![Puls MiniLine-2 ML30.241 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/puls/miniline-2-ml30-241/miniline-2-ml30-241_manual_1624301004.webp)
ML30.241
MiniLine-2
24V,
1.3A,
S
INGLE
P
HASE
I
NPUT
3.
AC-I
NPUT
AC input
nom.
AC 100-240V
-15% / +10%, TN/TT/IT-mains
AC input range
85-264Vac continuous
operation
264–300Vac
<
0.5s
Allowed voltage L or N to earth
max.
264Vac or 375Vdc
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
46Vac
see Fig. 3-1
Shut-down voltage
typ.
44Vac
see Fig. 3-1
AC 100V
AC 120V
AC 230V
Input current (rms)
typ.
0.63A
0.54A
0.3A
Power factor *)
typ.
0.55
0.52
0.49
at 24V, 1.3A see Fig. 3-4
Crest factor **)
typ.
3.1
3.3
3.9
at 24V, 1.3A
Start-up delay
typ.
90ms***)
90ms***)
90ms***)
see Fig. 3-2
Rise time
typ.
40ms
40ms
40ms
at 24V, 1.3A, 0mF, see Fig. 3-2
typ.
90ms
90ms
100ms
at 24V, 1.3A, 1.3mF
Turn-on overshoot
max.
250mV 250mV 250mV
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
***) At low temperatures, start-up attempts may occur which extends the start-up delay
Fig. 3-1
Input voltage range
Fig. 3-2
Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
45V
300Vac
264V
Shut
-down
2V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3
Input current vs. output load at 24V
Fig. 3-4
Power factor vs. output load at 24V
1.3A
0.3
0.5
0.9
0
0
0.2
0.7A
Input Current, typ.
1.1
0.4
0.7
0.5
0.3
0.1
0.6
b
c
a
0.1
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
1.3A
0.3
0.5
0.7
1.1
0.40
0.45
0.50
0.55
0.60
0.65
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
0.9
Output Current
Mar. 2013 / Rev. 1.2 DS-ML30.241-EN
All parameters are specified at 24V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/23