DeviceNET
®
Power Supply Instruction Manual
Bedienungsanleitung für DeviceNET
®
Stromversorgung
Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperature of:
60°C for ambient temperatures up to 45°C,
75°C for ambient temperatures up to 60°C and
90°C for ambient temperatures up to 70°C.
Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter
the terminal connection! Ferrules are allowed.
QS5.DNET:
Input:
Solid wire / Stranded wire / AWG
0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length
7mm / 0.28inch
Output and Signals: Solid wire / Stranded wire / AWG
0.3-4mm
2
/ 0.3-2.5mm
2
/ 26-12 AWG
Wire stripping length
6mm / 0.25inch
QS10.DNET:
Solid wire / Stranded wire / AWG
0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length
7mm / 0.28inch
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für:
60°C bei einer Umgebungstemperatur bis zu 45°C,
75°C bei einer Umgebungstemperatur bis zu 60°C und
90°C bei einer Umgebungstemperatur bis zu 70°C zugelassen sind.
Beachten Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine
einzelnen Drähte von Litzen abstehen. Aderendhülsen sind erlaubt.
QS5.DNET:
Eingang:
Starrdraht / Litze / AWG
0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge
7mm
/
0,28inch
Ausgang, Signale:
Starrdraht / Litze / AWG
0,3-4mm
2
/ 0,3-2,5mm
2
/ 26-12 AWG
Abisolierlänge
6mm
/
0,25inch
QS10.DNET:
Starrdraht / Litze / AWG
0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge
7mm
/
0,28inch
Output- and Overload Characteristic
(see Fig. 4 and 5)
The units are overload, no-load, short-circuit proof. At overload, the output current flows
continuously. The unit does not switch-off or hiccup at overload.
Ausgangs- und Überlastverhalten
(siehe Bild 4 und 5)
Die Geräte sind leerlauf-, überlast- und kurzschlussfest. Bei Überlast fließt kontinuierlich Strom.
Die Geräte schalten nicht ab und haben auch keinen „Hiccup“ Modus.
DC-OK Relay Contact
(see Fig. 6)
This feature monitors the output voltage, which is produced by the power supply, and is
independent of a return voltage from a unit which is connected in parallel.
Contact closes when the output voltage reaches 21.5V
Contact opens when the output voltage dips more than 10%. Short dips will be extended to a
length of 250ms. Dips shorter than 1ms will be ignored.
Contact ratings: max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, Resistive load, min.: 1mA
DC-OK Relais Kontakt
(siehe Bild 6)
Diese Funktion überwacht die vom Gerät erzeugte Ausgangsspannung und lässt sich von einer
rückwärts eingespeisten Spannung nicht beeinflussen (z.B.: bei Parallelschaltung)
Kontakt schließt sobald die Ausgangsspannung 21,5V erreicht
Kontakt öffnet sobald der Ausgang um mehr als 10% einbricht. Kurze Einbrüche werden auf
250ms verlängert. Einbrüche kürzer 1ms werden ignoriert.
Belastbarkeit: max.: 60Vdc 0,3A; 30Vdc 1A; 30Vac 0,5A; (R-Last); min.: 1mA
Dielectric Strength
(see Fig. 1)
The output voltage is floating and separated from the input according to SELV (IEC/EN 60950-1)
and PELV (EN 60204-1, EN 50178; IEC 62103, IEC 60364-4-41) requirements. Type and factory
tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down).
Connect phase and neutral together as well as all output poles before the test is conducted.
A B
C
D
Type Test (60s)
2500Vac
3000Vac
500Vac
500Vac
Factory Test (5s)
2500Vac
2500Vac
500Vac
500Vac
Field Test (5s)
2000Vac
2000Vac
500Vac
500Vac
Cut-off current setting
>10mA
>10mA
>20mA
>1mA
Isolationsfestigkeit
(siehe Bild 1)
Die Ausgangsspannung hat keinen galvanischen Bezug zur Erde oder Schutzleiter und ist zum
Eingang nach den SELV (IEC/EN 60950-1) und PELV (EN 60204-1, EN 50178, IEC 62103, IEC
60364-4-41) Standards getrennt. Typ- und Stückprüfungen werden beim Hersteller durchgeführt.
Wiederholungsprüfungen dürfen mittels geeigneten Prüfgenerators mit langsam (2s) ansteigenden
und abfallenden Spannungsrampen in der Anwendung erfolgen. Vor den Tests sind Phase und
Neutralleiter wie auch alle Ausgangspole miteinander zu verbinden.
A B C D
Typprüfung (60s)
2500Vac
3000Vac
500Vac
500Vac
Stückprüfung (5s)
2500Vac
2500Vac
500Vac
500Vac
Wiederholungsprüfung (5s)
2000Vac
2000Vac
500Vac
500Vac
Strom- Abschaltschwelle
>10mA
>10mA
>20mA
>1mA
Fig. 1 / Bild 1
Insulation / Isolation
Fig. 2 / Bild 2
QS5.DNET: Functional Diagram / Funktionsschaltbild
Fig. 3 / Bild 3
QS10.DNET: Functional Diagram / Funktionsschaltbild
A
D
C
B
B
Input
DC-ok
Earth
Output
-
+
N
L
+
+
-
-
DC-ok
contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
lamp
DC-ok
lamp
Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter
L
N
+
+
-
-
DC-ok
contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
lamp
DC-ok
lamp
Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter
V
OUT
L
N
Fig. 4 / Bild 4
QS5.DNET: Overload Characteristic / Überlastverhalten
Fig. 5 / Bild 5
QS10.DNET: Overload Characteristic / Überlastverhalten
Fig. 6 / Bild 6
DC-OK Signal
Output Voltage
0
0
1
3
4
5A
4
8
12
28V
16
20
24
2
Output Current
Output Voltage
0
0
2
6
8
10A
4
8
12
28V
16
20
24
4
Output Current
250ms
21.5V
<1ms
open
24V
open
closed
closed
>1ms
Fig. 7 / Bild 7 Physical Dimensions / Abmessungen
QS5.DNET
QS10.DNET
PU-348.010.06-10E