11. Technical inspections and maintenance. 

 
Technical  inspections  and  maintenance  can  be  performed  after  disconnecting  the  power  supply  from  the  power 
network.  The  PSU  does  not  require  any  specific  maintenance,  however,  its  interior  should  be  cleaned  with 
compressed  air  if  it  is  used  in  dusty  conditions.  In  case  of  fuse  replacement,  use  only  compatible  replacement 
parts. 
Technical inspections should be carried out not less frequently than once per year. During the inspection, check the 
batteries and run the battery test. 
4 weeks after installation, re-tighten all threaded connections, see Fig. 2 [11]  and Fig. 3 [2]. 

 

11.1. Battery replacement of the LCD panel. 

Estimated operating time of battery type CR2032 is about six years. After this period, the battery will need to be 
replaced. 
Battery replacement of the LCD panel should be done during mains operation or battery-assisted operation in order 
to avoid resetting the time settings. 

 

CAUTION! 
Removed  batteries  should  be  stored  in  a  designated  collection  point.  Do  not  reverse  the 
polarity  of  the  batteries.  Do  not  use  batteries  of  different  types.  Improper  use  of  the  battery 
may lead to explosion. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание EN54-2A17LCD

Страница 1: ...EN54 2A17LCD v 1 0 EN54 27 6V 2A 2x17Ah LCD power supply for fire alarm systems EN Edition 3 from 26 08 2014 Supersedes the edition 2 from 02 06 2014 LCD Version ...

Страница 2: ...LOSURE OPENING TAMPER 23 6 8 INCREASING THE NUMBER OF OUTPUTS WITH OPTIONAL EN54 LB4 OR EN54 LB8 FUSE MODULES 23 6 9 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP 24 6 10 PSU OVERLOAD 24 6 11 INDICATION OF EXCEEDING THE IMAX A CURRENT 24 6 12 SHORT CIRCUIT OF THE PSU OUTPUT 24 7 PSU SETTINGS 25 7 1 PASSWORD 25 7 1 1 Entering the password 25 7 1 2 Changing the password 26 7 1 3 Disabling the passwor...

Страница 3: ... 39 8 8 STANDBY TIME 39 9 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 40 9 1 COMMUNICATION VIA THE USB TTL INTERFACE 40 9 2 ETHERNET NETWORK COMMUNICATION 40 9 3 THE WI FI WIRELESS COMMUNICATION 41 9 4 RS485 NETWORK COMMUNICATION 42 9 5 POWERSECURITY PROGRAM 43 10 TECHNICAL PARAMETERS 44 Table 15 Electrical parameters 44 Table 16 Mechanical parameters 45 Table 17 Safety of use 45 Table 18 O...

Страница 4: ...am PowerSecurity to monitor the performance of the PSU remote control options WiFi Ethernet RS485 USB remote battery test required additional modules cooperation with optional EN54 LB4 or EN54 LB8 fuse modules optical indication of PSU overload OVL acoustic indication of failure adjustable delay for 230V AC power loss indication output of collective failure ALARM input of collective failure EXTi c...

Страница 5: ...ual CD Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial connection cable Keys to lock the power supply 2 pieces Cable tie 190x4 8 12 pieces ...

Страница 6: ... circuit YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Blown battery fuse indication YES YES Charging circuit failure indication YES YES Low output voltage indication YES YES High output voltage indication YES YES Indication of power supply failure YES YES Overvoltage protection YES YES Short circu...

Страница 7: ...utput current Imax b 2A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing color RAL 3001 red with battery housing for two 17Ah 12V batteries The PSU works with maintenance free lead acid batteries made with AGM technology or gel technology 4 2 Block diagram The PSU has been manufactured based on a high efficiency sy...

Страница 8: ... AC power AUX1 AUX1 output voltage AUX2 AUX2 output voltage OVL PSU overload APS battery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging Terminals AC AC power input EPS FLT technical output of AC power failure indication open AC power failure close AC power O K PSU FLT technical output of PSU failure indication open failure ...

Страница 9: ... Components of the PCB of the EMC filter Fig 3 Element No Description FMAINS fuse in the power supply circuit 230V T1A 250V L N power supply connector 230V AC PE protective connector Connector for connecting the PSU Fig 3 The view of the EMC filter ...

Страница 10: ... additional module INTR INTE INTW Place to install the EN54 LB4 or EN54 LB8 fuse module TAMPER microswitch contacts of antisabotage protection NC EMC filter module see Table 2 Fig 3 2x17Ah batteries Embossing for cable gland Embossing for cable gland WiFi antenna or cable communication interface Embossings for concealed wires Lock Battery connectors positive BAT red negative BAT black Fig 4 The vi...

Страница 11: ... cables Installation cables should be firmly connected to the battery side terminals and to the power supply connector The side walls of the housing include the embossings which should be used to carry out installation cables Use a blunt instrument to make an opening for cable gland from the outside of the housing Then carefully mount the cable gland protecting the PSU from water penetration in th...

Страница 12: ...re see Fig 4 Connect the batteries with the PSU paying special attention to the correct polarity Batteries must be connected in series using the special cable included 6 Switch on the 230V AC supply The corresponding LEDs on the power supply PCB should be ON green AC and green AUX1 and AUX2 Green LB LED should light up while charging 7 Check the current consumption of the receivers taking into acc...

Страница 13: ...rameters which should be displayed Fig 7 Control panel Table 6 The description of the buttons and LEDs of the LCD panel moves the pointer on the screen next screen selection selection approval quit editing without saving starts preview mode green LED indicating AC power green LED AUX1 indicating power at the AUX1 output of the PSU green LED AUX2 indicating power at the AUX2 output of the PSU yello...

Страница 14: ...the LCD Main screen of the LCD displays the basic electrical parameters and indicates the current status of the power supply Fig 9 Main screen of the LCD The resolution of voltage and current measurement is 0 1V and 0 1A respectively The displayed values of voltages and currents should be treated with caution if a greater accuracy is required use a multimeter Table 7 The description of the main sc...

Страница 15: ...y starts the preview menu allowing to choose one of the four available PSU screens Use the or buttons to choose a proper screen and press the SET button to confirm current parameters of the PSU see section 6 4 2 current failures of the PSU see section 6 4 3 parameters of the PSU stored in the memory see section 6 4 4 History of events see section 6 4 5 ...

Страница 16: ... current flashing Imax a exceeded See section 6 10 6 11 PSU failure indication highlighted PSU failure See sections 6 4 6 6 5 Battery failure indication highlighted battery failure See sections 6 4 6 6 5 EXTi input status indication highlighted EXTi input activated See sections 6 4 6 6 6 Current electrical parameters of the PSU UAC mains supply voltage 230V AC UBAT battery voltage TBAT battery tem...

Страница 17: ...are of the highest priority If there are more than five failures at the same time use the or buttons to display the next failure 6 4 4 LCD screen history of the parameters To set the screen press the ESC button use the or buttons to choose the icon and press the SET button to confirm Fig 13 Screen of the history of PSU s parameters During normal operation the PSU records voltage and current parame...

Страница 18: ...inimum the lowest value measured during 5 minutes maximum the highest value measured during 5 minutes of the following parameters UAC mains supply voltage 230V AC UAC MIN mains supply voltage minimum UAC MAX mains supply voltage maximum UAUX1 AUX1 output voltage UAUX1 MIN AUX1 output voltage minimum UAUX1 MAX AUX1 output voltage maximum UAUX2 AUX2 output voltage UAUX2 MIN AUX2 output voltage minim...

Страница 19: ...rying information about the fault type time of occurrence and the values of other electrical parameters In addition the diagnostic system assigns the failure code for a particular event on the basis of the stored parameters In order to preview the history of events use the or buttons It can be done in two modes short mode date time code fault description or full mode with additional information ab...

Страница 20: ...below 26V Battery charging circuit failure F09 Low AUX1 voltage PSU FLT ALARM Output voltage below 26V Low AUX2 voltage F10 Low battery voltage APS FLT ALARM The battery voltage has dropped below 23V during battery assisted operation F11 Low battery volt off APS FLT ALARM the battery voltage has dropped below 20V during battery assisted operation See section 8 4 F12 External input EXTi ALARM Activ...

Страница 21: ...dicates a failure in the battery circuit Under normal status during correct operation the output is closed In case of failure the PSU will switch the output into the open position Failure can be triggered by the following events faulty batteries undercharged batteries disconnected batteries high resistance of the battery circuit battery voltage below 23V during battery assisted operation blown bat...

Страница 22: ...on between the PSU s systems and the attached devices Fig 18 Electrical diagram of the EXT IN input The connection of external devices to the EXT IN input is shown in the electrical diagram below OC outputs open collector or relay outputs can be used as the source of the signal Fig 19 Examples of connections W In the option with external switch the V EXT jumper which polarises the EXT IN input cir...

Страница 23: ... circuit on the line could cause damage to other receivers connected to the same output The solution is provided by the optional fuse module EN54 LB4 4 channel or EN54 LB8 8 channel while its mounting location is provided within the housing see Fig 4 The figure below shows the connection between the power supply fuse module and receivers Fig 21 The connection of fuse module When installing the fus...

Страница 24: ... microprocessor may disconnect the AUX1 and AUX2 outputs and switch into the battery assisted operation Restart will occur after 1 minute PSU overload is indicated by the PSU FLT and ALARM technical outputs 6 11 Indication of exceeding the Imax a current Exceeding the Imax a output current during the power supply operation is indicated by the microprocessor using the LED OVL light overload on the ...

Страница 25: ...e password full access to the PSU s settings User s password locked access to the PSU settings menu Table11 Access ranges PASSWORD Access range Control panel settings PSU settings SERVICE USER Preset passwords user s password 1111 service password 1234 7 1 1 Entering the password If the access to the configuration of the power supply has been blocked by the activation of the service or user passwo...

Страница 26: ...change it To do this choose a password that will be changed user s password or service password and enter the new one 7 1 3 Disabling the password If the password is not required it can be turned off The access to the settings will not be locked after 30 seconds of inactivity To disable the password type 0000 as a new password User password 0000 unlocks the access from the user level Service passw...

Страница 27: ... by pressing the SET button When on the keyboard will be locked automatically if no buttons are pressed within 5 minutes After this time pressing any button on the control panel will display a window with keyboard password request Enter the password using the or buttons as explained above Fig 24 Keyboard password request Entering the correct user s password unlocks the access to the settings from ...

Страница 28: ... 4 6 NO acoustic indication OFF Section 7 2 2 EXTo output ON output ON see section 4 9 OFF output OFF Section 7 2 3 Delay time for EPS output Setting the delay time for AC power failure indication 10s factory setting 1min 10min 30min Section 7 2 4 Communication address 1 247 PSU address required during the communication with the computer 1 factory setting Section 7 2 5 Transmission Defines the spe...

Страница 29: ...t 1 1 signal every 10s battery mode AC power failure 2 1 signal every 10s mains operation Battery failure undercharged batteries 3 2 signals every 10s battery mode Low battery level 4 Fast signals battery mode The PSU will be disconnected because of the battery discharge 5 Constant indication PSU failure section 6 4 6 use the or buttons to display the Acoustic indication menu press the SET button ...

Страница 30: ...l control Z2 jumper must be on Information about the changes in the EXTo output is written in the event log of the PSU use the or buttons to display the EXTo output menu press the SET button the prompt will appear at the end of the line use the or buttons to select ON relay ON OFF relay OFF confirm by pressing the SET button 7 2 4 Setting the delay time for EPS output indicating 230V AC power loss...

Страница 31: ...ters responsible for communication between the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program Communication address allows to identify power supply units in the same communication network use the or buttons to display the Communication address menu press the SET button the prompt will appear at the end of the li...

Страница 32: ...ve the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original settings use the or buttons to display the Transmission menu press the SET button the prompt will appear at the end of the line use the or buttons to set the transmission speed 9 6k 8N1 115 2k 8E1 factory ...

Страница 33: ...he displayed messages Intensity of the LCD backlight can be set in the range from 0 to100 in 10 intervals The display features a function of constant or temporary backlight mode In temporary mode the screen will turn off if no buttons are pressed within 5 minute Fig 26 Control panel screen Table 14 The description of the Control panel screen Position Description Language Available languages Date C...

Страница 34: ... the front panel of the power supply 7 3 2 Setting the date The Date menu in the Control panel menu enables setting the correct date according to which error messages and operation history will be saved Built in real time clock does not take into account leap years and the changes resulting from the switch between summer and winter time These changes should be taken into account when analyzing eve...

Страница 35: ...ss the SET button the prompt will appear next to the hour digits use the or buttons to set the hour press the SET button the prompt will appear next to the minute position use the or buttons to set the minutes press the SET button the prompt will appear next to the seconds position use the or buttons to set the seconds confirm by pressing the SET button 7 3 4 Setting the backlight mode The Backlig...

Страница 36: ...ast of the display text use the or buttons to display the Contrast menu press the SET button the prompt will appear at the end of the line use the or buttons to set the contrast confirm by pressing the SET button 7 3 6 Blinking light indicating failure The Blinking light indicating failure menu enables setting the backlight mode during failure indication When on the blinking light will indicate a ...

Страница 37: ...D RED POWER 37 press the SET button the prompt will appear at the end of the line use the or buttons to select YES blinking light indicating failure ON NO blinking light indicating failure OFF confirm by pressing the SET button ...

Страница 38: ...ase of incorrect connection the FBAT fuse in the battery circuit becomes damaged The return to normal operation is possible only after replacing the fuse and correct connection of the batteries 8 4 Deep discharge battery protection UVP The PSU is fitted with the disconnection system and the battery discharge indication If the voltage at the battery terminals drops below 20V 0 2V during battery ass...

Страница 39: ...ies hence temperature readings should not be confused with the ambient temperature Temperature measurement and compensation of the battery charging voltage can extend the life of the batteries 8 8 Standby time Battery assisted operating depends on battery capacity charging level and load current To maintain an appropriate standby time current drawn from the PSU in battery mode should be limited Re...

Страница 40: ... power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 8 8 9 1 Communication via the USB TTL interface The easiest way of communication between the PSU and the computer is provided by the USB TTL INTU interface This interface allows direct connection between the computer and the PSU and is recognizable by the operating ...

Страница 41: ... mounted in a hermetic enclosure protecting against adverse environmental conditions Fig 31 Ethernet communication using the RS485 Ethernet INTRE interface 9 3 The Wi Fi wireless communication The Wi Fi wireless communication can be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequency band according to the IEEE 802 11 bgn standard The WiFi I...

Страница 42: ...t adverse environmental conditions Fig 33 The The Wi Fi communication using the RS485 WIFI INTRW interface 9 4 RS485 network communication Another type of network communication is the RS485 communication using two wire transmission path To achieve this kind of data exchange the PSU should be equipped with the additional RS485 TTL INTR interface converting data from the PSU into the RS485 standard ...

Страница 43: ... of the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orientation The application enables both the visualization and analysis of the received data Exceeding of the acceptable parameters is indicated by red illumination of the appropriate area or by blinking...

Страница 44: ...voltage protection OVP U 30 5V 0 5V disconnection of the output voltage AUX disconnection automatic return Short circuit protection SCP F3 15A FAUX1 FAUX2 melting fuse failure requires fuse replacement Overload protection OLP Hardware Software Battery circuit protection SCP and reverse polarity connection F5A FBAT melting fuse failure requires fuse replacement Deep discharge battery protection UVP...

Страница 45: ...osure Steel plate DC01 1 2mm color RAL 3001 red Closing Key lock Terminals Mains supply Ф0 51 2 AWG 24 12 Outputs Ф0 51 2 AWG 24 12 Battery outputs BAT Ф6 M6 0 2 5 Cable glands PG9 cable diameter Ф4 8mm PG11 cable diameter Ф5 10mm Notes The enclosure does not adjoin the mounting surface so that cables can be led Convection cooling Table 17 Safety of use Protection class PN EN 60950 1 2007 I first ...

Страница 46: ...stallation cables Mains supply 230V AC L N PE see Table 2 2 OMY 3 x 0 75 mm2 1 5 mm2 AUX1 AUX2 output terminals see Table 1 11 HLGs 2 x 1 5 mm2 2 5 mm2 Indication inputs outputs see Table 1 11 YnTKSY 1 x 2 x 0 8 mm2 Additional indication lines with optional interface FTP 4x2x0 5 cat 5e ...

Страница 47: ...year During the inspection check the batteries and run the battery test 4 weeks after installation re tighten all threaded connections see Fig 2 11 and Fig 3 2 11 1 Battery replacement of the LCD panel Estimated operating time of battery type CR2032 is about six years After this period the battery will need to be replaced Battery replacement of the LCD panel should be done during mains operation o...

Страница 48: ...de warranty repairs at the earliest convenience however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carri...