background image

www.pulsar.pl   

 

 

 

PSBEN2024B   

 

 

 

    

BLACK POWER

 

 

 

11 

6. With the 

P

BAT

  jumper  determine  if  the  discharged  battery  disconnection  system  U<20  V  (+/-5%)  shall  be  on  or 

off. 

The battery protection is on when the P

BAT

 jumper is off.

 

7. Switch on the ~230 V supply (red AC diode and green AUX diode should be on). 
8.  Check  the  output  voltage  (the  PSU  voltage  without  load  and  without  battery  should  amount  to  27.

5  V÷27.7 V, 

with a battery or during battery charging process: 22 

V÷27.6 V). If the value of the voltage requires adjustment, it 

should be set with use of the V

ADJ

 potentiometer, monitoring the voltage at the AUX output of the PSU. 

9. Connect the batteries in accordance with the markings: +BAT red to 'plus',  -BAT black 

to 'minus’. The LB diode 

should be on during battery charging process. 
10. Press the STOP button to activate or deactivate a dynamic battery test. Deactivating the test turns out the PSU 
failure  indication  at  the  APS  FLT  output,  but  it  does  not  affect  the  protection  system  against  complete  battery 
discharge. 
11. Check the current consumption of the receivers, taking into account the  battery charging current, so as not to 
exceed the total current efficiency of the PSU. 
12. Once the tests are completed, close the PSU cover. 
 
        

Table 3. Operation parameters. 

Environmental class 

II 

Operating temperature 

-

10ºC...+40ºC 

Storing temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, no condensation 

Sinusoidal vibrations during operation 

EN 50130-5 

Surges during operation 

EN 50130-5 

Direct insolation 

unacceptable 

Vibrations and surges during transport 

PN-83/T-42106 

 
 
         

Table 4. Factory settings of the PSU. 

Indication time of EPS network loss 

5s 

section 5.5 

Battery charging current 

0,6 A 

section 6.5 

Battery presence 

YES (battery present) 

section 6.6 

Battery test 

ON 

  section 5.3.1 

section 6.3 

Deep discharge battery protection UVP 

ON 

section 6.2 

Acoustic indication 

ON 

section 5.4 

LED display dimmer 

OFF 

 section 5.3.2 

Communication address 

 section 5.3.3 

Transmission 

115.2k 8E1 

 section 5.3.4 
 section 5.3.5

 

 

Содержание BLACK POWER PSBEN 2024B

Страница 1: ...PSBEN 2024B v 1 1 PSBEN 27 6V 2A 2x7Ah EN Buffer switch mode power supply unit Grade 3 EN Edition 8 from 31 01 2019 Supercedes edition 7 from 02 11 2017 LED Version...

Страница 2: ...s to cooperation with PowerSecurity 19 5 3 4 Setting the transmission speed trS applies to cooperation with PowerSecurity 20 5 3 5 Setting the parity of the transmission trP applies to cooperation wit...

Страница 3: ...www pulsar pl PSBEN2024B BLACK POWER 3 TABLE 13 ELECTRICAL PARAMETERS 32 TABLE 14 MECHANICAL PARAMETERS 33 TABLE 15 SAFETY OF USE 33 9 TECHNICAL INSPECTIONS AND MAINTENANCE 34...

Страница 4: ...overcharge protection battery output protection against short circuit and reverse polarity connection jumper selectable battery charging current 0 2 A 0 6 A 1 A 1 5 A remote battery test additional m...

Страница 5: ...ES YES No battery charge YES YES Low output voltage YES YES High output voltage YES YES PSU failure YES YES Surge protection YES YES Short circuit protection YES YES YES YES Overload protection YES YE...

Страница 6: ...is not mounted in an installation complaint with the EN 50131 standard the acceptable current efficiency amounts to 1 Output current 2 A 0 2 A battery charge 2 Output current 1 6 A 0 6 A battery charg...

Страница 7: ...ACK POWER 7 3 2 Block diagram The PSU is manufactured based on a high duty system of DC DC converter The microprocessor system is responsible for full diagnostics of the PSU and battery parameters Fig...

Страница 8: ...button disconnection of the PSU during battery assisted operation pin activation of the acoustic indication indication on indication off Caption jumper on jumper off VADJ potentiometer DC voltage adju...

Страница 9: ...nt no Description Insolation transformer PSU board see Tab 1 fig 2 TAMPER micro switch contacts of tamper resistance NC FMAINS fuse in the supply circuit 230 V L N power supply connector 230 V protect...

Страница 10: ...g surface The grip is located in the central part of the enclosure see fig 3 7 and guarantees indication in case of any attempts of detaching the device from the mounting surface Proper installation i...

Страница 11: ...ation at the APS FLT output but it does not affect the protection system against complete battery discharge 11 Check the current consumption of the receivers taking into account the battery charging c...

Страница 12: ...g 5 Control panel Table 5 The description of the buttons and LEDs of the LED panel Description Additional information moves the pointer on the screen next screen selection selection approval red LED i...

Страница 13: ...e voltage indicator displays the measured output voltage at the AUX output If the voltage drops below 26 V during operation with activated battery test or exceeds 29 4 V the PSU will indicate a failur...

Страница 14: ...tically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failures 5 2 4 Current fai...

Страница 15: ...e code will be automatically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failu...

Страница 16: ...Low battery voltage APS FLT the battery voltage has dropped below 23 V during battery assisted operation F11 Low battery volt off APS FLT the battery voltage has dropped below 20 V during battery ass...

Страница 17: ...bols Symbol Description Additional information Battery test tSt On battery test on OFF battery test off Sections 5 3 1 LED display dimmer On dimmer ON OFF dimmer OFF Sections 5 3 2 Communication addre...

Страница 18: ...your choice with the OK button in order to return to the main menu simultaneously press the rightmost and leftmost buttons on the LED panel Deactivating activating the test with the STOP button on the...

Страница 19: ...mer on OFF dimmer off confirm by pressing OK in order to return to the main menu simultaneously press the rightmost and leftmost buttons 5 3 3 Setting the communication address Adr applies to cooperat...

Страница 20: ...ss parity and speed should have the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 However if it is connected to the network...

Страница 21: ...he panel use the or buttons in order to set the required communication mode 8N2 8E1 factory setting 8O1 confirm by pressing OK in order to return to the main menu simultaneously press the rightmost an...

Страница 22: ...dicates the PSU failure Under normal status during correct operation the output is close In case of a failure the PSU will switch the output into the open state Any failures can be triggered by the fo...

Страница 23: ...ee a correct cooperation between the module and the EXT IN input the VEXT jumper must be on and the connections are to be made accordingly to the diagram below Fig 11 Example of a connection with the...

Страница 24: ...ted by the OVP yellow LED on the PCB board and the PSU FLT output 5 9 PSU overload The PSU is fitted with the LED OVL overload on the PCB and indicator on the LED panel informing about output overload...

Страница 25: ...s voltage The protection mode is off when the PBAT jumper is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing...

Страница 26: ...y charging time The PSU has a battery circuit charged with direct current The current selection is done with use of the IBAT jumpers The table below shows how long does it take to charge a fully disch...

Страница 27: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 6 4 7 1 Communication via the USB TTL interface The easiest way of...

Страница 28: ...g against adverse environmental conditions Fig 14 Ethernet network communication using the RS485 INTRE interface 7 3 The Wi Fi wireless communication The Wi Fi wireless communication can be implemente...

Страница 29: ...inst adverse environmental conditions Fig 16 The Wi Fi communication using the RS485 WIFI INTRW interface 7 4 RS485 network communication Another type of network communication is the RS485 communicati...

Страница 30: ...wer supplies in case of failures the backlight changes accordingly in both the manager window and the Windows taskbar In addition the program allows you to download the operation history of the power...

Страница 31: ...ynoptic board or the list mode This is especially useful when the PowerSecurity program works with a large number of power supplies The application enables both visualization and analysis of read data...

Страница 32: ...the output voltage AUX disconnection automatic return Short circuit protection SCP Electronic current limitation and or FBAT fuse failure in the battery circuit requires fuse replacement Automatic ret...

Страница 33: ...Mounting See Fig 3 Net gross weight 5 5 5 9 kg Enclosure Steel plate DC01 1mm color RAL 9005 black Closing Cheese head screw x2 at the front lock assembly possible Terminals Supply 0 63 2 50 AWG 22 10...

Страница 34: ...batteries and run the battery test 4 weeks after installation re tighten all screw connections see Fig 2 9 WEEE LABEL According to the European Union WEEE Directive waste electrical and electronic eq...

Отзывы: