Shock protection circuit shall be performed with a particular care, i.e.  yellow and green wire coat 

of power cable shall stick to one side of terminal - marked with symbol on PSU enclosure. Operation of 
PSU without the properly made and fully operational shock protection circuit is UNACCEPTABLE! It can 
cause a device failure or an electric shock

 

6.  After  connections  are  correctly  made,  perform  system  checking  procedure  according  to 

instructions of control panel manufacturer. 

       

 

WEEE LABEL 

Waste electrical and electronic equipment must not be disposed of with normal household waste. According to 

the European Union WEEE Directive, waste electrical and electronic equipment should be disposed of 

separately from normal household waste 

In Poland, according to the European Union WEEE Directive, waste electrical and electronic equipment, marked with a crossed 

out wheeled bin symbol, should be disposed of separately from normal household waste. The user is obliged to throw the end-

of-life equipment in a WEEE collection point. WEEE collection points are run by wholesale and retail sellers of this equipment, 

and municipal organizational units operating in the field of collecting municipal waste.  

The proper implementation of these obligations is particularly important when the waste equipment contains hazardous 

components which have a negative impact on the environment and human health.

 

 

 

 

CAUTION! 

The DSO uses sealed lead acid batteries (SLA). Used batteries must be disposed of in accordance with the 

applicable regulations. 

 

 

The warranty conditions

  

The warranty conditions can be found at: 

www.pulsar.pl

  

SEE

 

 

THE WARRANTY CONDITIONS FOR SLA BATTERIES 

- Additional arrangements 

The presented warranty conditions for SLA batteries are valid in conjunction with 

General Warranty Terms

 of the PULSAR company. 

1.

 

The battery will not be considered defective if its capacity during the warranty period has not dropped to 

80 [%] 

of the rated capacity. 

2.

 

The periodic  maintenance of all batteries, including performing the appropriate measurements, shall be performed every

  12

 months 

from  the  installation.    The  measurement  report,  prepared  in  accordance  with  the  guidelines  contained  in  the  "Installation"  section, 

should be sent within two weeks to the company's e-mail address 

[email protected]

. Presentation of the measurement results from all of 

required periodic maintenances is a 

condition for warranty claim

3.

 

The warranty applies only to batteries designed for 

buffer operation. Cyclic batteries are not covered by this warranty.

 

4.

 

The warranty period will be reduced by 50 [%] for each sustained temperature rise of 8 [°C] above nominal operating temperature of 

the battery of 25 [°C]. 

5.

 

The PULSAR company

 is not responsible for:

 

- Batteries with unreadable serial number; 

- Damages resulting from improper charging or installation; 
- Mechanical damages to the enclosure and polarity terminals (clamp caps) caused by the installation, commissioning, and operation of 

the batteries; 
- Damages caused by fire, high temperature (overheating), explosion, or freezing; 

- Damages caused by misuse or negligence; 
- Damages caused by force majeure. 

6.

 

The  PULSAR  company  reserves  the  right  to  verify  battery  operating  conditions  by  reading  the  operating  history  of  the  DSO  power 
supply system. The data can be read remotely or locally by employees of the PULSAR company  

7.

 

In the case of unjustified claim, the claimant may be charged with the travel and manhour costs of a PULSAR employee incurred by the 
PULSAR company. 

8.

 

The warranty is valid only upon presentation of the invoice and delivering the battery subjected to complaint along with a description of 
the defect at the expense of the claimant.

 

 

 

Pulsar sp. j. 

Siedlec 150, 32-744 Łapczyca, Poland 

Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 

e-mail

[email protected]

[email protected]

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

 

Содержание DSO-PRA

Страница 1: ...DSO PRA v 1 0 19 RACK CABINET FOR PRAESENSA DSO SYSTEM EN Edition 2 from 05 05 2021 Supersedes the edition 1 from 15 03 2021 ...

Страница 2: ...NET 7 4 1 THE LZXX PRA SAFETY STRIP 7 4 2 230 V AC LDXXXX VOLTAGE DISTRIBUTION TERMINAL 9 4 3 PSG3LA PANEL FOR OPTICAL AND ACOUSTIC INDICATION 10 4 4 RAWP600RZ FAN PANEL 11 5 CONFI DSO PROGRAM FOR DESIGNERS 13 6 TECHNICAL PARAMETERS 14 Table 9 Parameters of DSO system 14 Table 10 Operation safety 14 Table 11 Operating parameters 14 7 INSTALLATION 15 7 1 REQUIREMENTS 15 7 2 INSTALLATION PROCEDURE 1...

Страница 3: ...with overcurrent fuses surge arresters and a dummy connector single phase or 3 phase power supply 230 V AC LDxxxx voltage distribution terminal grounding terminals protection Class IP30 batteries included mounting bracket for batteries mounting shelves for each cluster enclosure of DSOS24VPU firefighter s microphone available as an option AWO506 End of Line EOL Supervision Board available as an op...

Страница 4: ...1 phase or 3 phase connection which depends on total power consumed by DSOdevices CONFI DSO PRAESENSA program is designed for proper and fast configuration of DSO cabinet based on implemented design parameters program selects a complete power supply system taking into account required backup time 2 2 Electrical scheme Figure 1 shows an exemplary wiring diagram inside a DSO cabinet for a 3 phase 23...

Страница 5: ...ull out shelf will be added to facilitate the use of the microphone The equipment installed inside the cabinet can be accessed via the glass front doors removable side walls and rear doors In addition the use of two types of locks separate for the front and rear doors restricts unauthorized access The cabinet can be mounted on a metal base with a height of 100 mm or wheels allowing it to move free...

Страница 6: ...x1303 mm 600x600x1837 mm 600x600x2103 or 600x800x2103 mm 600x600x2236 or 600x800x2236 mm 600x800x2459 mm Weight 66kg 76kg 89kg 600x600mm 104kg 600x800mm 91kg 600x600mm 106kg 600x800mm 152kg Static load 1000kg Protection class IP30 Notes set includes a base with a height of 100mm optional set of wheels glass front door two types of locks separately for front and rear doors ...

Страница 7: ...NFI DSO PRAESENSA program supporting DSO configuration 4 1 The LZxx PRA safety strip Safety strip is fitted with circuit breakers surge arresters and a dummy connector In right part there is a connector for connecting 230V 400V mains supply from power grid Main overcurrent circuit breaker disconnects 230 V 400 V mains from all system devices In addition to the main switch it is fitted with type 3 ...

Страница 8: ...nce socket Surge arresters Overcurrent circuit breaker of fan Main overcurrent circuit breaker Safety contact strip is connected to mains Access is obtained by removing front cover Connection to power system is shown below Fig 5 Connection to the power system a single phase 230 V AC connection Fig 6 Connection to the power system 3 phase 400 V AC connection ...

Страница 9: ... 3 x 1 5 mm 2 4 mm 2 5 x 1 5 mm 2 4 mm 2 Dimensions Standard RACK 19 H 3U 4 2 230 V AC LDxxxx voltage distribution terminal Voltage distribution terminal is equipped with 230 V connection sockets and it is used to supply components of DSO Depending on number of devices and amount of power consumption terminal can have 1 phase or 3 phase connection 3 phase version enables more uniform load per phas...

Страница 10: ...s must be normally without failure opened in the case of failure they must be closed A voice alarm signal or failure indication triggers the appropriate optical and acoustic indication The button on the front panel allows muting the acoustic signal while the optical signal remains unchanged Once the failure is cleared the optical and acoustic indication will automatically be stopped and the green ...

Страница 11: ...failure terminals are opened Alarm terminals closed Normal operation no failure terminals are opened Failure indication electrical contacts are closed Terminals Ф0 51 2mm AWG 24 12 Dimensions Standard RACK 19 H 1U Example of connection of optical acoustic indication panel to MPS3 PRA DSO controller is presented below Control output connector has SPDT type relay outputs which can be configured for ...

Страница 12: ...from 230 V mains in case of power loss they are switched off Fig 12 Fan unit with a thermostat Table 8 Components of fan panel Element no Description Bimetallic thermostat On off temperature control knob in range 0 60ºC Airflow openings of fan panel 230 V AC power outlet T 315mA fuse socket Fan power switch Table 9 Technical parameters of fan panel Supply voltage 230 V AC 50Hz Current consumption ...

Страница 13: ...onal space in RACK cabinet In next step indicate devices of DSO system that will be powered from system power supply During data input CONFI DSO makes ongoing calculations based on which minimum configuration of power supply system is automatically selected These effects can be observed both in graphic part and in output data area where technical parameters are additionally displayed After complet...

Страница 14: ...or forced cooling 1 1 Depending on DSO configuration Table 10 Operation safety Protection class EN 62368 1 2015 03 AC1 2016 01 I first Protection grade EN 60529 2003 IP30 Electrical strength of insulation between input network circuit and output circuits of PSU I P O P between input circuit and protection circuit I P FG between output circuit and protection circuit O P FG 3000 V AC min 1500 V AC m...

Страница 15: ...circuit is cut off Selection of installation cables should take account 187 of the Regulation of the Minister of Infrastructure on technical conditions to be met by buildings and their location 1 Equipment should be installed in appropriate compartments of cabinet 2 Make additional protective conductor connections between housings of devices and earthing plate set in a ziplock bag 3 Connect batter...

Страница 16: ...company 1 The battery will not be considered defective if its capacity during the warranty period has not dropped to 80 of the rated capacity 2 The periodic maintenance of all batteries including performing the appropriate measurements shall be performed every 12 months from the installation The measurement report prepared in accordance with the guidelines contained in the Installation section sho...

Отзывы: