CHAPTER 6 MODBUS
Modbus Protocol
The exchange of information between Master and Slave devices is done
using the Modbus RTU communication protocol (19200-8E1). This protocol
allows read and write operations over Registers allocated in the dBi-M unit.
The protocol includes (among others) an 8-bit field defined as Device
Address, a 8-bit field defined as Function Code, a 16-bit field defined as
Register Address, and 32-bit field(s) defined as Register(s).
Device Address
Each Modbus slave has a unique Modbus address. The Modbus protocol
defines the address range limits as 1 to 247. However, the dBi-M Series will
support an address range of 1 to 126. The device address used by the dBi-
M is set using the parameter shown below:
PAR. NO.
OPTIONS
DESCRIPTION
P133
1 to 126
Device Address
–
Enter the Modbus
device number for the dBi-M transducer.
Function Codes
Pulsar dBi-M Modbus Protocol supports functions 3, 4, 6 and 16. These
registers are listed below:
FUNCTION CODE
FUNCTION DESCRIPTIONS
PLC ADDRESS
03
Read holding registers
40XXX
04
Read Input registers
30XXX
06
Write to a single register
40XXX
16
Write to multiple registers
40XXX
Important Notice
Out of the box the dBi-M is set to the following Modbus Protocol:
Modbus ID = 126
Serial setup: 19200
–
8
–
E - 1
Note:
Only Slave operation with Modbus RTU is available.