6. 

From the wire chart found in step 4, assign, according to function, 

 

the cable wire colors to the thermostat wire legend provided below.  

 

Note:  The control feed and the load feed will be connected together 

 

for the 4-pipe installation.  If this is a new installation, record the cable 

 

wire colors in the thermostat legend provided below.

 Note:

  There is no medium fan in the thermostat.  The wire for the 

 

medium fan needs to be tied off following standard procedures.

 

New thermostat

wire function

Control Feed

Load Feed

Common

Heat
Cool

Low Fan

High Fan

New thermostat

wire color

Red

Orange

Gray

White

Yellow

Green

Yellow w/Red Stripe

Cable

wire color

7. 

Connect the thermostat wires to the cable wires recorded in Step 6.

8. 

Push the wires into the junction box.  Tilt 

  the thermostat so that the bottom of the 
  thermostat is resting on the mounting tabs 
  of the mounting plate.  Push the top of the 
  thermostat towards the wall and secure into 
  place with the self-tapping screw as shown 
  to the right.

 

Standard
Junction
Box

9. 

Turn power on.

 

 At start up, the fan will automatically run

 

 for three minutes to cycle room air.

 

 

BASIC FUNCTIONS

Adjust Temperature Setpoint:

 

Press up button (     ) to raise the temperature (warmer)

 

Press down button (     ) to lower the temperature (cooler)

ECONOMY

Screw: 6/32 x 3/4"

Mounting Bracket

Standard
Junction
Box

5. 

Install the mounting bracket to the 

  junction box with the two long 
  mounting screws provided.  
  See mounting detail to the right.
 

Note:  

If application involves a 

  double ganged junction box, 
  a backplate will be required for a 
  complete installation.  
  Please consult your supplier.

Select Fan Operation:

 

Press fan button (      ) to select the following fan functions*

 

 

Continuous HIGH speed fan

  Continuous 

LOW 

speed 

fan

 

 

AUTO on/off with automatic speed change

  ECONOMY
 

 

*fan function sequence with auto as the starting point

Change Scale Units:

 

Slide the °F/°C switch to the left to display °F

 

Slide the °F/°C switch to the right to display °C

 

When the °F/°C switch is invoked, the thermostat will reset and  

 

display the default setpoint in the selected scale.  The default  

 

setpoint (unprogrammed) is 72.0°F or 22.0°C.

Cycle Timing: 

 (Anti-short cycle protection)

 

3 minute (minimum) dwell time in no-call states 

 

(both heat and cool).  

 

1 minute (minimum) dwell time in call states 

 

(both heat and cool).   

 

Temperature is sampled every 5 seconds.

9510-0611  Rev -
9-27-05

Check Low Fan Function:

  Press the fan button until the fan 
  indicator on the LCD moves to the 
  LOW  fan position.  
  Low speed fan should turn on immediately. 

 

Check High Fan Function:

  Press the fan button until the fan indicator on 
  the LCD moves to the HIGH fan position.  
  High speed fan should turn on immediately. 

 

Check Heating:
 

Press and hold the up button until the heat 

  symbol appears on the LCD.  Within 4 seconds 
  the heat valve should be activated.
 

Note:  

Room temperature must be below the 

  Comfort Conditioning Heating Limit 
 85°F 

(29.5°C) 

  for heating to become active.
 

Wiring Diagram 4-pipe Fan Coil

Green

White

Gray

Yellow w/red stripe 

Yellow

Heat

Valve

Feed

Common

24VAC

Cool

Valve

High

Fan

Relay

Low

Fan

Relay

Red

Orange

 

Red

Control

Feed

Door Switch, Motion Detector Wiring Diagram 4-pipe Fan Coil

Green

White

Orange Load Feed

Gray

Yellow w/red stripe  

Yellow

Cool

Valve

Heat

Valve

24VAC Feed

Common

24VAC

High

Fan

Low

Fan

Door switch or motion detector control relay
must have a minimum of 3A rating.  In open 
position fan and valves will be deactivated.  
In closed position fan and valves will be 
activated.

°F/°C

Fan

°F/°C

Fan

Indicator

°F/°C

Up

Button

Heat

Symbol

°F/°C

2

Содержание HS-4024U

Страница 1: ...S USE WIRE NUTS ON ALL WIRE CONNECTIONS User Note The top of this unit will become warm to the touch This is a normal operation Internal heating is employed to continuously convect air upward through the thermostat thereby improving room air temperature measurement Direct conflict with a downward ceiling fan or system fan air flow may result in false temperature reading Locate thermostat to avoid ...

Страница 2: ...wing fan functions Continuous HIGH speed fan Continuous LOW speed fan AUTO on off with automatic speed change ECONOMY fan function sequence with auto as the starting point Change Scale Units Slide the F C switch to the left to display F Slide the F C switch to the right to display C When the F C switch is invoked the thermostat will reset and display the default setpoint in the selected scale The ...

Страница 3: ...AC from Gray to Yellow B When thermostat is calling for Heating meter should read 24VAC from Gray to White When Heating is deactivated meter should read 0VAC from Gray to White C When thermostat is calling for High fan meter should read 24VAC from Gray to Yellow w Red Stripe When High fan is deactivated meter should read 0VAC from Gray to Yellow w Red Stripe D When thermostat is calling for Low fa...

Страница 4: ...l the heat symbol appears on the LCD Within 4 seconds the heat valve should be activated Note Room temperature must be below the Comfort Conditioning Heating Limit 85 F 29 5 C for heating to become active Check Cooling Press and hold the down button until the cool symbol appears on the LCD Within 4 seconds the cool valve should be activated Note Room temperature must be above the Comfort Condition...

Отзывы: