CD10.241 Installation Manual 

 

 

 

Product Description 

The CD10.241 is a DIN-rail mountable DC/DC converter, which provides a floating, stabilized and 
galvanically separated SELV/PELV output voltage. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like. Do not use this 
device in equipment where malfunction may cause severe personal injury or threaten human life. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The input can be powered from batteries or similar DC sources. The voltage between the input 
terminals and ground must not exceed 60Vdc continuously. 
The input must be powered from a PELV or SELV source or an "Isolated Secondary Circuit" in order to 
maintain a SELV or PELV output. 
Check for correct input polarity. The device will not operate when the voltage is reversed. 
A disconnecting means shall be provided for the input of the device. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). See additional requirements in the product 
datasheet for use above 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 50A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 20A B- or C-
Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive and capacitive loads. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports a voltage on the output terminals above 21Vdc. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
45°C. The output voltage shall be adjusted to the same value (±100mV) with the same load 
conditions on all devices, or the devices can be left with the factory settings. If more than three 
devices are connected in parallel, a diode, fuse or circuit breaker with a rating of 15A or 16A is 
required on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32.5V. The 
output shuts down and automatically attempts to restart. 
 

 

Technical Data

 

All values are typical figures specified at 24Vdc input voltage, 24V, 10A 
output load, 25°C ambient and after a 5 minutes run-in time unless 
otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 – 28Vdc 

Factory setting 24.1V 

Output current 

12.0 – 10.3A 

Below +45°C ambient 

 

10.0 – 8.6A 

At +60°C ambient 

 

7.5 – 6.5A 

At +70°C ambient 

 

Derate linearly b45 and +70°C 

Input voltage 

DC 24V 

-25% / +46% 

Input current 

10.5A  

Input inrush current 

8A pk 

At 40°C, cold start 

Efficiency 

94.2%  

Power losses 

14.8W  

Hold-up time 

4ms  

Temperature range 

-25°C to +70°C 

 

Max. wire size (litz wire) 

4mm²  

Wire size AWG 

AWG 20-10 

 

Max. wire diameter 

2.8mm  

Wire stripping length 

7mm / 0.28inch 

 

Tightening torque 

1Nm / 9lb.inch 

 

Size 

(wxhxd)

 

42x124x117mm Without 

DIN-rail 

Weight 

500g / 1.1lb 

 

 
 
 

Functional Diagram 

+

+

-

-

V

OUT

Input
Fuse
&
Input
Filter

Output

Voltage

Regulator

Output

Filter

DC-

OK

Output

Over-

Voltage

Protection

Reverse

Polarity

Protection

&

Inrush

Limiter

PE

+

-

Power

Converter

 

 
 

Output Characteristic 

Output voltage

15A

24V

Output current

12V

0V

3A

6A

9A

12A

0A

Adjustment range

28V

 
 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-25

A: continuous

B: short term (max. 60s)

12A

+25

0

+45

+70°C

7.5A

A

B

10A

+60

 