background image

EN 

YRM2.DIODE Installation Manual 

 

 

 

Product Description 

The YRM2.DIODE is a redundancy module for building redundant power supply systems. It is 
equipped with two input channels and one output. The two inputs are decoupled by diodes. 
The device has a monitoring circuit included. Two LEDs and two relay contacts signal when one of the 
two DC-input voltages is not in range due to a non-functioning or disconnected power supply. 
 

Intended Use 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like. Do not use this 
device in equipment where malfunction may cause severe personal injury or threaten human life.  
The redundancy module can be used with any type of power supply as long as the maximum output 
current ratings are not exceeded. It is suitable for power supplies with continuous overload current as 
well as any kind of intermittent (Hiccup) overload behavior. 
 

Installation Instructions 

Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Do not ground or earth the positive output pole which could prevent redundancy in case of a ground 
failure. Ground the negative output pole, when needed. 
Use only power supplies with a negligible output ripple voltage in the low frequency range between 
50Hz and 10kHz when used in marine applications according to the GL regulations. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the top of the 
device.

 

Other mounting orientations require a reduction in output current. 

Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. 
Unused screw terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments.

 

No condensation or 

frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. 
The input must be powered from a PELV or SELV source or an “Isolated Secondary Circuit” in order to 
maintain a SELV or PELV output. 
Check correct input polarity. The device will not operate when input voltage is reversed. 
The device is designed as “Class of Protection III” equipment according to IEC 61140. 
A PE (ground) connection is not required. However, connecting the chassis ground terminal to ground 
can be beneficial to gain a high EMI immunity. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product 
datasheet for use above 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II 
Category 3 (Zone 2) environments. 
Hazardous Location classification: ATEX: EPS 11 ATEX 1 312 X, II 3G EX ec nC IIC T4 Gc 
WARNING EXPLOSION HAZARDS! 
Substitution of components may impair suitability for this environment.  
Do not disconnect the device unless power has been switched off or the area is known to be non-
hazardous. 
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 
and fulfils the requirements of the EN 60079-0. 

 

Functional Description 

The device can supply any kind of loads, including unlimited capacitive and inductive loads. 
Do not apply return voltages from the load to the output higher than 200Vdc. 
Both input voltages are monitored individually. The green Input-OK LEDs report an input voltage 
above 21.5V for the corresponding input channel. 
The Input-OK relays monitor the input voltages. The contact is closed, when the Input-OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 

 

 

Technical data

 

All values are typical figures specified at 24Vdc input voltage, 20A output 
current, 25°C ambient temperature and after a 5 minutes run-in time 
unless otherwise noted. 

Input voltage 

DC 24 - 48V 

±25% 

Input voltage range 

18 – 60Vdc 

 

Input current 

2x 10A 

Below +60°C ambient 

 

2x 7.5A 

At +70°C ambient 

 

2x 16A 

Up to 5 seconds 

Output current 

20A Continuous, 

<+60°C 

 

15A 

Continuous, at +70°C 

 

32A 

Short term, up to 5s 

Maximum overload current  25A R.M.S. 

In any overload or short 
circuit condition 

 

Derate linearly b60 and +70°C 

Input to output voltage loss 780mV 

At 2x 5A input 

 

850mV 

At 2x 10A input 

Power losses 

0W 

At no load 

 

8.8W 

At 2x 5A input 

 

18W 

At 2x 10A input 

Temperature range 

-40°C to +70°C 

 

Max. wire size (litz wire) 

4mm² Power 

terminals 

Wire size AWG 

AWG 20-10 

Power terminals 

Max. wire diameter 

2.8mm Power 

terminals 

Wire stripping length 

7mm / 0.28inch 

Power terminals 

Tightening torque 

1Nm / 9lb.inch 

Power terminals 

Max. wire size (litz wire) 

1.5mm² Signal 

terminals 

Wire size AWG 

AWG 22-14 

Signal terminals 

Max. wire diameter 

1.5mm Signal 

terminals 

Wire stripping length 

6mm / 0.25inch 

Signal terminals 

Tightening torque 

0.4Nm/ 3.5lb.inch

Signal terminals 

Size (wxhxd) 

32x124x117mm Without 

DIN-rail 

Weight 

350g / 0.77lb 

 

 

Functional diagram 

+

-

+

-

+

-

Alarm
Relay

Input

Voltage
Monitor

Input 1
Alarm
contact

Alarm
Relay

Input

Voltage
Monitor

Input 2
Alarm
contact

Input 1

ok

Input 2

ok

Input 1

Input 2

Output

Chassis
Ground

 

 

Wiring scheme - 1+1 redundancy 

Load

Failure

Monitor

Power

Supply

Output

Input

L N

+

-

+

-

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

o o o o

2

1

Input ok

Power

Supply

Output

Input

L N

+

-

+

-

L

PE

o

p

ti

onal

N

I

I

 

 

Wiring scheme - n+1 redundancy 

Load

Failure

Monitor

Power

Supply

Output

Input

L N

+

-

+

-

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

o o o o

2

1

Input ok

Power

Supply

Output

Input

L N

+

-

+

-

Power

Supply

Output

Input

L N

+

-

+

-

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

o o o o

2

1

Input ok

Power

Supply

Output

Input

L N

+

-

+

-

L

PE

op

ti

on

a

l

N

op

ti

on

al

I

I

I

I

 

Отзывы: