PULSAR MEASUREMENT
19
ATEX
For
EEx m
(
Zone 1)
applications a transducer certified to
Sira
02ATEX5104X
is used, and must be supplied via a 4000A breaking fuse,
which is fitted as standard to the BlackBox level controller.
For
EEx ia
(
Zone 0)
a transducer certified to
Sira 02ATEX2103X
is
used,
which must be connected to the BlackBox via an external Zener barrier.
FM
For
EEx m
(
Zone 1)
applications a transducer certified to
FM Class I Div 1
Group A, B, C & D, ClassII Div 1 Group E, F & G, Class III
is used, and must
be supplied via a 1500A breaking fuse, which is fitted as standard to the
blackbox level controller.
Restrictions do not use in the presence of these groups of Chemicals,
Aliphatic Hydrocarbons, Ketones or Esters
For
EEx ia
(
I.S.)
a transducer certified to
FM Class I Div 1 Group A, B, C &
D, ClassII Div 1 Group E, F & G
is
used, which must be connected to the
blackbox via an external Zener barrier.
See transducer label for certification details.
Relay Outputs
The two relays can be programmed to a variety of alarm & control functions.
The relay contacts are all rated at 2A at 240V AC. All connections should be
such that the short circuit capacity of the circuit to which they are
connected, is limited by fuses rated so that they do not exceed the relay
rating.
Current Output
This is an isolated active mA output of 4 - 20mA or 0 - 20mA, with an option
of a passive mA output. The load should not exceed 1K
.
RS232 Serial Interface
The serial interface is used to program the BlackBox either via a PC
(standard) using the software supplied or alternatively using the handheld
calibrator (optional).