Puls Dimension Q-Series Скачать руководство пользователя страница 21

 

 

QTD20.241

 

 

Q-Series 

24V,

 

20A,

 

DC

 

I

NPUT

 

 

 

21.

 

A

PPLICATION 

N

OTES

 

21.1.

 

R

EPETITIVE 

P

ULSE 

L

OADING

 

Typically, a load current is not constant and varies over time. This DC/DC converter is designed to support loads with a 
higher short-term power demand (=BonusPower

®

). The short-term duration is hardware controlled by an output 

power manager and is available on a repeated basis. If the BonusPower

®

 load lasts longer than the hardware 

controller allows it, the output voltage will dip and the next BonusPower

®

 is available after the BonusPower

®

 recovery 

time (see chapter 5) has elapsed. 

To avoid this, the following rules must be met: 
a)

 

The power demand of the pulse must be below 125% of the nominal output power. 

b)

 

The duration of the pulse power must be shorter than the allowed BonusPower

®

 time. (see output section) 

c)

 

The average (R.M.S.) output current must be below the specified continuous output current.  
If the R.M.S. current is higher, the unit will respond with a thermal shut-down after a period of time. Use the 
maximum duty cycle curve (Fig. 21-2) to check if the average output current is below the nominal current. 

d)

 

The duty cycle must be below 0.75. 
 

 

Fig. 21-1

   Repetitive pulse loads, definitions 

 

Fig. 21-2

   Max. duty cycle curve 

 

100%

P

PEAK

T

PEAK

P

0

T

0

max.

125%

 

 

125%

100

0

0.2

0.4

0.6

0.75

Duty Cycle

105

110

115

120

P

PEAK

P

0

 = 10%

P

0

 = 50%

P

0

 = 75%

P

0

 = 100%

 

P

Base load (W) 

P

PEAK

  Pulse load (above 100%) 

T

0

 

Duration between pulses (s) 

T

PEAK

  Pulse duration (s) 

 

D

uty

C

ycle

T

0

 =

T

peak 

-

 

 (D

uty

C

ycle

 x T

peak

)

T

peak + 

T

0

T

peak

D

uty

C

ycle 

 =

 

 

Example: 

A load is powered continuously with 240W (= 50% of the rated output load). From time to time a peak 
power of 600W (= 125% of the rated output load) is needed for 1 second.  

 

The question is: How often can this pulse be supplied without overloading the DC/DC converter? 

 

-  Make a vertical line at P

PEAK

 = 125% and a horizontal line where the vertical line crosses the P

0

 = 50% 

curve. Read the max. duty cycle from the duty cycle-axis  (= 0.37) 

-

 

Calculate the required pause (base load) length T

0

:  

21/27

-

 

Result: The required pause length = 1.7s 

-

 

Max. repetition rate = pulse +pause length = 

2.7s

 

 

More examples for pulse load compatibility: 

P

PEAK

 

P

0

 

T

PEAK

 

T

0

 

 

P

PEAK

 

P

0

 

T

PEAK

 

T

0

 

600W 480W 

1s  >25s   

600W 240W 

0.1s >0.16s 

600W 0W  1s  >1.3s   

600W 240W 

1s  >1.6s 

540W 240W 

1s  > 

0.75s 

 

600W 240W 

3s  >4.9s 

D

uty

C

ycle

T

0

=

T

peak 

-

 

 (D

uty

C

ycle

 x T

peak

)

0.37

1s

 

-

 

 (0.37 x 1s)

=

= 1.7s

Oct. 2016 / Rev. 2.0 DS-QTD20.241-EN  
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

Содержание Dimension Q-Series

Страница 1: ...is usually unfiltered and have high EMI noise so the QTD20 has a very robust input stage and an appropriate input filter included Additionally the QTD20 is UL 508 approved and is equipped with input...

Страница 2: ...ranty in the legal sense of the word As the state of our knowledge and experience is constantly changing the information in this data sheet is subject to revision We therefore kindly ask you to always...

Страница 3: ...0mm on top 20mm on the bottom 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50 of the rated power Increase this clearance to 15mm in case the adj...

Страница 4: ...e typ 325Vdc Steady state value load independent see Fig 3 1 Input current typ 0 79A At 24V 20A see Fig 3 3 Start up delay typ 350ms See Fig 3 2 Rise time typ 70ms At 24V 20A only resistive load see F...

Страница 5: ...ush delay typ 350ms The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on Fig 4 1 Typical turn on behavior at nominal load and 25 C ambient temp...

Страница 6: ...n 25A Short term 4s load impedance 50mOhm see Fig 5 1 max 28A Short term 4s load impedance 50mOhm see Fig 5 1 Output capacitance typ 950 F Included in the DC DC converter 1 BonusPower short term power...

Страница 7: ...utput Power 1 2 3 4 5s min Power Demand Output Voltage Limitation by Power Manager Bonus Power disabled Recovery Time 100 125 Bonus Time The BonusPower is available as soon as power comes on and after...

Страница 8: ...onverter output Contact closes As soon as the output voltage reaches the adjusted output voltage Contact opens As soon as the output voltage dips more than 10 below the adjusted output voltage Short d...

Страница 9: ...load for the rest of the time Fig 8 1 Efficiency vs output current at 24V typ Fig 8 2 Losses vs output current at 24V typ Efficiency 4 6 8 10 12 14 16 18 20A 88 89 90 91 92 93 94 95 96 Output Current...

Страница 10: ...are devices MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representation of the lik...

Страница 11: ...at all strands of a stranded wire enter the terminal connection d Do not use the unit without PE connection e Ferrules are allowed 1 Insert the wire 2 Snap the lever To disconnect wire same procedure...

Страница 12: ...ltage on the output terminals is 90 of the adjusted output voltage or in case of a short circuit in the output On when the unit has switched off due to over temperature Input voltage is always require...

Страница 13: ...sion output lines IEC CISPR 16 1 2 IEC CISPR 16 2 1 5dB higher than average limits for DC power port according to EN 61000 6 4 Radiated emission EN 55011 EN 55022 Class A This device complies with FCC...

Страница 14: ...IEC 62103 EN 62477 1 altitudes up to 2000m II For altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 62477 1 not conductive LABS compatibility The unit does not release any silicone or o...

Страница 15: ...otect the unit against internal short circuits and ground faults The fuses are not user accessible A tripping of an internal fuse is caused by an internal fault In case of a protection event audible n...

Страница 16: ...ommend that either the pole the pole or any other part of the output circuit shall be connected to the protective earth system This helps to avoid situations in which a load starts unexpectedly or can...

Страница 17: ...lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm Housing material Body Aluminium alloy Cover zinc plated steel Installation clearances See chapter 2 Fig 19...

Страница 18: ...m brackets and the black plastic slider of the unit have to be detached so that the steel brackets can be mounted Fig 20 1 Wall panel mounting Fig 20 2 Mounting Dimensions Wall mounting bracket Oct 20...

Страница 19: ...be mounted For sideway DIN rail mounting the removed aluminum brackets and the black plastic slider need to be mounted on the steel bracket Fig 20 3 Side mounting without DIN rail brackets Fig 20 4 Si...

Страница 20: ...A Using MOSFET instead of diodes reduces the heat generation and the voltage drop between input and output The YR40 241 does not require an additional auxiliary voltage and is self powered even in cas...

Страница 21: ...itive pulse loads definitions Fig 21 2 Max duty cycle curve 100 PPEAK TPEAK P0 T0 max 125 125 100 0 0 2 0 4 0 6 0 75 Duty Cycle 105 110 115 120 PPEAK P0 10 P0 50 P0 75 P0 100 P0 Base load W PPEAK Puls...

Страница 22: ...two examples show typical voltage dips Fig 21 3 Peak load with 2x the nominal current for 50ms typ Fig 21 4 Peak load with 5x the nominal current for 5ms typ 10ms DIV Output Voltage Output Current 24V...

Страница 23: ...5A circuit breaker or blocking diode between the DC DC converter and the battery c Ensure that the output current of the DC DC converter is below the allowed charging current of the battery d Use only...

Страница 24: ...1 0mm 1 5mm 2 5mm C 2A 31m 39m 59m 86m C 3A 24m 31m 43m 68m C 4A 15m 15m 32m 41m C 6A B 6A 16m 25m 34m 58m MCB Power Supply AC DC Load Wire length S1 Fault simulation switch S1 B 10A Don t forget to c...

Страница 25: ...case one DC DC converter unit fails the other one is automatically able to support the load current without any interruption Redundant systems for a higher power demand are usually built in a N 1 meth...

Страница 26: ...ed enclosure the temperature inside the enclosure will be higher than outside In such situations the inside temperature defines the ambient temperature for the DC DC converter The following measuremen...

Страница 27: ...e A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 21 6 Mounting Orientation A Standard orientation DC DC Converter OUTPUT INPUT Output Current 0 10 20 30...

Отзывы: