PISA-B-812-B1
PISA-B-812-B4

Apr. 2021 / Rev. 0.1 DS-PISA-B-812-Bx-xx-EN

www.pulspower.com

3 / 20

All parameters are specified at 24Vdc input voltage, 8x5A output currents, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

1.

Intended Use

This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control,
process control, monitoring and measurement equipment or the like.

Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without
additional appropriate safety devices, that are suited for the end-application.

If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.

2.

Installation Instructions

DANGER

Risk of electrical shock, fire, personal injury or death.

– Turn power off before working on the device. Protect against inadvertent re-powering.
– Do not open, modify or repair the device.
– Use caution to prevent any foreign objects from entering the housing.
– Do not use in wet locations or in areas where moisture or condensation can be expected.
– Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.

Obey the following installation instructions:

This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable
parts. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit
to the factory for inspection.

Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. Install the device
onto a DIN rail according to EN 60715 with the input terminals on top of the unit.

Up to eight devices can be connected via two power-bus-bars, where only one device is connected to the power supply.
The power-bus-bars must be long enough to make a connection to all contacts of the devices.

Use an appropriately sized 24V power supply, which can deliver the peak current required to trip the load channels. If
peak currents are too low, the supply voltage for the protection module can no longer be maintained, which results in a
malfunctioning of the protection module.

Make  sure  that  the  wiring  is  correct  by  following  all  local  and  national  codes.  Use  appropriate  copper  cables  that
are  designed  for  a  minimum  operating  temperature  of  60°C  for  ambient  temperatures  up  to  +45°C,  75°C  for  ambient
temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire enter
the terminal connection.

The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed. The
enclosure of the device provides a degree of ingress protection of IP20. The housing does not provide protection against
spilled liquids.

The isolation of the devices is designed to withstand impulse voltages up to 1.5kV according to IEC 60664-1.

The input can be powered from a regulated power supply or a similar DC source.

The input must be powered from a PELV or SELV source in order to maintain a SELV or PELV output. Check for correct input
polarity. The device will not operate when the voltage is reversed.

A disconnecting means shall be provided for the input of the device.

The device is designed as “Class of Protection III” equipment according to IEC 61140.

The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not
cover ventilation grid!

Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase
the 5mm to 15mm in case the adjacent device is a heat source. Between multiple PISA-B modules, no clearance is needed.

The device is designed for altitudes up to 5000m (16 400ft).

The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient or
surrounding air temperature and is defined 2cm below the device. The device is designed to operate in areas between 5%
and 95% relative humidity.

Содержание PISA-B-812-B1

Страница 1: ...al output built in for this function All PISA B devices are equipped with push in terminals which are optimized for automated wiring The mechanically robust housing is made of a high grade reinforced...

Страница 2: ...rience at the time of publication If not expressly agreed otherwise this information does not represent a warranty in the legal sense of the word As the state of our knowledge and experience is consta...

Страница 3: ...s of the devices Use an appropriately sized 24V power supply which can deliver the peak current required to trip the load channels If peak currents are too low the supply voltage for the protection mo...

Страница 4: ...power bus bar of 32A is not exceeded Fuse modules can be lined up on the DIN rail without spacing The power bus bars can be plugged in from the front and must have a length that all plug contacts of t...

Страница 5: ...ab 5 1 Larger load capacitors might result in an unintended turn off of the channel More detailed information regarding allowable capacitive loads is available on request If in doubt or when you do no...

Страница 6: ...10A and 12A settings typ 50A For CH3 to CH8 independent of the settings Channels 1 and 2 have a current limited output while channels 3 to 8 have an overcurrent shutdown behaviour only Load capacitan...

Страница 7: ...stic Slow Fast selectable factory setting is Fast Tripping delay typ 1 1s For all channels in Slow mode at 1 5x nominal current typ 0 22s For all channels in Fast mode at 1 5x nominal current typ 2ms...

Страница 8: ...LEDs indicate the actual channel current in percent of the set value Peak values are stored in a peak detector and are additionally shown with one LED for a short period of time Uppermost LED is red T...

Страница 9: ...ged in the measurement mode as well as in the parameter mode Parameters can be changed regardless of whether a channel is switched off or not Changing the current settings Press and hold the SET butto...

Страница 10: ...sh button Channel 4 is loaded with 80 100 of the set current Channel 5 is turned off on purpose with push button Channel 6 is loaded with 40 60 of the set current current Channel 7 is loaded with 0 10...

Страница 11: ...ISA B 812 B1 The device is equipped with an alarm contact The normally closed NC contact closes as soon as one output channel has switched off common signalling or the input voltage is lower than 19Vd...

Страница 12: ...w pulspower com 12 20 All parameters are specified at 24Vdc input voltage 8x5A output currents 25 C ambient and after a 5 minutes run in time unless otherwise noted 12 Functional Diagram Fig 12 1 Func...

Страница 13: ...ative return input power bus bar F Set button required for controlling the unit G Channel control buttons H LED matrix display I LED which indicates percentage values of the LED matrix Fig 13 1 Front...

Страница 14: ...V 8x2 5A and 40 C t b d At 24V 8x5A and 25 C t b d At 24V 8x2 5A and 25 C 16 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates r...

Страница 15: ...rion A Output lines 2kV Criterion A Surge voltage on input lines EN 61000 4 5 500V Criterion B housing 1kV Criterion B Surge voltage on output lines EN 61000 4 5 500V Criterion B housing 1kV Criterion...

Страница 16: ...ontrolled The user has to take this into consideration to stay below the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 Atmospheric pressure...

Страница 17: ...x 500Vac Power port to signal port max 500Vac Power port signal port to housing Class of protection III A PE Protective Earth connection is not required Degree of protection IP20 According to EN IEC 6...

Страница 18: ...pment Applicable for US and Canada E File E198865 UL 2367 UL Certificate Recognized component for category QVRQ UL 2367 Standard for Solid State Overcurrent Protectors Applicable for US E File E342020...

Страница 19: ...0mm 5 12 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 370g 0 82lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a...

Страница 20: ...ly of the 24V is then only done by one fuse module preferably in the middle because the current is then better distributed in both directions and the permissible current of the power bus bars of 32A i...

Отзывы: