Setting the control functions
31
„Basic settings“ menu
Position Symbol
Description
Range
Factory
settings
Current
settings
1 = ProBus, for working with conexio
600
The change will not take effect until
after the controller is restarted.
* Position 16: Glycol types
Selection
Meaning
Selection
Meaning
0
Anro
6
Tyfocor L5.5
1
Ilexan E, Glythermin
7
Dowcal 10
2
Antifrogen L
8
Dowcal 20
3
Antifrogen N
9
Dowcal N
4
Ilexan E
10
Tyfocor LS
5
Ilexan P
7
Setting the control functions
The general control functions allow you to configure the settings for the charging of the
storage tanks. You can set the following control functions:
•
Charging principle
•
Pump control
•
"Tube collector" function.
7.1
Setting the charging principle
In order to optimise the energy output, you can choose from the following charging
principles:
•
"Temperature difference" charging principle
•
"Target temperature" charging principle
The charging principle is selected in the "Basic settings" menu with the following value:
•
P:4: Charging principle.
"Temperature difference" charging principle“
In the case of the "Temperature difference" charging principle, the solar circuit pump is
controlled in such a way that the temperature difference between the collector and the
storage tank is maintained at as constant a level as possible.
"Target temperature" charging principle
In the case of the "Target temperature" charging principle, the solar circuit pump is