CS20.241, CS20.241-A1
C-Series
24V,
20A,
S
INGLE
P
HASE
I
NPUT
Preliminary
3.
AC-I
NPUT
AC input
nom.
AC 100-240V
suitable for TN-, TT- and IT mains networks
AC input range
min.
100-264Vac
continuous operation
min.
85-100Vac
short term or with output derating (1%/V), see Fig. 15-1,
no damage between 0 and 100Vac
min.
264-300Vac
< 500ms
Allowed voltage L or N to earth
max.
264Vac
continuous, IEC 62103
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
84Vac
steady-state value, see Fig. 3-1
!
Shut-down voltage
typ.
39Vac
steady-state value at 5A load, see Fig. 3-1
typ.
53Vac
steady-state value at 10A load, see Fig. 3-1
typ.
74Vac
steady-state value at 20A load, see Fig. 3-1
AC 100V
AC 120V
AC 230V
Input current
typ.
5.25A
4.36A
2.33A
at 24V, 20A, see Fig. 3-3
Power factor *)
typ.
0.99
0.99
0.95
at 24V, 20A, see Fig. 3-4
Crest factor **)
typ.
1.5
1.5
1.65
at 24V, 20A
Start-up delay
typ.
900ms
850ms
700ms
!
Rise time
typ.
60ms
60ms
60ms
0mF, 24V, 20A, see Fig. 3-2
!
!
typ.
105ms
105ms
105ms
20mF, 24V, 20A, see Fig. 3-2
Turn-on overshoot
max.
200mV
200mV
200mV
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1
Input voltage range
Fig. 3-2
Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac
264V
Shut
-down
Start-up
delay
Rise
Time
Ov
ersh
oot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3
Input current vs. output load at 24V
Fig. 3-4
Power factor vs. output load
24A
2
4
6
8 10 12 14 16 18
0
1
2
3
4
5
6A
Output Current
Input Current, typ.
230V
ac
120
Vac
10
0V
ac
20 22
Power Factor, typ.
2
4
6
8 10 12 14 16 18
24A
0.75
0.8
0.85
0.9
0.95
1.0
Output Current
230Vac
100Vac, 120Vac
20 22
Jan. 2012 / Rev. 0.5 DS-CS20.241-EN
Preliminary
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany