INSTALLATION (CONT.)
WALL MOUNT USE:
A. Use provided wall mount template to install screws to the wall for keyhole
mounting of the NXG-Pro. NOTE: Ensure that AC Cord provided will
accomodate length needed from NXG-Pro AC cord power input connector to AC
wall outlet.
B. Follow steps A-D as instructed in Installation: Destop Use.
C. Use provided keyhole mounting option for NXG-Pro to hang on previously
installed screws.
BATTERY TYPE
Standard sealed lead acid battery rated at 12Vdc/7-8Ah.
BATTERY REPLACEMENT
As long as AC line power is available, NXG-Pro can resume operation while
battery is replaced.
PROCEDURE:
1. Remove the battery cover from back of NXG-Pro
2. Slide battery out of NXG-Pro and disconnect both red and black connection
wires from battery terminals and remove battery. NOTE: Follow battery
manufacturer specifications for proper disposal of battery.
3. Install new battery by connecting red wire to red (positive) battery terminal and
black wire to black (negative) terminal and slide battery into NXG-Pro battery
compartment.
4. Replace battery cover to resume normal operation.
TECHNICAL SPECIFICATION
INPUT
Voltage Range
Frequency Range
Input Power Cord
Output Ground Reference
OUTPUT #1
On Battery Output Voltage
Continuous Power Capacity
Efficiency (at 75% Max Load)
OUTPUT #2
Voltage Range
Frequency Range
Output Max Current
Input Ground Reference
BATTERY
Battery Type
Number of Battery
Typical Recharge Time
Replaceable
SURGE PROTECTION
AND FILTERING
Lightning/Surge Protection
MANAGEMENT
Battery Auto-Charge
PHYSICAL
Maximum Dimensions (LxWxD)
Weight (lb.)
ENVIRONMENT
Operating Temperature
Operating Humidity
Max Operating Elevaion
Max Storage Elevation
Storage Temperature
100Vac-240Vac
47-70Hz
NEMA 5-15/3-Prong Power Cord
Earth Grounded
12Vdc
36W
> 75%
100Vac-240Vac
50-60Hz
15A
Earth Grounded
SLA Battery
12Vdc/7-8Ah x 1
< 20 hrs
Yes
Yes (IEC 61000-4-5 2005 Level D)
Yes
6.8 x 3.2 x 7.3 (in)
7.16 (with battery)
-20C - 45C (-4F - 113F) at full power
0-95% noncondensing within enclosure
10,000ft (3,000m)
50,000ft (15,000m)
-20 - 45C (-4F - 113F)
FCC NOTICE
This equipment has been tested and found to comply with the limit for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with these instructions, may cause harmful
interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by
tuning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures: (1) Reorient or relocate
the receiving antenna. (2) Increase the separation between the equipment and
receiver. (3) Connect the equipment into an outlet on a circuit different from that
to which the receiver is connected. (4) Consult the dealer or an experienced
radio/TV technician for help.
CAUTION: Any changes or modifications could void the authority granted by the
FCC to operate this equipment.
NOTE: PowerTec Solutions International reserves the right to change or correct
the contents of this document and does not assume any responsiblity for
ommissions or errors.
PowerTec Solutions International
Corporate Headquarters
1290 Harbor Court
Hollywood, FL 33019
P: 615-879-3326
E: [email protected]