www.pulsar.pl                                                                        DIN1220                                                                        

 

 

 

Operation safety (tab.4) 

Protection class PN-EN 60950-1:2007 

II (

second)

 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input input and output circuits of the PSU (I/P-O/P) 

 
3000 V/AC min 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC 

Operating specifications (tab.5). 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

 

                          Chart 1. Acceptable output current from the PSU depending on ambient temperature. 
 
 
2. Installation. 
 

2.1 Requirements 
 

The PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 
230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max. 
without condensation) and the temperature from -10°C to +40°C. The PSU shall work in a vertical positi  on that 
guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 

As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed about the method of unplugging (most frequently through separating and assigning an appropriate fuse in 
the fuse-box). The electrical system shall follow valid standards and regulations. 

 

           The device should be installed in the metallic enclosure, distribution board (ICT cabinet) equipped with a 
DIN TH35 rail (35 mm wide). In order to meet the UE requirements, the rules concerning: supply, development and 
shielding ought to be followed- accordingly to the application.  
 
 

2.2 Installation procedure 

1. Install an enclosure, a distribution board or a cabinet and lead the cables through the cable ducts. 
2. Install the PSU on the DIN rail: Mount the PSU onto the rail and block with a clip (Fig. 3) 
3. Connect the receivers’ cables to the OUTPUT (+,-) terminals of the terminal block on the PSU module’s board. 
4. Connect the 230VAC power leads (L, N). 
5. Activate the ~230V/AC supply (the DC OK diode  green  should be permanently illuminated) 

Отзывы: