Basic safety notes 

 

The actuators may only be operated by skilled and authorized operating personnel. 

 

Make sure to follow all security advices mentioned in this manual, any national rules for accident prevention, as 
well as the owner´s instructions for work, operation and safety. 

 

The isolating procedures specified in these operating instructions must be followed for all work pertaining to the 
installation, commissioning, operation, change of operating conditions and modes, maintenance, inspection, 
repair and installation of accessories. 

 

Before opening the actuator cover, ensure that mains supply is isolated and prevented from unintended re-
connection. 

 

Areas that can be under voltage have to be isolated before working on them. 

 

Ensure that the actuators are always operated in faultless condition. Any damage or faults, and changes in the 
operational characteristics that may affect safety, must be reported at once. 

 

Danger signs 

The following warning symbols are used in this manual: 

 

Caution! There is a general risk of damage to health and/or properties. 

 

 

 

 

Danger! Electrical voltages may be present that are dangerous to life!  

There is a risk of damage to health and/or properties with danger to lives. 

 

Other notes 

 

The motor surface may have elevated temperature when servicing, inspecting or repairing it immediately after 
operation. Danger of burning the skin! 

 

Always observe the relevant operating instructions when fitting PS accessories or operating the actuator with 
PS accessories. 

 

Connections for signal in- and output are double isolated from circuits that can be under dangerous voltage. 

2.

 

Usage as per specification 

 

The PSR-E-C quarter turn actuators are exclusively designed as electric valve actuators. They are meant to be 
mounted on valves for motor-operation. 

 

Any other use is considered to be not in accordance with standard specification, and the manufacturer cannot be 
held liable for any damage resulting from it. 

 

The actuators may not be used outside the limits laid out in data sheets, catalogs and order documentation. 
Otherwise the manufacturer cannot be held liable for any resulting damage. 

 

Usage as per specification includes the observance of the operating, service and maintenance conditions laid 
down by the manufacturer. 

 

Not to be regarded as usage as per specification are mounting and adjustment of the actuator, and servicing. 
Special precautions have to be taken while doing this! 

 

The actuators may only be used, serviced and repaired by personnel that are familiar with them and informed 
about potential hazards. The specific regulations for the prevention of accidents have to be observed. 

 

Damages caused by unauthorized modifications carried out on the actuators are excluded from the 
manufacturer's liability. 

 

Supply voltage may be switched on only after properly closing the main cover or terminal box. 

 

 

 

Содержание PSR-E Series

Страница 1: ...Version 2019 08 08 2019 PS Automation GmbH Operating Instructions PSR E C ...

Страница 2: ...afety regulations PSR E C actuators are built to state of the art technology and are safe to operate Despite this the actuators may be hazardous if operated by personnel that has not been sufficiently trained or at least instructed and if the actuators are handled improperly or not used as per specification This may cause danger to life and limb of the user or a third party damage the actuator and...

Страница 3: ... after operation Danger of burning the skin Always observe the relevant operating instructions when fitting PS accessories or operating the actuator with PS accessories Connections for signal in and output are double isolated from circuits that can be under dangerous voltage 2 Usage as per specification The PSR E C quarter turn actuators are exclusively designed as electric valve actuators They ar...

Страница 4: ...adjustment Depending on the operating time of the actuator the handwheel is either permanently engaged or it has to be pushed down against a spring for manual operation A sticker on the actuator cover indicates the relevant mode for manual operation At motor operation the handwheel serves as running indicator Electrical wiring is done to a terminal block under the actuator cover 5 Operating condit...

Страница 5: ...d and secured against an accidental switching on Mains connection cables must be dimensioned suitably to accept the maximum current requirement of the actuator and correspond to IEC 227 and IEC 245 The yellow green coloured cables may be used only for connecting to earth When inserting cables through the cable connector ensure that the maximum bending radius for the cable is observed PSR E C elect...

Страница 6: ...hood is valid for the specific actuator For any optional extras see the individual wiring diagram in the related service instructions X1 Internal wiring X2 Internal wiring X3 Internal wiring X4 Potentiometer 1 for PSAP X5 1 Neutral X5 2 Motor phase to open X5 4 Motor phase to close X5 6 Thermo switch as potential free contact X5 7 Thermo switch as potential free contact X6 Position signal switches...

Страница 7: ...nnections X5 6 and X5 7 Maximum thermal switch loading The thermo switch can be loaded up to the maximum nominal value for the motor see motor nameplate When using the thermo switch as a potential free contact the switching signal must immediately stop the motor Re starting the motor is allowed only after the thermo switch has reset Failure to observe this warning may result in damage to the actua...

Страница 8: ...crew Pos Stop screw Pos Protection cap Figure 7 Mechanical stop 10 Adjustment of limit switches Figure 8 Setting the switching cams for stroke limit switches The standard limit switches serve to switch off the motor when the end positions are reached Additional limit switches are free of voltage and serve to indicate the valve position These are available as optional auxiliaries The switches are a...

Страница 9: ...necessary re adjust the limit switches 12 Maintenance The actuators are maintenance free if used under the operating conditions as stated in the data sheet The gearboxes are lubricated for lifetime and do not require further lubrication Caution During maintenance and repair the actuator must not be operated electrically 12 1 Cleaning The actuators should be cleaned dryly 12 2 Spare parts Defective...

Страница 10: ... Signal Switches Gold 2WE Gold Positioner PSAP Position Transmitter PSPT Space Heating HR Potentiometer PD Increased Enclosure IP Increase to enclosure IP67 available With power supply 24 VAC the open motor phase can produce voltages up to 35 V due to motor generated induction voltage ...

Страница 11: ...11 14 Declaration of conformity ...

Страница 12: ... 66 Fax 91 20 25 47 39 66 E mail sales ps automation in www ps automation in Great Britain IMTEX Controls Ltd Unit 5A Valley Industries Hadlow Road GB Tonbridge Kent TN11 0AH Phone 44 0 17 32 85 03 60 Fax 44 0 17 32 85 21 33 E mail sales imtex controls com www imtex controls com Italy PS Automazione S r l Via Pennella 94 I 38057 Pergine Valsugana TN Phone 39 04 61 53 43 67 Fax 39 04 61 50 48 62 E ...

Отзывы: