background image

PIM90.241

Feb. 2022 / Rev. 2.0 DS-PIM90.241-EN

www.pulspower.com

4 / 17

All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

3.

AC-Input

The device is suitable to be supplied from TN, TT or IT mains networks.

AC input

nom.

AC 100-240V

AC input range

90-264Vac

Continuous operation

264-300Vac

For maximum 500ms

Allowed voltage L or N to
earth

max.

300Vac

Continuous, according to IEC 60664-1

Input frequency

nom.

50-60Hz

±6%

Turn-on voltage

typ.

75Vac

Steady-state value, see Fig. 3-1

Shut-down voltage

typ.

54Vac

Steady-state value, see Fig. 3-1

External input protection

See recommendations in chapter 2.

AC 100V

AC 120V

AC 230V

Input current

typ.

1.69A

1.45A

0.95A

At 24V, 3.8A, see Fig. 3-1

Power factor

typ.

0.6

0.58

0.45

At 24V, 3.8A, see Fig. 3-4

Start-up delay

typ.

50ms

50ms

50ms

See Fig. 3-2

typ.

21ms

21ms

20ms

At 24V, 3.8A constant current load,
0mF load capacitance, see Fig. 3-2

Rise time

typ.

42ms

42ms

40ms

At 24V, 3.8A constant current load,
2mF load capacitance, see Fig. 3-2

Turn-on overshoot

max.

100mV

100mV

100mV

See Fig. 3-2

Fig. 3-1: Input voltage range

Fig. 3-2: Turn-on behavior, definitions

Fig. 3-3: Input current vs. output

load at 24V output voltage

Fig. 3-4: Power factor vs. output

load at 24V output voltage

Содержание PIM90.241

Страница 1: ...Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO family is a compact industrial grade DIN rail power supply se...

Страница 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Страница 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Страница 4: ...g 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 69A 1 45A 0 95A At 24V 3 8A see...

Страница 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 14A 18A 40A At 40 C ambient...

Страница 6: ...unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 3 8A static value see Fig 6 1 Ripple and noise voltage max 100mVpp Bandwidth 20Hz to 20MHz 50Ohm Output curr...

Страница 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Страница 8: ...3W 0 3W 0 4W At no load typ 5W 4 3W 3 8W At 24V 1 9A half load typ 9 5W 7 9W 6W At 24V 3 8A full load The average efficiency is an assumption for a typical application where the device is loaded with...

Страница 9: ...1 9A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representation...

Страница 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Страница 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Страница 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Страница 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Страница 14: ...ins IT mains typ 130 A 270 A At 230Vac 50Hz TN TT mains IT mains max 80 A 190 A At 110Vac 50Hz TN TT mains IT mains max 120 A 270 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current ma...

Страница 15: ...witch mode power supply units ISA 71 04 1985 Manufacturer s Declaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Du...

Страница 16: ...rail height must be added to the unit depth to calculate the total required installation depth Weight 270g 0 6lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 1...

Страница 17: ...ANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phase...

Отзывы: