background image

 

 

MLY02.100

 

MiniLine

 

MLY-Series 

DC12-48V

 

(120V),

 

10A,

 

D

UAL 

R

EDUNDANCY 

M

ODULE

 

 

 

1.

 

I

NTENDED 

U

SE

 

This redundancy module is designed for installation in an enclosure and is intended for the general use such as in 
industrial control, office, communication, and instrumentation equipment. 

This redundancy module can be used with any type of power supply as long as the maximum ratings are not exceeded. 
It is suitable for power supplies with constant current overload behavior as well as any kind of “Hiccup” overload 
behavior. 

Do not use this redundancy module in equipment, where malfunction may cause severe personal injury or threaten 
human life. 

This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations. 

 

 

2.

 

I

NSTALLATION 

R

EQUIREMENTS

 

This device may only be installed and put into operation by qualified personnel. 

This device does not contain serviceable parts. 

If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to 
the factory for inspection. 

Mount the unit on a DIN-rail so that the input terminals are located on the top and the output terminals on the 
bottom of the unit. For other mounting orientations see de-rating requirements of chapter 16.6. in this document. 

This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do 
not cover the ventilation grid (e.g. cable conduits) by more than 30%! 

Keep the following installation clearances:  
40mm on top, 
20mm on the bottom,  
5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the 
rated output current. Increase the side clearance to 15mm in case the adjacent device is a heat source (e.g. another 
power supply). 

 

 

WARNING

  Risk of electrical shock, fire, personal injury or death. 

-  Turn power off before working on the device. Protect against inadvertent re-powering. 
-  Make sure that the wiring is correct by following all local and national codes. 
-  Do not open, modify or repair the unit. 
-  Use caution to prevent any foreign objects from entering the housing. 
-  Do not use in wet locations or in areas where moisture or condensation can be expected. 
-  Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns. 

 

Notes for use in hazardous location areas: 

The redundancy module is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II 
Category 3 (Zone 2) environments and is evaluated according to EN 60079-0:2009 and EN 60079-15:2010. 

WARNING EXPLOSION HAZARDS!  

Substitution of components may impair suitability for this environment. Do not disconnect the unit unless power has 
been switched off or the area is known to be non-hazardous.  

A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the 
requirements of the EN 60079-15:2010. 

 

Apr. 2014 / Rev. 1.3 DS-MLY02.100-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 

  

   

3/16

Содержание MiniLine MLY-Series

Страница 1: ...low a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation SHORT FORM DATA Input voltage DC 12 48V 25...

Страница 2: ...with standard tolerances usually 15 included E g DC 12V describes a 12V battery disregarding whether it is full 13 7V or flat 10V 24Vdc A figure with the unit Vdc at the end is a momentary figure wit...

Страница 3: ...by more than 30 Keep the following installation clearances 40mm on top 20mm on the bottom 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50 of th...

Страница 4: ...e applied to the output continuously allowed Note 1 Each input can be loaded up to 10A At currents above 10A the other input should not be loaded It is preferable to parallel the two inputs in order t...

Страница 5: ...oltage drop when only one input draws current Voltage Drop U1 UOUT Not used or power supply with lower voltage V A QS10 241 24V 10A I1 U1 Output A V IOUT UOUT Variable Load 0 10A Input 1 Input 2 Outpu...

Страница 6: ...ears at 24V and 40 C min 25 years at 24V and 25 C MTBF SN 29500 IEC 61709 84 868 000h at 24V 40 C 125 266 000h at 24V 25 C MTBF MIL HDBK 217F 71 454 000h at 24Vand 40 C Ground Benign GB40 81 453 000h...

Страница 7: ...shipped in open position Fig 6 1 Connecting a wire Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambien...

Страница 8: ...m Input 1 Input 2 Output 8 FRONT SIDE AND USER ELEMENTS Fig 8 1 Front side A Output terminals B Input terminals for input 1 C Input terminals for input 2 Apr 2014 Rev 1 3 DS MLY02 100 EN All parameter...

Страница 9: ...61000 4 8 50Hz 30A m Criterion A Criterions A Redundancy module shows normal operation behavior within the defined limits Notes A test is not applicable according to EN 61000 6 2 since the device does...

Страница 10: ...664 1 4 3 3 2 1 Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical substances and is suitable for use in paint sho...

Страница 11: ...ansient protection not included Internal input fuse not included 12 SAFETY FEATURES Input output separation no galvanic separation 200V epitaxial diode between input and output Safety level of output...

Страница 12: ...val for Canada CAN CSA C22 2 No 107 1 CAN CSA 60950 1 03 UL60950 1 HazLoc Class 1 Div 2 ANSI ISA 12 12 01 2007 LISTED for use in Hazardous Location Class I Div 2 T4 Groups A B C D systems U S A ANSI I...

Страница 13: ...h 91mm to calculate the total required installation depth Installation clearances See chapter 2 Fig 14 1 Front view Fig 14 2 Side view 15 ACCESSORIES DIN Rail bracket for wall or panel mount A suitabl...

Страница 14: ...lies to the same value 16 2 INDUCTIVE AND CAPACITIVE LOADS The unit is designed to supply any kind of loads including unlimited capacitive and inductive loads 16 3 EXAMPLE 1 1 REDUNDANCY 1 1 Redundanc...

Страница 15: ...IN 2 I I I Note Use separate mains systems for each power supply whenever it is possible 16 5 EXAMPLE BATTERY BACK UP A battery back up requires one power supply and one MLY02 100 redundancy module Pl...

Страница 16: ...andard orientation Redundancy Module INPUT OUTPUT Output Current 0 10 20 30 40 60 C 2 6 8 10A 50 4 Ambient Temperature Fig 16 5 Mounting Orientation B Upside down Redundancy Module INPUT OUTPUT Output...

Отзывы: