Product Description 

The CPS20.481-D1 is a DIN-rail mountable DC/DC converter, which provides a floating, stabilized and 
galvanically separated SELV/PELV output voltage. 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring, measurement equipment or the like. 
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 

Installation Instructions 

Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the 
input terminals. Unused screw terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The isolation of the devices is designed to withstand impulse voltages up to 2.5kV according to IEC 
60664-1. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The input can be powered from batteries or similar DC sources. The continuous voltage between the 
input terminals and PE potential must not exceed 360Vdc. 
Check for correct input polarity. The device will not operate when the voltage is reversed. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 10A 
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II 
Category 3 (Zone 2) environments. 
Classification: ATEX: EPS 13 ATEX 1 555 X, II 3G EX nA nC IIC T3 Gc / IECEx EPS 13.0016X

 

WARNING EXPLOSION HAZARDS! 

Substitution of components may impair suitability for this environment. 
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or 
the area is known to be non-hazardous. 
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 
and fulfils the requirements of the EN 60079-0. 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive or capacitive loads. If capacitors with a capacitance >0.15F 
are connected, the unit might charge the capacitor in an intermittent mode. 
Do not apply return voltages from the load to the output higher than 63V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC OK LED reports an output voltage above 90% of the adjusted voltage of a running 
device. 
The DC OK relay monitors the output voltage and the contact is closed when the DC OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
At heavy overloads (when output voltage falls below 25V), the device delivers continuous output 
current for 2s. After this, the output is switched off for 18s before a new start attempt is automatically 
performed. This cycle is repeated as long as the overload exists. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 

60°C. The output voltage of all devices shall be adjusted to the same value (±100mV) in 

“Single Use” mode with the same load conditions on all units, or the units can be left with the factory 
settings. After the adjustments, set the unit to “Parallel Use” mode, in order to achieve load sharing. 
The “Parallel Use” mode regulates the output voltage in such a manner that the voltage at no load is 
approx. 4% higher than at nominal load. Energize all units at the same time. It also might be 
necessary to cycle the input power (turn-off for at least five seconds), if the output was in overload or 
short circuit. If more than three devices are connected in parallel, a diode, fuse or circuit breaker with a 
rating of 15A or 16A is required on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 60V. The output 
shuts down and automatically attempts to restart. 

 

Technical data

 

All values are typical figures specified at 300Vdc input voltage, 48V 10A 
output load

, 25°C ambient temperature and after a 5 minutes run-in time 

unless otherwise noted. 

Output voltage 

DC 48V 

Nominal 

Adjustment range 

48 

– 56Vdc 

Factory setting 48.0V 

Output current 

12.0 

– 10.3A 

Below +45°C ambient  

 

10.0 

– 8.6A 

At +60°C ambient 

 

7.5 

– 6.5A 

At +70°C ambient 

 

Derate linearly 

b45°C and +70°C 

Input voltage DC 

DC 110 - 300V 

±20% 

Input current DC 

4.68 / 1.69A 

At 110 / 300Vdc 

Input inrush current 

6 / 4A pk 

At 110 / 300Vdc 

Efficiency 

93.1 / 94.6% 

At 110 / 300Vdc 

Power losses 

35.6 / 27.4W 

At 110 / 300Vdc 

Hold-up time 

26 / 26ms 

At 110 / 300Vdc 

Temperature range 

-25 t

o +70°C 

 

Max. wire size (litz wire) 

4mm² 

Power terminals 

Wire size AWG 

AWG 20-10 

Power terminals 

Max. wire diameter 

2.8mm 

Power terminals 

Wire stripping length 

7mm / 0.28inch 

Power terminals 

Tightening torque 

1Nm / 9lb.inch 

Power terminals 

Max. wire size (litz wire) 

1.5mm²

 

 

Signal terminals 

Wire size AWG 

AWG 26-14 

Signal terminals 

Max. wire diameter 

1.5 mm 

Signal terminals 

Wire stripping length 

7mm / 0.28inch 

Signal terminals 

Size 

(wxhxd)

 

65x124x127mm 

Without DIN-rail 

Weight 

940g / 2.1lb 

 

 
 

Functional diagram 

Single /

Parallel

Use

+

+

-
-

Output

Over-

Voltage

Protection

Boost

Converter

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Reverse
Polarity Prot.
Inrush Current
Limiter

13

14

Output

Voltage

Regulator

Output

Voltage
Monitor

V

OUT

DC-ok
Contact

DC-ok

LED

DC-ok
Relay

+

-

 

 
 

Output characteristic 

Output voltage (single use)

48V

Output current

24V

0V

5A

15A

20A

0A

Adjustment range

56V

10A

A: continuous current
B: intermitted current

A

B

 

 
 

Temperature range 

Allowed output current at 48V

Ambient temperature

0A

-25

A: 88Vdc, continuous
B: 100-360Vdc, continuous
C: short term (max. 5s)

12A

+25

0

+45

+70°C

7.5A

B

C

10A

+60

A

 

 