ML120.244
MiniLine-2
24V,
5A,
S
INGLE
P
HASE
I
NPUT
7.
H
OLD
-
UP
T
IME
Hold-up Time
typ.
71ms
at 24V, 2.5A, see Fig. 7-1
min.
60ms
at 24V, 2.5A, see Fig. 7-1
typ.
35ms
at 24V, 5A, see Fig. 7-1
min.
30ms
at 24V, 5A, see Fig. 7-1
Note: At no load, the hold-up time can be up to several seconds. The green DC-on LED is also on during this time
Fig. 7-1
Hold-up time vs. input voltage
Fig. 7-2
Shut-down behavior, definitions
0
15
30
75
90ms
200
210
230
240
260Vac
Hold-up Time
45
60
a
b
c
d
220
Input Voltage
250
a) 24V 2.5A typ.
b) 24V 2.5Amin.
c) 24V 5A typ.
d) 24V 5A min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.