ML60.122
MiniLine-2
12V,
4.5A,
S
INGLE
P
HASE
I
NPUT
Fig. 3-5
De-rating requirements for
low input voltages
0
85Vac
10
20
30
40
50
60W
Input Voltage
A... < +45°C
B... < +60°C
A
B
90Vac
108Vac
Allowable
Output Power
4.
I
NPUT
I
NRUSH
C
URRENT
An electronic inrush current circuit limits the input inrush current after turn-on of the input voltage. The inrush current
is input voltage and ambient temperature independent.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V
AC 120V
AC 230V
Inrush current
max.
8A
peak
8A
peak
8A
peak
between -40°C and +70°C
typ.
6A
peak
6A
peak
6A
peak
between -40°C and +70°C
Inrush energy
max.
0.2A
2
s 0.2A
2
s 0.3A
2
s
between -40°C and +70°C
Fig. 4-1
Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
Input:
230Vac
Output:
12V, 4.5A
Ambient: 25°C
Upper curve: Input current 2A/DIV
Middle curve: Input voltage 200V/DIV
Lower curve: Output voltage 2.5V/DIV
Time basis:
20ms / DIV
Nov. 2015 / Rev. 1.4 DS--ML60.122-EN
All parameters are specified at 12V, 4.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/23