ML50.111 Installation Manual 

 

 

 

Product Description 

The ML50.111 is a DIN-rail mountable single-phase-input power supply, which provides a floating, 
stabilized and galvanically separated SELV/PELV output voltage. 
The output of the device fulfils the requirements for a limited power source acc. to NEC Class 2. 
The device is optimized for parallel use to increase the output current or for redundant power supply 
systems. For an easy replacement, the device is equipped with pluggable screw terminals. 

Intended Use 

This device is designed for installation in an enclosure and is intended for commercial use, such as 
in industrial control, process control, monitoring and measurement equipment or the like. Do not use 
this device in equipment where malfunction may cause severe personal injury or threaten human 
life. 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up 
to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to 
+70°C. Ensure that all strands of a stranded wire enter the terminal connection. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The housing of the device provides a degree of protection of IP20. The housing does not provide 
protection against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of overvoltage category II 
according to IEC 60664-1. 
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage 
between the input terminals and the PE potential must not exceed 300Vac. 
The input can also be powered from batteries or similar DC sources. The continuous voltage 
between the supply voltage and the PE/ground potential must not exceed 375Vdc. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 0mm left 
and right side. Increase the 0mm to 15mm in case the adjacent device is a heat source. 
The device is designed, tested and approved for branch circuits up to 16A (IEC) or 15A (UL) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 
10A B- or 6A C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations. 
Substitution of components may impair suitability for this environment. 
Do not disconnect the device or operate the voltage adjustment unless power has been switched off 
or the area is known to be non-hazardous. 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including inductive and capacitive loads.  
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports a voltage on the output terminals above 19V. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
60°C. The device is featured with a “soft output regulation characteristic” in order to 
achieve current share between multiple devices. This regulates the output voltage in such a manner 
that the voltage at no load is approx. 4% higher than at nominal load. If more than three devices are 
connected in parallel, a diode, fuse or circuit breaker with a rating of 4A is required on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as 
many outputs in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 39V. The 
output shuts down and automatically attempts to restart. 
The DC-OK signal reports an output voltage above 19V on the output terminals. The signal is an 
open collector source output to feed loads up to 30mA. Connect the load (relay, LED, PLC) between 
the DC-OK pin and the negative output voltage. An external free-wheeling diode is not required. 

 

Technical Data

 

All values are typical figures specified at 230Vac, 50Hz input 
voltage, 24V 2.1A output load, 25°C ambient temperature and 
after a 5 minutes run-in time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 – 28Vdc 

Factory setting 24.5V 

Output current 

2.1 – 1.8A 

Below +60°C ambient  

 

1.6 – 1.3A 

At +70°C ambient 

 

Derate linearly b60°C and +70°C

Input voltage AC 

AC 100 – 240V 

-15% / +10% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

0.83 / 0.52A 

At 120 / 230Vac 

Power factor 

0.56 / 0.48 

At 120 / 230Vac 

Input voltage DC 

DC 110-300V 

-20% / +25% 

Input current DC 

0.51 / 0.19A 

At 110 / 300Vdc 

Input inrush current 

17 / 35A pk 

At 120 / 230Vac, 40°C, 
cold start 

Efficiency 

88.4 / 89.0% 

At 120 / 230Vac 

Power losses 

6.6 / 6.2W 

At 120 / 230Vac 

Hold-up time 

40 / 180ms 

At 120 / 230Vac 

Temperature range 

-10 to +70°C 

 

Max. wire size (litz wire) 

2.5mm²  

Wire size AWG 

AWG 24-12 

 

Max. wire diameter 

2.4mm  

Wire stripping length 

7mm / 0.28inch 

 

Tightening torque 

0.45Nm / 4lb.inch   

Size (wxhxd) 

45x75x91mm Without 

DIN-rail 

Weight 

240g / 0.53lb 

 

 

Functional Diagram 

Input
Fuse
&
Input
Filter

L

N

Output Over-

Voltage

Protection

Input
Rectifier
&
Inrush
Limiter

Output

Voltage

Controller

+

+

-

DC-OK

Output

Filter

V

OUT

DC-ok

LED

Power

Converter

-

 

Output Characteristic 

Output voltage

4.0A

24V

Output current

0V

2.0A

3.0A

0A

Adjustment range

28V

1.0A

2.5A

A: 100Vac
B: 120Vac
C: 230Vac

0.5A

1.5A

3.5A

A: for 100Vac mains
B: for 120Vac mains
C: for 230Vac mains

A

B

C

 

 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-10

2.1A

+60

+70°C

1.6A

 

 