background image

 EN 

PIC240.241D Installation Manual 

 

 

Product Description 

The PIC240.241D is a DIN-rail mountable single-phase-input power supply, which provides a 
floating, stabilized and galvanically separated SELV/PELV output voltage. 
 

Intended Use 

This device is designed for installation in an enclosure and is intended for commercial use, such as 
in industrial control, process control, monitoring and measurement equipment or the like. Do not use 
this device in equipment where malfunction may cause severe personal injury or threaten human 
life. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up 
to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to 
+70°C. Ensure that all strands of a stranded wire enter the terminal connection. 
Unused screw terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of overvoltage category III 
according to IEC 60664-1. Above 2000m the overvoltage category is reduced to level II. 
The device is designed as “Class of Protection” I equipment according to IEC 61140. 
Do not use without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage 
between the input terminal and the PE potential must not exceed 300Vac. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the 
product datasheet for use above 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left 
and right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the 
device is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) 
without additional protection device. If an external fuse is utilized, do not use circuit breakers smaller 
than 10A B- or 6A C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive loads and capacitive loads. If capacitors with a 
capacitance >2F are connected, the unit might charge the capacitor in an intermittent mode. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports an output voltage above 18V of a running device. 
The DC-OK relay monitors the output voltage of a running device. The contact is closed when the 
output voltage is above 21.4V. Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive 
loads. 
The device is equipped with an over-temperature protection. In case of a high temperature, the 
output shuts down and starts automatically again after cooling off. 
At heavy overloads (when output voltage falls below 13V), the device delivers continuous output 
current for 3-5s. After this, the output is switched off for 7s before a new start attempt with 1s is 
automatically performed. This cycle is repeated as long as the overload exists. 
Do not parallel devices for higher output currents. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as 
many devices in series as needed, providing the sum of the output voltage does not exceed 
150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The 
output shuts down and automatically attempts to restart. 

 

Technical Data

 

All values are typical figures specified at 230Vac 50Hz input 
voltage, 24V 10A output, 25°C ambient temperature and after a 5 
minutes run-in time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 – 28Vdc 

Factory setting 24.1V 

Output current 

10.0 – 8.6A 

Below +55°C ambient  

 

6.25 – 5.4A 

At +70°C ambient 

 

Derate linearly b55°C and +70°C

Input voltage AC 

AC 100 - 240V 

±10% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

2.17 / 1.18A 

At 120 / 230Vac 

Power factor 

0.98 / 0.93 

At 120 / 230Vac 

Input inrush current 

14 / 26A pk 

At 40°C, 120 / 230Vac 

Efficiency 

94.0 / 95.2% 

At 120 / 230Vac 

Power losses 

15.3 / 12.1W 

At 120 / 230Vac 

Hold-up time 

32 /32ms 

At 120 / 230Vac 

Temperature range 

-25 to +70°C 

 

Max. wire size (litz wire) 

4mm² Power 

terminals 

Wire size AWG 

AWG 20-10 

Power terminals 

Max. wire diameter 

2.8mm Power 

terminals 

Wire stripping length 

7mm / 0.28inch 

Power terminals 

Tightening torque 

1Nm / 9lb.inch 

Power terminals 

Max. wire size (litz wire) 

1.5mm²

 

 DC-OK 

terminals 

Wire size AWG 

AWG 24-16 

DC-OK terminals 

Max. wire diameter 

1.6 mm 

DC-OK terminals 

Wire stripping length 

7mm / 0.28inch 

DC-OK terminals 

Size (wxhxd) 

49x124x124mm Without 

DIN-rail 

Weight 

540g / 1.2lb 

 

 

Functional Diagram 

+

+

-
-

Output

Over-

Voltage

Protection

PFC

Converter

Voltage

Regulator

Power

Converter

Output

Filter

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter

V

OUT

L

N

DC-OK
Contact

DC-OK

LED

DC-ok
Relay

13

14

 

 

Output Characteristic 

Output voltage

15A

24V

Output current

13V

0V

2.5A

5.0A

7.5A

12.5A

0A

Adjustment range

28V

A

B

10A

A: continuous current
B: intermitted current

 

 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-25

10A

0

+55

+70°C

6.3A

 

 

Отзывы: