![Puls DIMENSION CS5.243 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/puls/dimension-cs5-243/dimension-cs5-243_manual_1624261007.webp)
CS5.243
C-Line
24V,
5A,
S
INGLE
P
HASE
I
NPUT
Nov. 2020 / Rev. 2.1 DS-CS5.243-EN
All parameters are specified at 24V, 5A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/26
4.
DC-I
NPUT
Do not operate this power supply with DC-input voltage. Use the QS5.241 unit instead.
5.
I
NPUT
I
NRUSH
C
URRENT
After turn-on of the input voltage, an active inrush limitation circuit limits the input inrush current. Virtually no input
inrush current is generated.
The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V
AC 120V
Inrush current
max.
47A
peak
56A
peak
at +40°C ambient, cold start
typ.
38A
peak
45A
peak
at +40°C ambient, cold start
Inrush energy
max.
2A
2
s
3A
2
s
at +40°C ambient, cold start
Fig. 5-1
Typical input inrush current behavior
1 >
2 >
3 >
Input:
120Vac
Output:
24V, 5A
Ambient:
+40°C
Upper curve:
Input current (20A / DIV)
Medium curve: Input voltage (100V / DIV)
Lower curve:
Output voltage (10V / DIV)
Time scale:
10ms / DIV