All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
Apr. 2022 / Rev. 0.2 FPS300-EN
12 / 43
Parameter read
read out value range
Description
Actual output current
0-68 A
Actual average total output current
E-Fuse current
channel 1 to channel 4
0-15 A
Actual average E-Fuse output current for each E-Fuse
channel
E-Fuse output status
bit 0 - Ch1
bit 1 - Ch2
bit 2 - Ch3
bit 3 - Ch4
0 – off
1 - on
Actual state of E-Fuse output channels
Bit coded parameter.
0 - channel is off
1 - channel is on
E-Fuse trip status
channel 1 to channel 4
0 - No trip
1 - Over-load trip
2 - Short circuit trip
3 - Temperature trip
4 - Power budget trip
5 - Installation failure trip
6 - Sensor fault trip
7 - Fatal fault trip
Actual trip state of E-Fuse channel
If the E-Fuse has tripped, this parameter gives
detailed information about the reason. This
information might help for failure analysis in the
application.
Stress level
0 - “<5 %”
1 - “>5 %”
2 - “>25 %”
3 - “>50 %”
4 - “>75 %”
Stress level based on output power delivery.
This parameter gives an indication about the total
power consumption of the application and the
remaining margin.
Remaining Endurance LED
coded
0 - “<10 %”
1 - “>10 %”
2 - “>25 %”
3 - “>50 %”
4 - “>75 %”
This parameter gives an estimated remaining
endurcance indication.
Overall performance of the PSU might decrease at
low remaining endurance code.
Remaining Endurance
10-99 %
This parameter gives an estimated remaining
endurcance indication in percent.
Overall performance of the PSU might decrease at
low remaining endurance.