4. Battery-assisted operation. 

 

4.1. Running the PSU from the battery. 

 

The PSU has been equipped with two buttons on the pcb board which enable running or disconnecting the 

PSU during battery-assisted operation. 

 

Running the PSU from the battery: press the START button on the main board and hold for 1s. 

 

Disconnecting the PSU from the battery: press the STOP button on the main board and hold for 5s. 

 
 

4.2. Deep discharge battery protection UVP. 

The PSU is equipped with the disconnection system and the discharged battery indication. If the voltage at 

the  battery  terminals  drops  below  20V±0.2V  during  battery-assisted  operation,  the  battery  will  be  disconnected 
after appr.15s.  

Switching off/on the function of the battery protection: 
Press the ‘SET’ button from the level of the LCD desktop and then choose:  

”PSU -> Battery protection: YES/NO”

 (see chapter 3.4.2, table 7). 

 

Caution. 
Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its 
capability of storing energy, lowers its capacity and shortens its durability. 
 
 

 

4.3 Dynamic battery test. 

The PSU runs a battery test every  10 minutes. It is done by a momentary switching into a battery-assisted 

operation. A failure is indicated when voltage drops below 24V. The battery test facility can be switched off. 

Deactivating/activating the test:  
- enter the PSU settings from the level of the LCD desktop by pressing the ‘SET’ button. Then choose:  

”PSU -> Battery protection: YES/NO”

 (see chapter 3.4.2, table 7) or 

             - from the pcb level: during mains-powered PSU operation press the STOP button on the main board and 
hold it for 3 seconds.  
           The  device  will  confirm  the  activation/deactivation  of  the  test  (see  tab.8  [6,  7])  and  show  an  appropriate 
message on the display: 

”TEST ON/ TEST OFF”

 

 
Deactivating/activating  the  test  is  stored  in  the  memory  even  after  unplugging  the  device  from 
mains.  The  battery  failure  indication  at  the  APS  FLT  output  is  automatically  switched  off.  The 
battery protection system against deep discharged remains on, though.  
 

 

4.4. Standby time.  
The  standby  time  during  batter-assisted  operation  depends  on:  battery  capacity,  battery  charge  level  and 

load current. In order to keep the standby time, the current drawn from the PSU during battery-assisted operation 
should be limited. Characteristics for a 2x17Ah/12V SLA: 

 
Grade 1, 2 - standby time 12h   

 

 

 

 

Output current 1,4A + 0,6A battery charge 

 
Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving 
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output current 0,56A + 1A battery charge 

 

 
 - standby time 60h if the faults of the main power source are reported to the Alarm Receiving 

Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output current 0,28A + 1,5A battery charge 

 
 
 
 
 
 
 
 
 

Содержание Black Power PSBEN 2024C/LCD

Страница 1: ...PSBEN 2024C LCD v 1 0 PSBEN 27 6V 2A 2x17Ah EN LCD Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Страница 2: ...the EPS output lag 16 Setting the communication address 17 3 4 3 Desktop 17 Setting the language of messages 18 Setting the date 18 Setting the time 19 Setting the highlighting 19 Setting the contrast...

Страница 3: ...QUIREMENTS 30 7 2 INSTALLATION PROCEDURE 30 8 OPERATION AND USE 31 8 1 OVER VOLTAGE PROTECTION OVP AT THE PSU OUTPUT 31 8 2 OVERLOAD OF THE PSU 31 8 3 SHORT CIRCUIT AT THE PSU OUTPUT 31 8 4 BATTERY RE...

Страница 4: ...s operation history failure history real time clock battery backed optical indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs o...

Страница 5: ...ource are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 1 5A battery charge General use if the PSU is not mounted within an installation which is...

Страница 6: ...off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZZER acoustic indicator 8 FBAT fuse in the battery circuit 9 Connectors AC AC power input BAT DC power battery output A...

Страница 7: ...N 230V AC power connector PE connector 6 Battery connectors positive BAT red negative BAT black 7 Grip of tamper resistance Fig 3 The view of the PSU 3 Operating status indication 3 1 Control panel T...

Страница 8: ...lay The main screen of the LCD display shows basic electrical parameters and informs about the current PSU state Fig 5 The main screen Table 4 Description of the symbols on the main screen Screen fiel...

Страница 9: ...tatus during operation Highlighting of an element informs about an active state and reflects the status of LEDs on the pcb of the PSU see table 1 12 Fig 7 Screen parameters of the PSU Table 5 Descript...

Страница 10: ...analysis of the values shown on the chart the time range of the chart screen can be adjusted in the bottom axis Here are the available ranges 8h 24h 2days week weekly In order to change the displayed...

Страница 11: ...erates 3 levels of access to configuration which limit the possibility of changing the PSU s settings from the level of the LCD desktop They are protected with separate passwords Keypad password locks...

Страница 12: ...ear with or choose the right level of the password confirm your choice with the SET button with or enter the first digit confirm your choice with the SET button with or enter the second digit confirm...

Страница 13: ...swords have been lost there is a procedure that will allow reassigning the passwords Please do as follows a unplug the PSU from the AC network and the battery for at least 10 seconds b press the STOP...

Страница 14: ...to the PSU NO battery not connected to the PSU see chapter 4 6 Battery test YES battery test on NO battery test off see chapter 4 3 Battery protection YES battery protection function disconnection on...

Страница 15: ...onfirm your choice with the SET button Setting the battery test with or choose the Battery test menu press the SET button you will see the prompt at the end of the line with or set YES or NO YES batte...

Страница 16: ...nction disconnection on NO battery protection function disconnection off confirm your choice with the SET button Setting the EPS output lag with or choose the EPS output lag menu press the SET button...

Страница 17: ...mputer confirm your choice with the SET button 3 4 3 Desktop The facility is only available after entering the correct user s or installer s password The Desktop menu enables setting the current date...

Страница 18: ...you will see the prompt at the end of the line with or choose the language of messages confirm your choice with the SET button Setting the date with or choose the Date menu press the SET button the pr...

Страница 19: ...ection with or set the minutes press the SET button the prompt will move to the second section with or set the seconds approve the settings with the SET button Setting the highlighting Intensity of th...

Страница 20: ...t to the constant option with or change the setting into 60 s press the SET button the prompt will move to the end of the line with or set the demanded screen brightness approve your choice with the S...

Страница 21: ...ly the output is close In case of a power failure the PSU will switch the output into the open state after a period of time determined by the EPS output lag facility see 3 4 2 table 7 APS FLT output i...

Страница 22: ...IN technical input has been implemented with galvanic isolation between the PSU s systems and the devices attached Fig 16 Electrical diagram of the EXT IN input The electrical diagram below shows the...

Страница 23: ...ery test facility can be switched off Deactivating activating the test enter the PSU settings from the level of the LCD desktop by pressing the SET button Then choose PSU Battery protection YES NO see...

Страница 24: ...J2 J3 15h18m 1 J1 J2 J3 25h30m 0 6 J1 J2 J3 0 2 J1 J2 J3 4 6 Operation without a battery In case of an expected PSU operation without an attached battery make a necessary configuration setting from t...

Страница 25: ...ces 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz freque...

Страница 26: ...Ethernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correct...

Страница 27: ...ation with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and mem...

Страница 28: ...2A battery charge Io 1 4A 0 6A battery charge Io 1A 1A battery charge Io 0 5A 1 5A battery charge Output voltage setting escalation and keeping time 10ms 34ms 12ms Output voltage adjustment range 24V...

Страница 29: ...x 355 x 90 8 WxHxD mm 2 Fixing 370 x 318 x 6 x4 WxH Fitting battery 2x17Ah 12V SLA max Net gross weight 5 9 6 2 kg Enclosure Steel plate DC01 1mm colour RAL 9005 black Closing Cheese head screw x2 at...

Страница 30: ...and assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 7 2 Installation procedure CAUTION Before installation cut off the voltage in the...

Страница 31: ...peration and use 8 1 Over voltage protection OVP at the PSU output In case of voltage exceeding 31V 0 5V at the regulator s output the system cuts off the power at the outputs to protect the battery a...

Страница 32: ...high output voltage Output voltage 29 4V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 28V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of...

Страница 33: ...ssibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are car...

Отзывы: