3

TROUBLE SHOOTING TESTS (4-Pipe System)

Voltage:

 When using a voltmeter across "White" and "Black", the  

 

   

voltage must be 120VAC.

To Check Continuity:

  (Using a Voltmeter with all loads connected)

A) 

When thermostat is calling for Cooling, meter should read

 

120VAC from "White" to "Blue".  When Cooling is deactivated,  

 

 

meter should read 0VAC from "White" to "Blue".

B)

 When thermostat is calling for Heating, meter should read  

 

 

120VAC from "White" to "Red".  When Heating is deactivated,  

 

 

meter should read 0VAC from "White" to "Red".

C) 

When thermostat is calling for High fan, meter should read  

 

 

120VAC from “White” to “Yellow w/Red Stripe”.  When High fan is   

 

deactivated, meter should read 0VAC from “White” to “Yellow  

 

 

w/Red Stripe”.

D) 

When thermostat is calling for Low fan, meter should read

 

120VAC from “White” to “Yellow”.  When Low fan is deactivated

 

meter should read 0VAC from “White” to “Yellow”.

Adjust setpoint as follows:

4°F (2°C) or more ABOVE room temperature

2°F to 4°F (1°C to 2°C) ABOVE room temperature

Within 0°F to 2°F (0°C to 1°C) of room temperature

2°F to 4°F (1°C to 2°C) BELOW room temperature

4°F (2°C) or more BELOW room temperature

Function Test:

HIGH

Lo

Hi

Hi

Lo

Lo

Hi

Lo

Hi

Lo

Lo

Hi

Lo

Hi

Hi

On

On

LOW

AUTO

COOL

HEAT

FAN SPEED

SYSTEM

On

On

Stop

(Dead band)*

*Deadband:  Active on start-up or initial call for heating or cooling

From the wire chart found above, assign, according to function, the 
cable wire colors to the thermostat wire legend provided below. If this 
is a new installation, record the cable wire colors in the thermostat 
legend provided below.

Note:

  There is no medium fan in the thermostat.  The wire for the 

medium fan needs to be tied off following standard procedures, unless 
used as a neutral.  

See Figure 1.

2-Pipe Fan Coil Installation:

Follow the instructions for a 4-Pipe installation with the following 
exceptions.

NOTE:  

Fan will cycle only with calls for heating or cooling.  

 

Continuous fan is not available on 2-pipe systems.

Old thermostat

wire function

Power Feed

Load Feed

Neutral

Heat
Cool

Low Fan

Medium Fan

High Fan

Cable

wire color

New thermostat

wire function

Control Feed

Load Feed

Neutral

Heat
Cool

Low Fan

High Fan

New thermostat

wire color

Black

Orange

White

Red

Blue

Yellow

Yellow w/Red Stripe

Cable

wire color

Diagnostic mode can be deactivated by 
changing the °F/°C slide switch.   

ECON

Economy Mode

Display

°F/°C

Diagnostic Mode:

Press and hold the "up" and "down" buttons 
together until "DIAG" appears on the display.  
Release the buttons. 

°F/°C

AUTO

DIAG

Diagnostic mode will alternately display setpoint 
and room temperature every 5 seconds.  
The setpoint temperature is displayed with 
"SETPOINT"

°F/°C

Current Setpoint

Display

AUTO

DIAG

SETPOINT

The room temperature is displayed with °F and 
"ROOM".  Both setpoint and room temperature 
displays will indicate the fan speed activity and 
"DIAG".

°F/°C

Room Temperature

Display

ROOM

AUTO

DIAG

Aquastat (mounted on water 
supply line) or season change 
switch

Wiring Diagram 2-pipe Fan Coil

Yellow  LOW

Red

Black

White

Yellow w/red stripe  HIGH

Blue

Valve

Line

Neutral

120VAC

Orange

Fan

Note:  Fan will cycle with
heat or cool only

Cool pipe
position

Hot pipe

position

Black

Control

Feed

Door Switch, Motion Detector Wiring Diagram 2-pipe Fan Coil

Yellow  LOW

Blue  COOL

Red  HEAT

White

Yellow w/red stripe  HIGH

Orange

Valve

Line

Neutral

120VAC

Fan

Motor

Door switch or motion detector control relay
must have a minimum of 10A inductive load 
rating.  In open position fan and valves will be 
deactivated.  In closed position fan and valves 
will be activated.

Aquastat (mounted on water supply line)
or season change switch