Puls PIM60.121 Скачать руководство пользователя страница 2

PIM60.121

Feb. 2022 / Rev. 2.0 DS-PIM60.121-EN

www.pulspower.com

2 / 17

All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

Index

1

Intended Use.......................................................

3

2

Installation Instructions......................................

3

3

AC-Input..............................................................

4

4

DC-Input..............................................................

5

5

Input Inrush Current..........................................

5

6

Output.................................................................

6

7

Hold-up Time......................................................

7

8

Efficiency and Power Losses..............................

8

9

Lifetime Expectancy...........................................

9

10 MTBF....................................................................

9

11 Functional Diagram............................................ 10
12 Terminals And Wiring........................................ 10
13 Front Side And User Elements........................... 11
14 EMC.....................................................................

12

15 Environment.......................................................

13

16 Safety and Protection Features......................... 14
17 Dielectric Strength.............................................. 14
18 Approved, Fulfilled or Tested Standards........... 15
19 Regulatory Product Compliance........................ 15
20 Physical Dimensions And Weight...................... 16
21 Application Notes............................................... 17

21.1

Charging of Batteries.............................. 17

21.2

Series Operation...................................... 17

21.3

Parallel Use to Increase Output Power... 17

21.4

Parallel Use for 1+1 Redundancy...........

17

21.5

Two Phase Operation.............................

17

21.6

Use in a Tightly Sealed Enclosure........... 17

The information given in this document is correct to the best of our knowledge and experience at the time of publication.
If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the word. As the
state of our knowledge and experience is constantly changing, the information in this data sheet is subject to revision. We
therefore kindly ask you to always use the latest issue of this document (available under www.pulspower.com).

No part of this document may be reproduced or utilized in any form without our prior permission in writing.

Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic
refuse.

TERMINOLOGY AND ABBREVIATIONS

PE and 

 Symbol

PE is the abbreviation for Protective Earth and has the same meaning as the symbol

 .

Earth, Ground

This document uses the term “earth” which is the same as the U.S. term “ground”.

t.b.d.

To be defined, value or description will follow later.

AC 230V

A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included. 
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)

230Vac

A figure with the unit (Vac) at the end is a momentary figure without any additional
tolerances included.

50Hz vs. 60Hz

As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50Hz mains
frequency. AC 120V parameters are valid for 60Hz mains frequency.

may

A key word indicating flexibility of choice with no implied preference.

shall

A key word indicating a mandatory requirement.

should

A key word indicating flexibility of choice with a strongly preferred implementation.

Содержание PIM60.121

Страница 1: ...surrounding temperatures up to 70 C The unit is designed as Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO fa...

Страница 2: ...tly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this doc...

Страница 3: ...th the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operatin...

Страница 4: ...ee Fig 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 15A 1A 0 6A At 12V 5A see F...

Страница 5: ...pact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 12A 15A 36A At 40 C ambient c...

Страница 6: ...ed value which can be achieved Factory settings typ 12V 0 2 at full load cold unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 5A static value see Fig 6 1 Ri...

Страница 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Страница 8: ...W 0 2W 0 3W At no load typ 3 6W 3 4W 3 4W At 12V 2 5A half load typ 7 5W 6 5W 6 2W At 12V 5A full load The average efficiency is an assumption for a typical application where the device is loaded with...

Страница 9: ...At 12V 2 5A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical represen...

Страница 10: ...1 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stran...

Страница 11: ...e noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally con...

Страница 12: ...terion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Crit...

Страница 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude U...

Страница 14: ...ns IT mains typ 100 A 200 A At 230Vac 50Hz TN TT mains IT mains max 60 A 100 A At 110Vac 50Hz TN TT mains IT mains max 80 A 150 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current max...

Страница 15: ...s for supply voltages up to 1100V Particular requirements and tests for switch mode power supply units and transformers for switch mode power supply units ISA 71 04 1985 Manufacturer s Declaration Onl...

Страница 16: ...ight Width 36mm 1 42 Height 90mm 3 54 Depth 91mm 3 58 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 225g 0 5lb DIN rail Use 35mm DIN rai...

Страница 17: ...DANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phase...

Отзывы: