CD5.121 Installation Manual 

 

 

 

 

Product Description 

The CD5.121 is a DIN-rail mountable DC/DC converter, which provides a floating, stabilized and 
galvanically separated SELV/PELV output voltage. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like. Do not use this 
device in equipment where malfunction may cause severe personal injury or threaten human life. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temper

ature of 60°C for ambient temperatures up to 

+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of 1.5kV according to IEC 60664-
1. 
The input can be powered from batteries or similar DC sources. The voltage between the input 
terminals and ground must not exceed 60Vdc continuously. The ripple voltage in the low frequency 
range between 50Hz and 10kHz must be negligible when used in marine applications. 
The input must be powered from a PELV or SELV source or an "Isolated Secondary Circuit" in order to 
maintain a SELV or PELV output. 
Check for correct input polarity. The device will not operate when the voltage is reversed. 
A disconnecting means shall be provided for the input of the device. 
The device is designed as “Class of Protection III” equipment according to IEC 61140. A PE (ground) 
connection is not required. However, connecting the chassis ground terminal to ground can be 
beneficial to gain a high EMI immunity. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 50A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 8A C-
Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II 
Category 3 (Zone 2) environments. 
Classification: ATEX: EPS 08 ATEX 1 142 X, II 3G EX ec nC IIC T4 Gc / IECEx EPS 14.0001X 

WARNING EXPLOSION HAZARDS! 

Substitution of components may impair suitability for this environment. 
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or 
the area is known to be non-hazardous. 
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 
and fulfils the requirements of the EN 60079-0. 
Reduced output current conditions must be considered for high ambient temperatures and non-
standard mounting orientations. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive and capacitive loads. 
Do not apply return voltages from the load to the output terminals higher than 16V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports a voltage on the output terminals above 8.5Vdc, which is produced by 
the device itself. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
45

°C. The output voltage shall be adjusted to the same value (±100mV) with the same load 

conditions on all devices, or the devices can be left with the factory settings. If more than three 
devices are connected in parallel, a diode, fuse or circuit breaker with a rating of 15 or 16A is required 
on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 16.8V. The 
output shuts down and automatically attempts to restart. 
 

 

Technical Data

 

All values are typical figures specified at 24Vdc input voltage, 12V, 8A 
output load, 

25°C ambient and after a 5 minutes run-in time unless 

otherwise noted. 

Output voltage 

DC 12V 

Nominal 

Adjustment range 

12 

– 15Vdc 

Factory setting 12.0V 

Output current 

9.6 

– 7.7A 

Below 

+45°C ambient 

 

8.0 

– 6.4A 

A

t +60°C ambient 

 

6.0 

– 4.8A 

A

t +70°C ambient 

 

Derate linearly 

b45 and +70°C 

Input voltage 

DC 24V 

-25% / +35% 

 

See also low input voltage diagram below 

Input current 

4.6A 

 

Input inrush current 

1.2A pk 

Temp. independent 

Efficiency 

88.2% 

 

Power losses 

12.8W 

 

Hold-up time 

7ms 

 

Temperature range 

-

25°C to +70°C 

 

Max. wire size (litz wire) 

4mm² 

For all terminals 

Wire size AWG 

AWG 20-10 

For all terminals 

Max. wire diameter 

2.8mm 

For all terminals 

Wire stripping length 

7mm / 0.28inch 

For all terminals 

Tightening torque 

1Nm / 9lb.inch 

For all terminals 

Size 

(wxhxd)

 

32x124x102mm 

Without DIN-rail 

Weight 

425g / 0.94lb 

 

 

Functional Diagram 

+

+

-
-

V

OUT

Input
Fuse
&
Input
Filter

Output

Voltage

Regulator

Output

Filter

DC-

OK

Output

Over-

Voltage

Protection

Reverse
Polarity
Protection
&
Inrush
Limiter

Chassis

Ground

+

-

Power

Converter

 

 

Output Characteristic 

Output voltage

16A

12V

Output current

6V

0V

2A

6A

10A

12A

0A

Adjustment range

15V

4A

14A

8A

 

 

Temperature Range 

Allowed output current at 12V

Ambient temperature

0A

-25

A: continuous
B: short term (max. 60s)

9.6A

+25

0

+45

+70°C

6.0A

A

B

8.0A

+60

 

 

Temperature Range 

Allowed output at low input voltages

Input voltage

0A

14

A: ambient < 45°C
B: ambient < 60°C

9.6A

6.0A

7.5A

16

18

20

22

24V

A

8.0A

B

 

 