YRM2.DIODE 

 

 

Y-Series

 

24-60V, 20A, D

UAL 

R

EDUNDANCY 

M

ODULE

 

 

 

Nov 2006 / Rev. 1.0  DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

6/17 

 

10. T

ERMINALS AND 

W

IRING

 

 

  Type 

Screw terminals, Alarm-signal terminals are pluggable 
IP20 Finger safe construction. Suitable for field- and factory installation. 

  Ferrules 

allowed, but not required  

 

   

Input and output terminals 

Alarm-signal terminals 

 Solid 

wire 

0.5-6mm

2

 0.2-1.5mm

2

 

 Stranded 

wire 

0.5-4mm

2

 0.2-1.5mm

2

 

  American wire gauge 

20-10 AWG 

22-14 AWG 

  Wire stripping length 

10mm / 0.4inch 

6mm / 0.25inch 

  Recommended tightening torque 

0.8Nm / 7lb.in 

0.4Nm / 3.5lb.in 

Instructions for wiring:  

a) 

Use appropriate copper cables that are designed for an operating temperature of:  
60°C for ambient up to 45°C and  
75°C for ambient up to 60°C minimum.  

b) 

Follow national installation codes and installation regulations! 

c) 

Ensure that all strands of a stranded wire enter the terminal connection!  

d) 

Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire). 

e) 

Do not use the unit without PE connection. 

 

 

11. R

ELIABILITY

 

 

   

DC 24V 

 

  Lifetime expectancy 

min. 

> 25 years 

40°C, input: 2x10A, output: 20A, no electrolytic capacitors involved 

   

min. 

> 25 years 

40°C, input: 2x5A, output: 10A, no electrolytic capacitors involved 

   

min. 

> 25 years 

25°C, input: 2x10A, output: 20A, no electrolytic capacitors involved 

  MTBF SN 29500, IEC 61709 

T.B.D. 

40°C, input: 2x10A, output: 20A 

   

T.B.D. 

25°C, input: 2x10A, output: 20A 

  MTBF MIL HDBK 217F 

T.B.D. 

40°C, input: 2x10A, output: 20A, Ground Benign GB40 

   

T.B.D. 

25°C, input: 2x10A, output: 20A, Ground Benign GB25 

 

The 

Lifetime expectancy

 shown in the table indicates the operating hours (service life) and is determined by the 

lifetime expectancy of the built-in electrolytic capacitors.  

Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s 
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment. 

MTBF

 stands for 

M

ean 

T

ime 

B

etween 

F

ailure, which is calculated according to statistical device failures, and indicates 

reliability of a device. It is the statistical representation of the likelihood of the unit to fail and does not necessarily 
represent the life of a product. 

Содержание Dimension Y Series

Страница 1: ...t 20A output current Temperature range 25 C to 70 C Operational Derating 0 5A C 60 to 70 C The YRM2 DIODE is a redundancy module which can be used for various purposes The most popular application is...

Страница 2: ...16 23 8 Use in a Tightly Sealed Enclosure 16 23 9 Mounting Orientations 17 INTENDED USE The redundancy module shall only be installed and put into operation by qualified personnel This redundancy modu...

Страница 3: ...continuous see Fig 5 3 max 1x 30A Up to 5s Single use continuous see Fig 5 4 Peak input current max 150A Max 10ms per input Output current max 20A 30A Normal mode continuous up to 5s max 25A 37 5A At...

Страница 4: ...0 60Vdc 20A output current see Fig 6 1 Fig 6 1 Power losses vs output current Power Losses typ 0 0 5 10 20 4 8 12 16 20 24W 25A 15 Output Current 7 ALARM CONTACTS Both input voltages are monitored ind...

Страница 5: ...2 Alarm contact Input 1 ok Input 2 ok 9 FRONT SIDE AND USER ELEMENTS Fig 9 1 Front side Alarm contacts relays plug connector NO contact 11 12 Alarm contact for input 1 13 14 Alarm contact for input 2...

Страница 6: ...e cross section are permitted in one connection point except PE wire e Do not use the unit without PE connection 11 RELIABILITY DC 24V Lifetime expectancy min 25 years 40 C input 2x10A output 20A no e...

Страница 7: ...rge EN 61000 4 2 Contact discharge Air discharge 8kV 15kV Criterion A Criterion A Electromagnetic RF field EN 61000 4 3 80MHz 1GHz 10V m Criterion A Fast transients Burst EN 61000 4 4 Input Output Ala...

Страница 8: ...Vibration random 0 5m 2 s 3 2 hours axis IEC 60068 2 64 Shock 30g 6ms 20g 11ms 3 bumps direction 18 bumps in total IEC 60068 2 27 Altitude 0 to 6000m 0 to 20 000ft Reduce output power or ambient temp...

Страница 9: ...n case of a protection event audible noise may occur 15 SAFETY Input output separation 200V Epitaxial diode Class of protection III PE Protective Earth connection not mandatory PE resistance 0 1Ohm Be...

Страница 10: ...ory C EMC2 18 FULFILLED STANDARDS EN IEC 60204 1 Safety of Electrical Equipment of Machines EN IEC 61131 2 Programmable Controllers EN 50178 Electronic Equipment in Power Installations 19 USED SUBSTAN...

Страница 11: ...l must be located on top and output terminal on the bottom For other orientations see section 0 Cooling Convection cooled no forced cooling required Do not cover ventilation grid e g cable conduits by...

Страница 12: ...ched so that the two steel brackets can be mounted Fig 22 1 ZM1 WALL Wall Mounting Bracket Fig 22 2 Assembled Wall Mounting Bracket ZM11 SIDE Side mounting bracket This bracket is used to mount Dimens...

Страница 13: ...se separate input fuse for each power supply Use Three phase power supplies to gain functional safety if one phase fails When Single phase power supplies are utilized connect them to different phases...

Страница 14: ...y 20A output current L1 L2 L3 PE Power Supply 24V 20A Failure Monitor 20A Load I I I optional optional I I I L1 L2 PE L3 YRM2 DIODE OUT IN 1 IN 2 IN 1 IN 2 YRM2 DIODE OUT IN 1 IN 2 IN 1 IN 2 L1 L2 L3...

Страница 15: ...load instead of charging the battery Use a fuse between battery and YRM2 DIODE Fig 23 4 Wiring diagram 10A Battery back up Failure Monitor 10A Load optional L N PE 24V Battery I Battery Charger L N PE...

Страница 16: ...itor Buffered Load e g Controller optional I I I L1 L2 PE L3 Load e g Motor L1 L2 L3 PE Power Supply 24V 20A Buffer Module YRM2 DIODE OUT IN 1 IN 2 IN 1 IN 2 23 8 USE IN A TIGHTLY SEALED ENCLOSURE Whe...

Страница 17: ...rve A2 Max allowed output current results approx in half the lifetime expectancy of A1 Fig 23 7 Mounting Orientation A Standard Orientation Redundancy Module INPUT OUTPUT Output Current 0 10 20 30 40...

Отзывы: