PIM90.245
Feb. 2022 / Rev. 2.0 DS-PIM90.245-EN
www.pulspower.com
4 / 18
All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
3.
AC-Input
The device is suitable to be supplied from TN, TT or IT mains networks.
AC input
nom.
AC 100-240V
AC input range
90-264Vac
Continuous operation
264-300Vac
For maximum 500ms
Allowed voltage L or N to
earth
max.
300Vac
Continuous, according to IEC 62477-1
Input frequency
nom.
50-60Hz
±6%
Turn-on voltage
typ.
75Vac
Steady-state value, see Fig. 3-1
Shut-down voltage
typ.
54Vac
Steady-state value, see Fig. 3-1
External input protection
See recommendations in chapter 2.
AC 100V
AC 120V
AC 230V
Input current
typ.
1.69A
1.45A
0.95A
Power factor
typ.
0.6
0.58
0.45
Start-up delay
typ.
50ms
50ms
50ms
typ.
21ms
21ms
20ms
At 24V, 3.8A constant current load,
0mF load capacitance, see Fig. 3-2
Rise time
typ.
42ms
42ms
40ms
At 24V, 3.8A constant current load,
2mF load capacitance, see Fig. 3-2
Turn-on overshoot
max.
100mV
100mV
100mV
Fig. 3-1: Input voltage range
Fig. 3-2: Turn-on behavior, definitions
Fig. 3-3: Input current vs. output
load at 24V output voltage
Fig. 3-4: Power factor vs. output
load at 24V output voltage