background image

 

The charging voltage during buffer operation (emergency power) should be in the range from 

2.25

 to 

2.30 [V / cell]

 (

2,275 

[V / cell]

 recommended), that is from 

13.50 

to

 13.80

 [V] for the battery with a voltage of 

12 [V]

 (6 cells) and from 

243.00

 

to 

248.4 [V]

 for 18 batteries connected in series (battery 220 V, 108 cells). 

 
During cyclic operation (repeated charge / discharge cycles), when the battery is the primary power source, the charging 
voltage should be in the range from 

2.40

 to 

2.50 [V / cell]

 that is from 

14.40 

to 

15.00

 [V] for the battery with a voltage of 

12 [V] (6 cells). At high operating temperature fluctuations, a power supply fitted with voltage temperature compensation 
system  -  reducing  the  charging  voltage  with  increasing  temperature-  should  be  used.

 

Temperature  compensation 

coefficient is 

minus 3 [mV / ° C / cell] 

from 25 [° C]. 

The charging voltage should be well regulated and its ripple should not exceed 1.5 [%]. 
  
Each cell of maintenance-free battery (6 volt - 3 cell, 12 volt - 6 cells) is fitted with one way, self-sealing valve that opens 
when the pressure increase inside the battery (e.g. overload) and releases gases to the outside, protecting the container 
against  explosion.  Therefore,  do  not  charge  maintenance-free  batteries  in  sealed  enclosures;  the  battery  space  needs 
efficient natural (gravity) ventilation. 

 
b) Operating temperature: 
 

The  rated  operating  temperature  of  maintenance  free  batteries  is 

25  [°  C].

  Operation  of  maintenance  free  batteries  at 

elevated temperatures leads to a 

significant

 reduction in 

battery life

. Battery life is reduced 

by half

 for each sustained 

temperature  rise  of 

8

 

[° C] 

above  nominal  operating  temperature.  This  means  that  the  battery  opera

ted at  33 [° C]  will 

retain  50  [%]  while  the  battery  operated  at  41  [°  C],  only  25  [%]  of  the  projected  service  life.  For maximum  battery  life 
(buffer operation) perform the following steps: 
 

  place the battery away from heat source devices (e.g. transformer, heat sink), 

  keep  at  least  1.5  cm  of  free  space  around  the  battery  and  use  the  devices  fitted  with  ventilation  holes  in  the 

housing to allow free air circulation, 

  use effective natural or forced ventilation or air conditioning, 

  use a power supply with 

temperature-compensated charging voltage

 

if the operating temperature exceed 25 [° 

C]. 

 

Operation  at  high  temperatures  (above  40  [°  C])  significantly  reduces  lifetime  of  batteries  and  may  also  lead  to  their 
failure.  

The  temperature  rise  of  batteries  causes  a  reduction  in  internal  resistance,  resulting  in  an  increase  in  charging 

current. Higher current raises the temperature of the batteries so their resistance decreases. Then the cycle is repeated, 
leading  to  the  so-called 

thermal  runaway

,  that  is  lack  of  thermal  stability  of  the  battery. When  the  battery  temperature 

exceeds  40  [

°  C],  the  process  occurs  rapidly  and  leads  to  irreversible  damage  to  the  battery  (C,  in  extreme  cases  - 

deformation of the housing). 

Please note: when the room air temperature is40 [° C], the temperature of battery located inside the UPS power 

supply will be from a few to several [° C] higher depending on the operation mode of the battery (buffer charging or high 
current discharge). 
 

c) The depth of discharge: 
 

Tightly  sealed  lead-acid  batteries  are  sensitive  to  excessive  (too  deep)  discharge.  Excessive  discharge  of  the  battery 
reduces  its  energy  storage  capabilities,  capacity  and  lifetime.  Leaving  a  discharged  battery  for  a  longer  time  without 
recharging  can  also  result  in  excessive  discharge.  Too  deeply  discharged  batteries  are  damaged  by  sulphation  which 
results partial irreversible loss of capacity available. The minimum allowable discharge voltage of the battery depends on 
the discharge current and is specified in the battery discharge characteristics. 
 

4. Maintenance:

 

 

For  maximum  lifetime  and  reliability  of  maintenance  free  batteries  connected  in  series  or  in  parallel  to  increase  their 
voltage  or  capacity,  periodic  inspections  of  their  status  and  operating  parameters  should  be  carried  out.  Periodic 
maintenance of batteries should be performed only by qualified and authorized personnel. Presentation of 

the results of 

measurements from all of required periodic maintenances is a condition for warranty claim

.  

 
Every 

12 months

 (every 6 months recommended) from the date of installation, check and 

document

 the following: 

 

a)  Battery  charging  voltage 

-  should  be  in  the  range  between 

2.25  and  2.30  [V  /  cell]

  that  is,  for  example: 

243.0

  to 

248.4 [V]

 for 18 batteries connected in series (220V battery, 108 cells). The recommended value is 

245.7 [V] (2,275 [V / 

cell])

. The charging rectifier should be equipped with a charging voltage temperature compensation system.  

 

b) The charging voltage for each battery 

- should be in the range between 

13,5 and 13,8 [V]

 

Отзывы: