background image

QS10: Power Supply Instruction Manual  
QS10: Bedienungsanleitung für Stromversorgung 

 

 

 

Technical Data 

1)

 Technische 

Daten 

1)

 

 

QS10.121

QS10.121-A1

11)

QS10.241 

QS10.241-A1

11) 

QS10.241-C1

11) 

QS10.241-D1

11)

 

QS10.301

QS10.481

QS10.481-A1

11)

QS10.481-D1

11)

Output Voltage 

Ausgangsspannung 

nom.

DC 12-15V

DC 24-28V 

DC 28-32V

DC 48-56V

Factory Setting at Full Load 

Werkseinstellung bei Nennlast 

typ.

12.0V

24.1V 30.0V

48.0V

Output Current 

continuous

 Ausgangsstrom 

dauernd

 

nom.

15A at 12V

13.5A at 15V

10A at 24V 

9A at 28V 

8.5A at 28V
7.5A at 32V

5A at 48V

4.3A at 56V

 

for typical 4s

 

 

 

für typisch 4s

 

nom.

22.5A at 12V

18A at 15V

15A at 24V 

13.5A at 28V 

12.75A at 28V
11.25A at 32V

7.5A at 48V
6.5A at 56V

Output Power 

continuous

 Ausgangsleistung 

dauernd

 

nom.

180W

240W 240W

240W

 

for typical 4s

 

 

 

für typisch 4s

 

nom.

270W

360W 360W

360W

Output Ripple & Noise Voltage 

2)

 Ausgangswelligkeit 

2

max.

50mVpp

50mVpp 50mVpp

100mVpp

AC Input Voltage 

AC Eingangsspannung 

nom.

AC 100-240V  ±15%

AC 100-240V  ±15% 

AC 100-240V  ±15%

AC 100-240V  ±15%

Input Frequency 

Eingangsfrequenz 

nom.

50-60Hz

50-60Hz 50-60Hz

50-60Hz

AC Input Current 

3)

 AC 

Eingangsstrom 

3)

 

typ.

1.65A / 0.93A

2.22A / 1.22A 

2.22A / 1.22A

2.22A / 1.22A

Power Factor 

3)

 Leistungsfaktor 

3)

 

typ.

0.98 / 0.92

0.98 / 0.92 

0.98 / 0.92

0.98 / 0.92

Allowed Voltage L or N to Earth 

Erlaubte Spannung L oder N zu Erde 

max.

276Vac / 375Vdc

276Vac / 375Vdc 

276Vac / 375Vdc

276Vac / 375Vdc

EN 61000-3-2 

EN 61000-3-2 

PFC-Norm

Yes / Ja

Yes / Ja 

Yes / Ja

Yes / Ja

DC Input Voltage 

10

 DC 

Eingangsspannung 

10

 

-D1

11)

 Version

All others DC 110-150V

 -20%/+25%

DC 110-300V

-20%/+25% 

DC 110-150V

 -20%/+25%

  DC 110-150V

 -20%/+25%

DC 110-300V

-20%/+25%

DC 110-150V

 -20%/+25%

Input Inrush Current 

4)

 Einschaltspitzenstrom 

4)

 

typ.

7A peak

7A peak 

7A peak

7A peak

Hold-up Time 

3)

 Pufferzeit 

3)

 

typ.

32ms / 32ms

27ms / 28ms 

22ms / 23ms

27ms / 28ms

Efficiency 

3)

 Wirkungsgrad 

3)

 

typ.

91.5% / 91.8%

92.3% / 93.0% 

92.3% / 93.0%

91.2% / 92.0%

Power Losses 

3)

 Verlustleistung 

3)

 

typ.

16.7W / 16.1W

20.0W / 18.1W 

20.0W / 18.1W

23.2W / 20.9W

Operational Temperature Range Betriebstemperaturbereich 

nom.

-25°C - +70°C

-25°C - +70°C 

-25°C - +70°C

-25°C - +70°C

Output Derating 

Leistungsrücknahme 

+60°C to +70°C

6W/°C

6W/°C 

6W/°C

6W/°C

Storage Temperature Range 

Lagertemperaturbereich 

nom.

-40°C - +85°C

-40°C - +85°C 

-40°C - +85°C

-40°C - +85°C

Humidity 

5

)

 Feuchte 

5)

 

IEC 60068-2-30

5 - 95% r.H.

5 - 95% r.H. 

5 - 95% r.H.

5 - 95% r.H.

Vibration Schwingen 

IEC 60068-2-6

2g

2g 

2g

2g

Shock Schocken 

IEC 60068-2-27

30g 6ms, 20g 11ms

30g 6ms, 20g 11ms 

30g 6ms, 20g 11ms

30g 6ms, 20g 11ms

Degree of Pollution 

(non-conductive)

 Verschmutzungsgrad 

(nicht leitend)

 

EN 50178 / IEC 62103

2

2

2

Degree of Protection 

Schutzart 

EN 60529

IP20

IP20 

IP20

IP20

Class of Protection 

Schutzklasse 

IEC 61140

6)

6)

 I 

6)

6)

Over-temperature Protection 

Übertemperaturschutz 

OTP

Yes / Ja

Yes / Ja 

Yes / Ja

Yes / Ja

Output Over-voltage Protection Überspannungsschutz 

am 

Ausgang 

OVP, max.

20Vdc

39Vdc 

45Vdc

60Vdc

Leakage Current 

7) 

TN, TT-mains 

  

IT-mains

 

PE- Ableitstrom 

7) 

TN, TT-Netze 

  

IT-Netze

 

max.
max.

0.38mA / 0.74mA
0.79mA / 1.29mA

0.38mA / 0.74mA 
0.79mA / 1.29mA 

0.38mA / 0.74mA
0.79mA / 1.29mA

0.38mA / 0.74mA
0.79mA / 1.29mA

Return Voltage Resistance 

8)

 Rückspeisefestigkeit 

8)

 

max.

18Vdc

35Vdc 35Vdc

58Vdc

Parallel Use 

12)

 Parallelschaltbar 

12)

 

-

Yes / Ja

Yes / Ja 

Yes / Ja

Yes / Ja

Serial Use 

13)

 Serienschaltbar 

13)

 

-

Yes / Ja

Yes / Ja 

Yes / Ja

Yes / Ja

Dimensions 

9)

  

(WxHxD

) Abmessungen 

9)

  

(BxHxT)

 

nom.

60x124x117mm

60x124x117mm 60x124x117mm

60x124x117mm

Weight Gewicht 

max.

930g, 2.05lb

900g, 1.98lb 

900g, 1.98lb

900g, 1.98lb

1)  All parameters are specified at 230Vac input voltage, nominal output current, 25°C ambient 

and after a 5 minutes run-in time unless otherwise noted. 

2)  50 Ohm measurement, bandwidth 20MHz 
3)  At 120Vac / 230Vac 
4)  Input inrush current electronically limited and is temperature independent. 
5)  Do not energize while condensation is present. 
6)  PE connection required (Ground). 
7)  Leakage current at 132Vac, 60Hz / 264Vac, 50Hz 
8)  Loads such as decelerating motors and inductors can feed voltage back to the output of the 

power supply. The figure represents the maximum allowed feed back voltage 

9)  Depth without DIN-rail. 
10) Use a battery or a similar DC source. Cpole to L and –pole to N. A supply from the 

intermediate DC-bus of a frequency converter is not recommended and can cause a 
malfunction or damage the unit. 

11) -C1 Version: with conformal coated PC-board 

-A1 Version: with conformal coating and ATEX approval; fulfills the ATEX directive 94/9/EC 
-D1 Version: with extended DC-Input range 
QS10.121-A1 and QS10.481-A1 are no standard products and are available upon request. 

12) A fuse (or diode) on the output is only required if more than three units are paralleled. 
13) Use only power supplies of the same type. The total voltage should not exceed 150Vdc. 

 

1)  Alle Werte gelten bei 230Vac Eingangsspannung, Nennausgangsstrom, 25°C Umgebungs-

temperatur und nach einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist. 

2)  50 Ohm Messung, Bandbreite 20MHz 
3)  Bei 120Vac / 230Vac 
4)  Der Einschaltstromstoß ist elektronisch begrenzt und temperaturunabhängig. 
5)  Nicht betreiben, solange das Gerät Kondensation aufweist. 
6)  PE Verbindung erforderlich. 
7)  Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz 
8)  Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils 

rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an. 

9)  Tiefe ohne DIN-Schiene 
10) Geeignet sind Batterien oder ähnliche Quellen. Den +Pol an L und –Pol an N anschließen.  

Ein Betrieb am Zwischenkreis von Frequenzumrichtern wird nicht empfohlen und kann zu 
Defekten oder Fehlfunktionen führen. 

11) -C1 Version: Gerät mit schutzlackierter Leiterplatte 

-A1 Version: Gerät mit Schutzlack und ATEX Zulassung; erfüllt die ATEX Richtlinie 94/9/EG 
-D1 Version: Gerät mit erweiterten DC-Eingangsspannungsbereich 
QS10.121-A1 und QS10.481-A1 sind keine Standardgeräte und nur auf Anfrage erhältlich. 

12) Bei mehr als drei Geräten wird eine Sicherung oder eine Diode zur Entkopplung benötigt.  
13) Nur gleiche Geräte bis zu einer Gesamtspannung von 150Vdc 

 

Installation 

Use DIN-rails according to EN 60715 with a height of 7.5 or 15mm. Mounting orientation must be 
output and input terminals on the bottom. For other orientations see datasheet. Do not obstruct air 
flow as the unit is convection cooled. Ventilation grid must be kept free of any obstructions. The 
following installation clearances must be kept when power supplies are permanently fully loaded: 
 

Left / right: 5mm (15mm in case the adjacent device is a heat source) 

 

40mm on top, 20mm on the bottom of the unit. 

Use in hazardous location areas 

Units which are marked with "Class I Div 2" are suitable for use in Class I Division 2 Groups A, B, 
C, D locations.  

Units which are marked with 

 II 3G Ex nA nC IIC T3 Gc or 

 II 3G Ex nA nC IIC T4 Gc are 

suitable for use in Group II Category 3 (Zone 2) environments and are evaluated according to EN 
60079-0:2009 and EN 60079-15:2010. 
WARNING EXPLOSION HAZARDS! 
Substitution of components may impair suitability for this environment. Do not disconnect the unit 
or operate the voltage adjustment unless power has been switched off or the area is known to be 
non-hazardous. A suitable enclosure must be provided for the end product which has a minimum 
protection of IP54 and fulfils the requirements of the EN 60079-15:2010. 

 

Installation 

Geeignet für DIN-Schienen entsprechend EN 60715 mit einer Höhe von 7,5 oder 15mm. Der 
Einbau hat so zu erfolgen, dass sich die Eingangs- und Ausgangsklemmen unten befinden. Für 
andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht behindern! Das Gerät ist für 
Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulation zu sorgen. Folgende 
Einbauabstände sind bei dauerhafter Volllast einzuhalten: 
 

Links / rechts: 5mm (15mm bei benachbarten Wärmequellen) 

 

Oben: 40mm, unten 20mm vom Gerät. 

Betrieb in explosionsgefährdeter Umgebung

 

Geräte, die mit "Class I Div 2" gekennzeichnet sind, sind für den Einsatz in Klasse I Division 2 
Gruppen A,B,C,D Umgebung geeignet.  

Geräte, die mit 

 II 3G Ex nA nC IIC T3 Gc oder 

 II 3G Ex nA nC IIC T4 Gc, gekennzeichnet 

sind, sind nach EN 60079-0:2009 und EN 60079-15:2010 getestet und kann in Gruppe II, 
Kategorie 3 (Zone 2) Umgebungen verwendet werden.  
ACHTUNG EXPLOSIONSGEFAHR! 
Veränderungen am Gerät können die Tauglichkeit für diese Umgebung beeinträchtigen. 
Anschlüsse nicht abklemmen und Spannungseinstellung nicht verändern, solange Spannung 
anliegt oder die Umgebung als explosionsgefährlich gilt. Das Gerät muss mindestens in ein IP54 
Gehäuse, welches den Anforderungen der EN 60079-15:2010 entspricht, eingebaut werden. 

 

Отзывы: