PIM90.241
Feb. 2022 / Rev. 2.0 DS-PIM90.241-EN
www.pulspower.com
5 / 17
All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
4.
DC-Input
Do not operate this device with DC-input voltage.
5.
Input Inrush Current
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and ambient
temperature dependent. The output load has no impact on the inrush current value.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V
AC 120V
AC 230V
typ.
14A
18A
40A
At 40°C, ambient, cold start
Inrush current I
peak
typ.
12A
16A
35A
At 25°C, ambient, cold start
max.
17A
22A
48A
At 40°C, ambient, cold start
max.
15A
20A
43A
At 25°C, ambient, cold start
Inrush energy I
2
t
max.
0.3A
2
s
0.4A
2
s
1.7A
2
s
At 40°C, ambient, cold start
Fig. 5-1: Typical turn-on behavior
at 120Vac and 25°C ambient
Fig. 5-2: Zoom into the first inrush peak
Fig. 5-3: Typical turn-on behavior
at 230Vac and 25°C ambient
Fig. 5-4: Zoom into the first inrush peak