![Pulsar Blue Power PSBS 5012E Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/pulsar/blue-power-psbs-5012e/blue-power-psbs-5012e_manual_1624827006.webp)
PSBS5012E
BLUE POWER
6
W
H
D
replacement)
Automatic return
Overload protection OLP
110-150% of the PSU power, manual restart (failure
requires the disconnection of the DC output)
Battery circuit protection SCP and reverse
polarity connection
T6,3A- current limitation, the F
BAT
melting fuse (failure
requires fuse replacement)
Surge protection
varistors
Deep discharge battery protection UVP
U<10V (
± 0,5V) – disconnection of battery terminal
Tamper protection:
- TAMPER output indicating enclosure opening or
detachment from the wall
- micro switch x 2, NC contacts (enclosure closed and
mounted to the mounting base), 0,5A@50V DC (max.)
Optical indication: front panel of the PSU
- AC OK.; LED indicating the AC power status
- DC OK.; LED indicating the DC supply at the PSU
output
- BAT OK.; LED indicating the battery voltage
- red, normal operation: permanently illuminated,
failure: off
- green, permanently illuminated, failure: off
- green, permanently illuminated,
failure: off
Technical outputs:
- EPS; output indicating AC power failure
- PSU; output indicating no DC power/PSU failure
- LoB output indicating low battery voltage
- OC type: 50mA max.
Normal operation: L state (0V),
failure: hi-Z state,
- delay time 10s/60s (+/-20%)
– jumper selectable
T
AC
- OC type: 50mA max.
Normal operation: L state (0V),
failure: hi-Z state,
- OC type, 50mA max.
Normal operation (U
BAT
>11,5V): L state (0V),
failure (U
BAT
<11,5V): hi-Z state
The power supply unit does not feature a battery detection
function.
Fuses:
- F
MAINS
- F
BAT
T 3,15A / 250V
T 6,3A / 250V
Table 4. Mechanical parameters
.
Enclosure dimensions
400 x 370 x 170+8 (WxHxD) [mm] (+/- 2)
Mounting
See Fig., 3
Battery housing
65Ah/12V (SLA) max.
350x175x165mm (WxHxD) max
Net/gross weight
8,60kg / 9,90kg
Enclosure
Steel plate, DC01 0,7mm color RAL 9003
Closing
Cylindrical screw (at the front), (lock assembly possible)
Terminals
Mains supply 230V AC:
Ф0,51÷2 (AWG 24-12)
Outputs
: Ф0,41÷1,63 (AWG 26-14)
BAT battery outputs: 6,3F-2,5, 30cm
TAMPER output: cables, 25cm
Notes
The enclosure does not adjoin the mounting surface so that cables can be led.
Convection cooling.
Table 5. Safety of use.
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC