outputs 0 51 2 AWG 24 12 Battery outputs BAT 6 M6 0 2 5 Cable glands PG9 cable diameter 4 8mm PG11 cable diameter 5 10mm Notes The enclosure does not adjoin the mounting su...

Страница 38: ...after installation re tighten all threaded connections see Fig 2 11 and Fig 3 2 CAUTION According to the recommendations of the CNBOP and VdS institutes the batteries should be replaced after four yea...

Отзывы: