Important: Risk of electrical shock.
This device should only be installed by qualified personnel.
PSP Products Inc. | Phoenix Drive | Manassas, VA 20110
www.pspproducts.com | 800-648-6802 | [email protected]
Technical Assistance Call: 800-648-6802
After Hours Tech Support 443-600-3403
Rev: 05-01-19
Hurricane 1000 Series
Surge Protection Device 120 & 240-277 Volt AC
Installation Instructions
1. To assure proper installation measure the voltage on each phase and insure the correct device has been selected for your installation.
2. Turn off power to circuit where surge protector is to be installed.
3. Mount device so as to keep conductor length as short as possible. Cut wires to length and connect to circuit per wiring diagram below avoiding sharp bends or looping.
4. Reinstall covers, restore power and confirm diagnostic LED is Illuminated.
LED On = System Protected
LED Off = Replace Device
120 & 240-277 VAC Wiring Diagram
Installation Options
Diagnostic Operation
*All surge protection devices require good ground connection for effective operation
Device Ratings
H1S75-04N
H4S75-04N
Normal Voltage
120 VAC
240-277 VAC
Max. Operating Voltage (MCOV)
150 VAC
320 VAC
Max. Discharge Current (Imax)
75 kA
75 kA