The

 Dimming / Switching Datapaks

 are capable of dimming or 

switching resistive and inductive loads, and switching capacitive 
loads.  To dim capacitive loads, e.g. projectors with power factor 
correction (PFC) capacitors, remove their PFC capacitors. 

The 

Switching Datapaks

 are capable of switching resistive and 

inductive loads, but they are not suitable for capacitive loads. 

This makes the 

Datapak range

 suitable for running all types of low 

voltage lamps, electric motors, neon lights, properly ballasted 
fluorescent lamps etc. besides ordinary resistive tungsten lamps. 

INSTALLATION AND SERVICE

 

must only be carried 

out by suitably skilled and competent persons.   The 
Datapak must be connected in accordance with current 

local and national wiring regulations.  When not in use for a period of 
time or before working on the lighting installation, replacing lamps or 
loads, the Datapak should be isolated (disconnected) from the mains 
supply.   If the Datapak is not installed or operated according to this 
instruction leaflet then the protection provided by the Datapak may be 
impaired. 

WARNING - THIS APPLIANCE MUST BE EARTHED

 

INSTALLATION AND VENTILATION 

All Dimming and 

Switching Packs generate a certain amount of heat, so it is essential 
to leave a 25mm air gap around the Datapak.   Rack cabinets should 
be ventilated or open backed.  Do not obstruct the cooling air inlets 
on the back panel or outlets at the top right hand corner.  The 
Dimming/Switching models contain a fan.  The mounting brackets 
supplied space the Datapak suitably from a wall. 

19” RACK MOUNTING 

To rack mount your Datapak remove the 

four M4 countersunk screws that hold each of the two wall mounting 
brackets.  Rotate and re-fix these to the front four nutserts provided 
along each side of the Datapak. 

 

A CONNECTION PANEL

 for hardwiring the mains input/output 

connections are located on the bottom panel. 
To allow cable access to the mains input and outputs, remove the 
appropriate knockout (20, 32mm) from the panel. 
Knockouts removed, but not in use, must be covered up. 
A further two blanking plugs (25, 32mm) are located on the right of 
the top panel to allow the entry/exit of such cables. 
The signal inputs are accessed by removing the 20mm blanking plug 
from the bottom panel.    Another blanking plug is located on the left 
of the top panel to allow the entry/exit of such cables. 
Signal cables following this route 

must

 be double insulated, mains 

rated. 

LEVER OPERATED TERMINAL BLOCKS

 

are used for all 

input /output connections for speed and reliability. 
Use a small bladed screwdriver or similar, to operate the lever. 

Max.  cable size:

 2.5 mm

2

MAINS SUPPLY 
Important:

  For your Safety the Datapak must be Earthed, fed via a 

Residual Current Circuit Breaker and Local Isolator fused for the max 
IMUM current taken by the load.   You might find a Pulsar Mains 
Distribution Unit suitable. 

Mains Voltage:

  100 - /-10%, single or three phase, star or 

delta.   There is no voltage selector - the electronics automatically 
adjusts to the incoming voltage. 

Mains Frequency:

 48-62Hz, the electronics automatically adjusts to 

the frequency. 

Power Consumption:

  The Datapak itself uses very little power, so 

the maximum power consumed (when all the lights are on full) = the 
total wattage of lamps connected.   The maximum load per channel 
is 5, 10 or 20 Amps - see Front Panel. 

MAINS CONNECTIONS 

Live, Neutral and Earth Inputs: 

As supplied, the, short brass bars are set for 3 phase star 
mains operation.  To convert the Datapak for other mains 
configurations they must be relocated or removed, following the 
diagrams printed on the Front Panel and shown above. 

Delta supplies: 

In order not to exceed the rating of the terminal blocks, a supply 
connection with two cables per phase is required.  Connect one 
cable to the upper phase terminal and the other to the lower phase 
terminal. 

All supplies: 

When connecting your live phase cables be sure to re-connect the 
ring connectors that take this supply to the front panel fuse holders. 
The ring connectors must be in direct contact with the supply cable.

CONNECTIONS 

INTRODUCTION 

 

INSTALLATION 

DATAPAK III 