1.4. Technical parameters:  
- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operation parameters (tab.6) 

      

E

lectrical parameters (tab. 3). 

Supply voltage 

230V AC  (-15%/+10%) 

Supply frequency 

50Hz (47÷53Hz) 

PSU module  power P 

36W max.  

Current consumption  

0.5A/230V 

Output voltage 

12,0V DC nom. 

Output voltage setting, escalation and keeping 
time 

55ms/50ms/12ms 

Voltage setting range 

11,0V÷15,0VDC (-/+5%), 3x adjustment A, B, C 

Output current  

9x 0,33A for fuses F 500mA, ΣI= 3,0A max (total, uninterrupted)  

Short-circuit protection SCP 

9x F 500mA fuses (damage, fuse-element replacement required) 
or PTC 500mA - set by jumper 

Short-circuit protection OLP 

110%÷150% power supply power, limitation for three sections by 
PTC fuses, reset requires turn off the supply or load for about 1 min. 

Overvoltage protection OVP 

17V (-/+ 5%) 

Surge protection 

varistors 

TAMPER output indicating the opening of 
the power supply casing

 

- micro-switch x2, NC contacts (closed casing, mounted on 
foundation), 0.5A@50V DC (max)

 

Optical indication: 
diodes 1÷5 (green) 
 
diode AC  (red) 
 
 
diodes 

A

OVP, 

B

OVP, 

C

OVP

 (red) 

(on unit PCB) 

 

- outputs status A1, A2, A3, B1, B2, B3, C1,C2, C3 
normal status  = lights 
failure status= does not light 
- supply status AC: 
normal status  = lights 
failure status= does not light  
- OVP overvoltage protection status: 
normal status  = lights 
failure status= does not light  

Fuse F 
Bezpiecznik FA1÷FC3 

T 1A/250V 
F 500mA/ 250V

 

      

Mechanical parameters (tab. 4). 

Casing dimensions 

235 x 235 x 98 (230 x 230 x 90) (WxHxD)  

Fixation 

205 x 203 x  Φ 6  WxH  

Net/gross weight 

3,2/3,4 kg 

Casing color 

RAL 9003 

Closing 

Cheese screw: at the front of the casing 

Connectors 

Supply 230V AC: Φ0,63-2,05 (AWG 22-12) 
DC outputs: Φ0,51- 2,05 (AWG 24-12) 

Notes 

The casing is distant from the assembly surface so that cables can be installed  
convection cooling 

       

Operation safety 

(tab.5). 

Protection class PN-EN 60950-1:2004 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input (network) circuit and output circuits of power-supply (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Operation parameters 

(tab.6). 

Operation temperature 

-10ºC...+40ºC 

Storage temperature 

+5ºC...+40ºC 

Relative humidity 

30%...90%, without condensation 

Vibrations during operation 

Unacceptable 

Impulse waves during operation 

Unacceptable 

Direct isolation 

Unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 
 

Содержание AWZ 09123

Страница 1: ...PSU S 12V L 3A 9 FTA PTC TR MC AWZ 09123 v 1 0 Linear stabilized power supply unit EN Edition 1 from the 30th January 2011 Supercedes edition _____________...

Страница 2: ...and operation 4 1 Short circuit protection 4 2 Overload protection 4 3 Maintenance 1 Technical description 1 1 General description Buffer power supply unit is designed for the supply of equipment req...

Страница 3: ...circuit DC 3 P A B C voltage adjustments output voltage regulation for a particular group 4 OUTPUTS of power supply unit connector Tab 2 5 F fuse in the power supply circuit 230V AC 6 L N power suppl...

Страница 4: ...4 Fig 2 The view of the power supply unit...

Страница 5: ...status AC normal status lights failure status does not light OVP overvoltage protection status normal status lights failure status does not light Fuse F Bezpiecznik FA1 FC3 T 1A 250V F 500mA 250V Mech...

Страница 6: ...230V AC shall be connected to L N terminals of the power supply The earth conductor shall be connected to the terminal marked by the earth symbol The connection shall be made by means of a three core...

Страница 7: ...of about 1 min It is acceptable to change values of fuses to other than original if not all outputs of power supply are used and Pmax is not exceeded 4 2 Procedure in case of overload activation of OL...

Страница 8: ...n item 5 may be prolonged if there is no technical capability to carry out the repairs and in the case that the equipment has been accepted conditionally due to the failing of the warranty terms by th...

Отзывы: